Gree VRF Protocol Gateway
3
Fig.2 Communication method of BACnet and communication method network topology of
Modbus TCP
Internet topological graph statement:
485 bus
: L1 shown in Fig. 1 is 485 bus, one 485 bus can connect to 254 gateways at most.
Network table
: L1 shown in Fig. 2 is general network cable, the gateway can connect to BMS
via the network cable.
CAN1 network
: L3 shown in Fig. 1 and Fig. 2 is CAN1 bus, which consists of network and all
the outdoor units and indoor units of system; one CAN1 network can connect to 80 sets of indoor
units at most.
CAN2 network
: L2 shown in Fig. 1 and Fig. 2 is CAN2 bus, which consists of gateway and
master outdoor unit of system; one CAN2 network can connect to 16 sets of outdoor units and 255
sets of indoor units. When the quantity of outdoor units exceeds 16 or the quantity of indoor units
exceeds 255, it should be divided into two CAN2 networks.
System
: One system consists of one set of outdoor unit (one set of outdoor unit is a module
set, which can consist of 1~4 modules, that is, 1~4 sets of outdoor units) and its indoor unit.
Connectable quantity of units of gateway: One gateway can connect to 16 sets of outdoor
units and 255 sets of indoor units at most.