Calculate

Number of Points is the number of flow reference points. Each point is 
one reference flow rate (determined by traverse testing or other) and 
the associated Vari-Green system flow rate. The traverse testing flow 
rate for these reference points is performed before entering this screen 
and is written down with the associated Vari-Green point (flow rate). For 
most applications, a minimum of two points (low and high flow rates) are 
recommended for an accurate Field Characterization. Three points may 
be required.
Electra Point refers to the flow rate measured by the transmitter, and 
Reference Point refers to the flow rate measured externally. Electra Point 
1 and Reference Point 1 will be the flow rates for the first test, Points 
2 for the second test and Points 3 for the third test. Best practice will 
be to go from the lowest to highest flow rates when inputting this data. 
Once all data has been entered and the

 ENT

 button is pushed for the 

final Reference Point, the Calculator will display the calculated gain and 
exponent values.

NOTE: Whenever a system is being retested in order to determine 
a new Field Characterization (K-factor), the existing Field 
Characterization should be turned off prior to testing.
Manual

Selecting Manual will allow inputting of externally determined Gain (K) 
and Exponent (E) values, where:
 

Flow (corrected) = K x Flow (uncorrected) ^ E

Note:  A Gain (K) only Field Characterization (K-factor) can be 
achieved with an exponent (E) value = 1.0.

SERVICE MENU

Total System Scan

Displays the current status of all of the system sensors, thus allowing 
the user to quickly verify all is operating properly. Expected (white) 
and Enabled (green) sensor values should be the same unless sensors 
have been intentionally Disabled (red). See below for sensor control. 
If Missing (yellow) is at a value other than zero, the transmitter is not 
communicating with the associated node.

Sensor Control

An enabled sensor will report measurement data to the Vari-Green 
transmitter. This is the default condition after initially powering the 
system. A disabled sensor will not report measurement data to the  
Vari-Green transmitter. Disabled sensors may have a malfunction that 
causes this condition. It may also be desirable to intentionally disable a 
sensor for troubleshooting purposes. A known bad or suspect sensor 
can be disabled to remove it from the flow and temperature averages 
until it can be evaluated and/or repaired if necessary.

Sensor Data Scan

Displays sensor number (Sen), power input to sensors (PWM), 
temperature difference between flow and temperature sensors (DELTAt), 
velocity (FPM), flow temperature sensor (FLOWt) and the reference 
temperature sensor (REFt).
This data display screen can be used to further evaluate and 
troubleshoot the system performance and the application 
characteristics; e.g., the individual sensor velocities and temperatures 
will provide comprehensive data regarding the flow profile measured. 

Characterization Calculator

 

ENT - Accept ESC - Leave UP/DN - Change

 

Number of Points:

 

1

 

300.0

 

400.0

 

Electra Point 1:

 

Electra Point 2:

 

Electra Point 3:

 

Reference Point 1:

 

Reference Point 2:

 

Reference Point 3:

Total System Scan

 

ESC - Leave

 

Expected

 

Missing

 

Enabled

 

Disabled

0

0

2

2

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

32

31

32

Sensor Control

 

ENT - Toggle ESC - Leave UP/DN - Select

 

Sensor 2:  Enabled

 

Sensor 1:  Disabled

Sensor Data Scan

 

ESC - Leave UP/DN - Page Scroll

Sen

PWM

DELTAt

FPM

FLOWt

REFt

1

8980

31.3

885.0

104.9

73.6

2

6813

35.0

382.0

108.2

73.2

3

0

0.0

0.0

0.0

0.0

4

0

0.0

0.0

0.0

0.0

5

0

0.0

0.0

0.0

0.0

6

0

0.0

0.0

0.0

0.0

7

0

0.0

0.0

0.0

0.0

8

0

0.0

0.0

0.0

0.0

9

0

0.0

0.0

0.0

0.0

10

0

0.0

0.0

0.0

0.0

Vari-Green® Transmitter

8

®

Содержание AMD-TD Series

Страница 1: ...y for the customer s failure to comply with these requirements If this product is used in a manner not specified in this manual the protection providied by this product may be impaired Regarding This Manual This manual should be passed on to the end user Before use read this manual thoroughly to comprehend its contents The contents of this manual may be changed without prior notice All rights rese...

Страница 2: ...s also measured via these sensors The Vari Green transmitter can receive up to 32 individual flow sensors measuring airflow in a single duct and it generates the outputs including network and analog signals which are conveyed to a local controller or BMS Physical installation details for the probe array or flow stations can be found in Greenheck s Installation Instructions Typical Vari Green Insta...

Страница 3: ...r APPROVALS UL 60730 PENDING BTL FCC Part 15 Subpart B Class A Device 2 1 PROBE ASSEMBLY INDIVIDUAL SENSOR ACCURACY Velocity 2 of reading from 0 5000 FPM Temperature 0 1 F Multi point NIST traceable calibration of both temperature and velocity SENSOR TYPE Her metically sealed precision matched thermistors with laser trimmed resistive heating element mounted in flow conditioning aperture Max number...

Страница 4: ... 4 POWER and SIGNAL CONNECTIONS NOTE The Vari Green transmitter terminal connections for power and signal wire are labeled on the board for installation convenience Power wiring is located at terminal strip J4 Signal wiring is located at terminal strip J1 The REMOVABLE terminal strips for power and signal are located in the lower portion of the transmitter and are accessible by opening the hinged ...

Страница 5: ... FPM set point drives display and output to zero Alarm Alert Configuration Configure alarm type upper and lower limits Network Configuration Configure network type baud rate and address information Field Characterization For information on field characterization please see section below SERVICE MENU SELECTION DESCRIPTION Password Configuration Enable disable and change password Total System Scan D...

Страница 6: ... ID can be entered through the Service Menu It is typically used to describe the transmitter location in the building Brightness Allows the user to set the brightness of the display in real time Inactivity Timeout The time period which holds the display in menu mode When the timer expires the display is returned to the main display screen showing the process values Analog Output Configuration The ...

Страница 7: ...nable Reg Alerts will turn ON OFF Enable Global Alerts will turn ON OFF Field Characterization Field characterization K factoring of a flow element is the adjustment of the flow measurement system to match a known reference measurement most commonly airflow traverse testing Field characterization is typically done when there is insufficient straight duct run or another issue that creates questiona...

Страница 8: ... See below for sensor control If Missing yellow is at a value other than zero the transmitter is not communicating with the associated node Sensor Control An enabled sensor will report measurement data to the Vari Green transmitter This is the default condition after initially powering the system A disabled sensor will not report measurement data to the Vari Green transmitter Disabled sensors may ...

Страница 9: ...xternal 24 VAC 24 VDC power source 1 Press the power button located on the bottom left corner of the front cover to turn the system ON 2 The display will show a loading bar After reaching 100 the display will indicate which sensors have been discovered for approximately 2 seconds Then the normal operating screen will be displayed The default normal operating screen will display Total Flow on the f...

Страница 10: ... controller ceases to receive valid airflow and or temperature signals make certain the following have been checked and confirmed The power wiring is securely connected to the proper terminals and is providing the intended 24V AC DC power The signal wiring is securely connected to the proper terminals The probe to probe and probe to transmitter cables and connections are properly connected and sec...

Отзывы: