Pre-Starting Belt Tension Checks

  8.  Always loosen tension enough to install belts 

without stretching, see figure 9.

  9.  For units with two groove pulleys, adjust so the 

tension is equal in both belts.

10.  If adjustments are made, it is very important to 

check the pulleys for proper alignment. Misaligned 
pulleys lead to excessive belt wear vibration, noise 
and power loss, see figure 10.

11.  For CWB units: Belt tension can be adjusted by 

loosening four fasteners on the drive frame, see 
figure 11. The motor plate slides on the slotted 
adjusting arms and drive frame angles in the same 
manner.

12a. Sizes 071-161:  Belts should be tensioned just 

enough to prevent slippage at full load. Belts 
should have a slight bow on the slack side while 
running at full load (see figure 12a).

12b. Sizes 180-540: Belt tension should be adjusted to 

allow 1/64 in. (0.397 mm) of deflection per inch of 
belt span. For example, a 15 in. (381 mm) belt span 

should have 15/64 in. (0.234 mm) (or about 1/4 in. 
(6 mm)) of deflection with moderate thumb pressure 
at mid-point between pulleys (see figure 12b).

13.  The adjustable motor pulley is factory set for the 

RPM specified. Speed can be increased by closing 
or decreased by opening the adjustable motor 
pulley. Two groove variable pitch pulleys must be 
adjusted an equal number of turns open or closed.

14.  Any increase in speed represents a substantial 

increase in the horsepower required by the unit.

15.   Motor amperage should always be checked to avoid 

serious damage to the motor when speed is varied.

Operation: CW/CWB

  1.  Before starting up or operating fan, check all 

fasteners for tightness. In particular, check the 
setscrews in wheel hub (and pulleys, if applicable).

  2.  While in the OFF position or before connecting the 

fan to power, turn the fan wheel by hand to be sure 
it is not striking the venturi or any obstacle.

  3.  Start the fan and shut it off immediately to check 

rotation of the wheel with directional arrow in the 
motor compartment, see figure 8.

  4.  When the fan is started, observe the operation and 

check for any unusual noises.

  5.  With the system in full operation and all ductwork 

attached, measure current input to the motor and 
compare with the nameplate rating to determine if 
the motor is operating under safe load conditions.

  6.  Keep inlets and approaches to fan clean and free 

from obstruction.

WARNING

Correct direction of wheel rotation is critical. 
Reversed rotation will result in poor air 
performance, motor overloading and possible 
burnout.

WARNING

The fan has been checked for mechanical noises at 
the factory prior to shipment. If mechanical noise 
should develop, suggested corrective actions are 
offered in the Troubleshooting section.

IMPORTANT

Over tightening will cause excessive bearing wear 
and noise. Too little tension will cause slippage at 
startup and uneven wear.

Figure 10

Do not force belt(s). Forcing the 
belt(s) will break the cords and 
cause belt failure

.

Belts

Figure 9

Slack

Side

Deflection

 

Figure 12a

 

Figure 12b

Fasteners

(4) *Fasteners

*Identical fasteners on 

opposing side must also 

be loosened.

Figure 11

Содержание Centrifugal Sidewall Exhaust Fans CW/CWB

Страница 1: ...urer s engraved metal nameplate containing the model number and individual serial number Only qualified personnel should install this fan Personnel should have a clear understanding of these instructi...

Страница 2: ...t be responsible for damage during storage These suggestions are provided solely as a convenience to the user Indoor The ideal environment for the storage of fans and accessories is indoors above grad...

Страница 3: ...petroleum solvent and clean with lint free cloths Polish any remaining rust from surface with crocus cloth or fine emery paper and oil Do not destroy the continuity of the surfaces Thoroughly wipe cl...

Страница 4: ...s to the support angles on top 13 Also horizontal alignment can be made by loosening the bearings from the bearing plate Removal of the entire power pack motor drives and wheel for maintenance or clea...

Страница 5: ...by the unit 15 Motor amperage should always be checked to avoid serious damage to the motor when speed is varied Operation CW CWB 1 Before starting up or operating fan check all fasteners for tightnes...

Страница 6: ...e program will help these units deliver years of dependable service Belt Bearing Maintenance CWB Unit 1 Belts tend to stretch after a period of time They should be checked periodically for wear and ti...

Страница 7: ...light duty in clean atmosphere Recommended Relubrication Frequency in Months NOTE If unusual environment conditions exist extreme temperature moisture or contaminants more frequent lubrication is requ...

Страница 8: ...actices for Users and Installers of Industrial and Commercial Fans provides additional safety information This publication can be obtained from AMCA International Inc at www amca org Troubleshooting W...

Отзывы: