background image

Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com

Printed in Malaysia

Warranties and Limitation of Liability  

DIP Switch Settings  

Troubleshooting  

Please refer to www.coopercontrol.com under the Legal section for our terms and conditions.

Checkout and Adjustment  

Issue

Possible Causes

Suggestions

Lights  

Will Not 

Turn ON  

automatically

Wall switch OFF

Turn wall switch ON

If low voltage switch option is used, lights  

may have been turned-off manually

Press low-voltage switch

Daylighting Feature Enabled

If all lights are required to turn ON adjust DIP  

Switch 10 and/or daylight potentiometer

Power interruption

Check incoming voltage and/or wiring

Lights  

Will Not  

Turn ON  

manually

Daylighting Feature Enabled

If all lights are required adjust DIP  

Switch 10 and/or daylight potentiometer

Power interruption

Check incoming voltage and/or wiring

If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879

Lights  

Will Not  

Turn OFF  

automatically

Override

Make sure sensor is not in Override Mode (DIP Switch 8 up)

Sensor installed close to an air vent 

Sensors should be installed 4-6 feet away  
from any air vent and out of heavy air flow

Sensor installed close to indirect lighting

Sensors should be mounted away from indirect lighting

Self-adjust

It may be possible for the unit to have self-adjusted  
the time delay to a 30 minute delay. If the lights do  

not turn OFF after 30 minutes follow next step

30 Minute Delay

Maximum time delay is 30 Minutes. Check DIP  

Switches to verify DIP Switch settings. If lights do  

not turn OFF at the set time delay, check next step

PIR activated by heat source other than occupant

Move DIP Switch 5 UP

Bypass

Check wiring to make sure sensor  

or switchpack are not bypassed

Lights  

Will Not  

Turn OFF  

automatically

Override

Make sure sensor is not in Override Mode (DIP Switch 8 up)

If lights will still not turn OFF, call Technical Services at 1-800-553-3879

Adjustments should be made with the HVAC system ON. Use only insulated tools to make adjustments.

Self-Adjust

Sensor is shipped in the Self-Adjust Mode. This applies to time delay and PIR sensitivity. In preparation for the 

Installer Test, the time delay is set to 15 seconds, after the sensor is installed, powered ON and has stabilized, the 

unit will time-out 15 seconds after the last motion detected. Coverage and sensitivity can be confirmed by watching 

the Red (PIR) indicator LEDs on the front of the sensor, while moving around the room.

1. Walk around the room and monitor LEDs. LEDs should only turn ON for one second with each motion. (If LEDs 

do not turn ON, go to Installer Adjustments - Sensitivity Adjustments Section)

2. Stand still six to eight feet away from the sensor for five seconds. LEDs should not turn ON. (If any LED turns 

ON, note LED and go to Installer Adjustments – Sensitivity Adjustment section)

3. Walk outside the room and wait 15 seconds for the lights to turn OFF. (If lights do not turn OFF go to Installer 

Adjustments Section)

4. Re-enter the room to activate sensor. (If lights do not turn ON go to Troubleshooting Section)

5. The unit will remain in Test Mode for 5

 

minutes then automatically exit Test Mode and go for 10 min. Time 

Delay User Mode setting.

Note:

 

To place into Test Mode, toggle DIP Switch 10 out of its current position, wait 3 seconds, and then back in to its original position. To 

force into 10 min User Mode move Dip Switches 1 and 2 down. (If DIP Switches 1 and 2 are already down, toggle DIP Switch 1 out of its current 
position, wait 3

 

seconds, and then back to its original position) While in Test Mode, the LEDs will flash once per 1/4 second.

Installer Adjustments  

Sensitivity Adjustments

PIR Sensitivity

1. Stand in different areas of the room and wave your hands.

2. If the Red LED does not turn ON, check for any obstructions.

3. Stand still six to eight feet away from sensor for five seconds. LED should not turn ON.

4. If Red LED turns ON without motion or is constantly ON adjust PIR sensitivity to 50% by moving DIP Switch 5 UP.

Hot

Neutral

Line

Load 1

Black

Red

Blue

Purple 

Gray 

Orange

Switchpack

Blue

Blue

**Hot

**Use Black Lead for 120VAC

Use Orange Lead for 277VAC

Cap Unused Lead

White

Hot

Neutral

Line

Load 2

Switchpack

Blue

Blue

**Hot

**Use Black Lead for 120VAC

Use Orange Lead for 277VAC

Cap Unused Lead

White

Yellow

Brown

Brown/White

Optional Greengate GMDS Switch- 

Blue Control Lead- Manual on/off

Red (15VDC)

Black(Common)

Blue (Control)

SENSOR WIRE LEAD LEGEND
Black   

(Common)

Red 

(10-30VDC)

Blue

(Control)

Yellow

(Control)

Brown

(Switch-Blue Lead Control)

Brown/White(Switch-Yellow Lead Control)
Sensor's Isolated Relay

Orange

(Normally Open)

Gray 

(Common)

Purple

(Normally Closed)

Red (15VDC)

Black(Common)

Blue (Control)

To Additional Switchpacks

10 switchpacks Maximum

Activation

Activation

PIR Sensitivity

Daylighting Mode

Lighting Sweep

Override

LEDs

10

9

8

7

50%

5

4

5 Minutes
15 Minutes
30 Minutes

Auto

Auto

Manual

Manual

DIP Switch

3

2

Power Pack One Power Pack Two

(-R model only)

(-R model only)

Full

Disable

Disable

Disable

Enable

Enable

Enable

Auto*

*Self-Adjusts to
10 min. user mode

Default =

Time Delay

1

Disable
Enable

6

Walk-Through Mode

Half
Full

1 2 3 4 5 6

7 8 9 10

One Sensor, Multiple Switchpacks

Field-of-view outside the space

1. Adjust PIR sensitivity to 50% by moving DIP Switch 5 up.

Daylight Adjustments

If this feature is not needed, leave the light level at maximum (fully CW).

The Daylighting feature (-R model only) prevents the lights from turning ON when the room is adequately illuminated 

by natural light. If there is enough light in the room regardless of occupancy, the sensor will hold the lights OFF. If there 

is not enough light in the room, the sensor will allow the lights to turn ON when occupied.

Full and Half Logic Modes

 (See DIP Switch legend):

In both Full and Half Logic modes, lights connected to the yellow control lead will not turn ON upon occupancy 

activation, should the ambient light level exceed the preset foot-candle level.

After activation:

Full Logic Mode – should the ambient light level exceed the preset foot-candle level, the lights connected to the 

yellow control lead will turn OFF. The lights will remain OFF, until the ambient light level falls below the set point.

Half Logic Mode – the output state of the yellow control lead will not change with ambient light changes, after 

occupancy activation. If the amount of natural light available rises above the setpoint, the daylight sensor will not turn 

the lights OFF while occupancy is being detected.

Note:

 Set the light level when the ambient light is at the level where no artificial light is needed. In order for this 

feature to function, the yellow control lead must be wired.

1. With the load ON, put the sensor into Test Mode. To place into Test Mode, toggle DIP Switch 10 out of its current 

position, wait 3 seconds and then back in to its original position.

2. Set DIP Switch 10 to Full or Half Logic Mode.

3. Set the light level to minimum (fully CCW).

4. Leave the room and let the sensor time-out so lights are OFF. Enter the space and lights should remain OFF.

5. Make sure not to block the sensor from the daylight source and adjust the light level potentiometer CW in small 

increments until the lights are ON. (Pause 5 seconds between each adjustment)

6. Once the lights are ON, the load connected to the sensor will not turn ON if light levels are above the  

current illumination.

Time Delay Adjustments

People who remain very still for long periods of time may need a longer time delay than the default setting of 10 

minutes. As long as Auto is enabled, the sensor will respond to each pair of false-OFFs with no normal OFF in between, 

by alternately making slight adjustments to either time delay (by 2 minute increments) or sensitivity, so there should be 

no need for manual adjustment.  If manual adjustment is desired, refer to Time Delay settings in DIP Switch legend.

Reset sensor time delay to factory settings by moving DIP Switches 1 and 2 down. (If DIP Switches 1 and 2 are 

already down, toggle DIP Switch 1 out of its current position, wait 3 seconds, and then back to its original position)

Automatic Mode

In Automatic ON Mode, the lights turn ON when a person enters the room. If optional momentary low voltage 

switches are used along with Automatic ON Mode, activating the switch(es) while the load is ON turns the load OFF. 

When the load is turned OFF manually, as long as the sensor continues to detect occupancy the loads stay OFF. After 

the time delay expires, the lights stay OFF and the sensor goes back to Automatic ON Mode. For wiring information for 

the optional momentary low voltage switch(es), please see the wiring section of the installation instructions.

Manual Mode

In Manual ON Mode, the optional momentary low voltage switch(es) is required to turn the load(s) ON. Once activated 

the sensor will maintain the lights ON until motion ceases and the time delay expires.  While the room is occupied the 

BAS relay remains active. After the time delay expires, the load(s) will automatically be turned OFF and the switch(es) 

must be used to turn the load(s) ON unless there is motion detected within the 10 second re-trigger period.

Lighting Sweep Option

If selected, this DIP Switch option forces an initial 60 second delay upon “power-up” to prevent false activation in 

buildings with computer control systems.

1. Move DIP Switch 9 UP.

Override

The Override setting allows the lights to remain ON in the unlikely event of sensor failure.

1. Move DIP Switch 8 UP.

While in Override Mode, the optional low voltage momentary switch(es) will toggle the lighting load(s).

Отзывы: