Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Printed in Malaysia
Warranties and Limitation of Liability
DIP Switch Settings
Troubleshooting
Please refer to www.coopercontrol.com under the Legal section for our terms and conditions.
Checkout and Adjustment
Issue
Possible Causes
Suggestions
Lights
Will Not
Turn ON
automatically
Wall switch OFF
Turn wall switch ON
If low voltage switch option is used, lights
may have been turned-off manually
Press low-voltage switch
Daylighting Feature Enabled
If all lights are required to turn ON adjust DIP
Switch 10 and/or daylight potentiometer
Power interruption
Check incoming voltage and/or wiring
Lights
Will Not
Turn ON
manually
Daylighting Feature Enabled
If all lights are required adjust DIP
Switch 10 and/or daylight potentiometer
Power interruption
Check incoming voltage and/or wiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override
Make sure sensor is not in Override Mode (DIP Switch 8 up)
Sensor installed close to an air vent
Sensors should be installed 4-6 feet away
from any air vent and out of heavy air flow
Sensor installed close to indirect lighting
Sensors should be mounted away from indirect lighting
Self-adjust
It may be possible for the unit to have self-adjusted
the time delay to a 30 minute delay. If the lights do
not turn OFF after 30 minutes follow next step
30 Minute Delay
Maximum time delay is 30 Minutes. Check DIP
Switches to verify DIP Switch settings. If lights do
not turn OFF at the set time delay, check next step
PIR activated by heat source other than occupant
Move DIP Switch 5 UP
Bypass
Check wiring to make sure sensor
or switchpack are not bypassed
Lights
Will Not
Turn OFF
automatically
Override
Make sure sensor is not in Override Mode (DIP Switch 8 up)
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Adjustments should be made with the HVAC system ON. Use only insulated tools to make adjustments.
Self-Adjust
Sensor is shipped in the Self-Adjust Mode. This applies to time delay and PIR sensitivity. In preparation for the
Installer Test, the time delay is set to 15 seconds, after the sensor is installed, powered ON and has stabilized, the
unit will time-out 15 seconds after the last motion detected. Coverage and sensitivity can be confirmed by watching
the Red (PIR) indicator LEDs on the front of the sensor, while moving around the room.
1. Walk around the room and monitor LEDs. LEDs should only turn ON for one second with each motion. (If LEDs
do not turn ON, go to Installer Adjustments - Sensitivity Adjustments Section)
2. Stand still six to eight feet away from the sensor for five seconds. LEDs should not turn ON. (If any LED turns
ON, note LED and go to Installer Adjustments – Sensitivity Adjustment section)
3. Walk outside the room and wait 15 seconds for the lights to turn OFF. (If lights do not turn OFF go to Installer
Adjustments Section)
4. Re-enter the room to activate sensor. (If lights do not turn ON go to Troubleshooting Section)
5. The unit will remain in Test Mode for 5
minutes then automatically exit Test Mode and go for 10 min. Time
Delay User Mode setting.
Note:
To place into Test Mode, toggle DIP Switch 10 out of its current position, wait 3 seconds, and then back in to its original position. To
force into 10 min User Mode move Dip Switches 1 and 2 down. (If DIP Switches 1 and 2 are already down, toggle DIP Switch 1 out of its current
position, wait 3
seconds, and then back to its original position) While in Test Mode, the LEDs will flash once per 1/4 second.
Installer Adjustments
Sensitivity Adjustments
PIR Sensitivity
1. Stand in different areas of the room and wave your hands.
2. If the Red LED does not turn ON, check for any obstructions.
3. Stand still six to eight feet away from sensor for five seconds. LED should not turn ON.
4. If Red LED turns ON without motion or is constantly ON adjust PIR sensitivity to 50% by moving DIP Switch 5 UP.
Hot
Neutral
Line
Load 1
Black
Red
Blue
Purple
Gray
Orange
Switchpack
Blue
Blue
**Hot
**Use Black Lead for 120VAC
Use Orange Lead for 277VAC
Cap Unused Lead
White
Hot
Neutral
Line
Load 2
Switchpack
Blue
Blue
**Hot
**Use Black Lead for 120VAC
Use Orange Lead for 277VAC
Cap Unused Lead
White
Yellow
Brown
Brown/White
Optional Greengate GMDS Switch-
Blue Control Lead- Manual on/off
Red (15VDC)
Black(Common)
Blue (Control)
SENSOR WIRE LEAD LEGEND
Black
(Common)
Red
(10-30VDC)
Blue
(Control)
Yellow
(Control)
Brown
(Switch-Blue Lead Control)
Brown/White(Switch-Yellow Lead Control)
Sensor's Isolated Relay
Orange
(Normally Open)
Gray
(Common)
Purple
(Normally Closed)
Red (15VDC)
Black(Common)
Blue (Control)
To Additional Switchpacks
10 switchpacks Maximum
Activation
Activation
PIR Sensitivity
Daylighting Mode
Lighting Sweep
Override
LEDs
10
9
8
7
50%
5
4
5 Minutes
15 Minutes
30 Minutes
Auto
Auto
Manual
Manual
DIP Switch
3
2
Power Pack One Power Pack Two
(-R model only)
(-R model only)
Full
Disable
Disable
Disable
Enable
Enable
Enable
Auto*
*Self-Adjusts to
10 min. user mode
Default =
Time Delay
1
Disable
Enable
6
Walk-Through Mode
Half
Full
1 2 3 4 5 6
7 8 9 10
One Sensor, Multiple Switchpacks
Field-of-view outside the space
1. Adjust PIR sensitivity to 50% by moving DIP Switch 5 up.
Daylight Adjustments
If this feature is not needed, leave the light level at maximum (fully CW).
The Daylighting feature (-R model only) prevents the lights from turning ON when the room is adequately illuminated
by natural light. If there is enough light in the room regardless of occupancy, the sensor will hold the lights OFF. If there
is not enough light in the room, the sensor will allow the lights to turn ON when occupied.
Full and Half Logic Modes
(See DIP Switch legend):
In both Full and Half Logic modes, lights connected to the yellow control lead will not turn ON upon occupancy
activation, should the ambient light level exceed the preset foot-candle level.
After activation:
Full Logic Mode – should the ambient light level exceed the preset foot-candle level, the lights connected to the
yellow control lead will turn OFF. The lights will remain OFF, until the ambient light level falls below the set point.
Half Logic Mode – the output state of the yellow control lead will not change with ambient light changes, after
occupancy activation. If the amount of natural light available rises above the setpoint, the daylight sensor will not turn
the lights OFF while occupancy is being detected.
Note:
Set the light level when the ambient light is at the level where no artificial light is needed. In order for this
feature to function, the yellow control lead must be wired.
1. With the load ON, put the sensor into Test Mode. To place into Test Mode, toggle DIP Switch 10 out of its current
position, wait 3 seconds and then back in to its original position.
2. Set DIP Switch 10 to Full or Half Logic Mode.
3. Set the light level to minimum (fully CCW).
4. Leave the room and let the sensor time-out so lights are OFF. Enter the space and lights should remain OFF.
5. Make sure not to block the sensor from the daylight source and adjust the light level potentiometer CW in small
increments until the lights are ON. (Pause 5 seconds between each adjustment)
6. Once the lights are ON, the load connected to the sensor will not turn ON if light levels are above the
current illumination.
Time Delay Adjustments
People who remain very still for long periods of time may need a longer time delay than the default setting of 10
minutes. As long as Auto is enabled, the sensor will respond to each pair of false-OFFs with no normal OFF in between,
by alternately making slight adjustments to either time delay (by 2 minute increments) or sensitivity, so there should be
no need for manual adjustment. If manual adjustment is desired, refer to Time Delay settings in DIP Switch legend.
Reset sensor time delay to factory settings by moving DIP Switches 1 and 2 down. (If DIP Switches 1 and 2 are
already down, toggle DIP Switch 1 out of its current position, wait 3 seconds, and then back to its original position)
Automatic Mode
In Automatic ON Mode, the lights turn ON when a person enters the room. If optional momentary low voltage
switches are used along with Automatic ON Mode, activating the switch(es) while the load is ON turns the load OFF.
When the load is turned OFF manually, as long as the sensor continues to detect occupancy the loads stay OFF. After
the time delay expires, the lights stay OFF and the sensor goes back to Automatic ON Mode. For wiring information for
the optional momentary low voltage switch(es), please see the wiring section of the installation instructions.
Manual Mode
In Manual ON Mode, the optional momentary low voltage switch(es) is required to turn the load(s) ON. Once activated
the sensor will maintain the lights ON until motion ceases and the time delay expires. While the room is occupied the
BAS relay remains active. After the time delay expires, the load(s) will automatically be turned OFF and the switch(es)
must be used to turn the load(s) ON unless there is motion detected within the 10 second re-trigger period.
Lighting Sweep Option
If selected, this DIP Switch option forces an initial 60 second delay upon “power-up” to prevent false activation in
buildings with computer control systems.
1. Move DIP Switch 9 UP.
Override
The Override setting allows the lights to remain ON in the unlikely event of sensor failure.
1. Move DIP Switch 8 UP.
While in Override Mode, the optional low voltage momentary switch(es) will toggle the lighting load(s).