2 ODU LEDS TABLE
On the master ODU AP7, there are three LEDS and the flashing meaning is:
Flicker
Times
Green
Red
Yellow
1
Drive board
Outdoor unit is always at ON status
Fan ON
2
Reservation
Reservation
Compressor ON
3
Reservation
Oil return
IPM Overcurrent for fan
4
PC monitor
Defrosting
IPM Overcurrent for compressor
5
Indoor unit 1
Limited frequency reduction for IPM temperature protection
Fan IPM protection
6
Indoor unit 2
Limited frequency reduction for PFC temperature protection
Compressor IPM protection
7
Indoor unit 3
Limited frequency reduction for AC current protection
PFC overcurrent
8
Indoor unit 4
Limited frequency reduction for power protection
PFC protection
9
Indoor unit 5
Limited frequency reduction for discharge temperature
protection
Low voltage protection
10
Indoor unit 6
Limited frequency reduction for low pressure protection
High voltage protection
11
Indoor unit 7
Limited frequency reduction for high pressure protection
Low pressure protection
12
Indoor unit 8
Malfunction of discharge temperature sensor of
compressor 1
High pressure protection
13
Indoor unit 9
Malfunction of outdoor ambient temperature sensor
High-pressure switch protection
14
Indoor unit 10
Malfunction of outdoor defrosting temperature sensor
Drive charging circuit
malfunction of compressor
15
Indoor unit 11
Malfunction of suction temperature sensor
AC current protection
16
Indoor unit 12
Malfunction of sub-cooler liquid tube temperature sensor
Malfunction of EEPROM chip
17
Indoor unit 13
Malfunction of sub-cooler gas tube temperature sensor
18
Indoor unit 14
Malfunction of low-pressure sensor
19
Indoor unit 15
Malfunction of high-pressure sensor
20
Indoor unit 16
Fan protection
21
Indoor unit 17
Malfunction of discharge temperature sensor of
compressor 2
22
Indoor unit 18
Malfunction of outlet temperature of gas-liquid separator
Phase-lacking of PFC
23
Indoor unit 19
Phase-reversed of PFC
24
Indoor unit 20
25
26
27
28
Reservation
29
Power protection of compressor
30
Discharge protection for
compressor
31
Refrigerant-lacking protection
Содержание Ultra Heat GMV-VQ72W/A-F
Страница 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Страница 26: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 22 CHAPTER 2 INSTALLATION ...
Страница 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Страница 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Страница 120: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 116 CHAPTER 4 MAINTENANCE ...
Страница 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Страница 136: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 132 2 System high pressure protection E1 ...
Страница 137: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 133 3 System low pressure protection E3 ...
Страница 167: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 163 PFC board Drive board ...
Страница 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Страница 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Страница 207: ...Jf00303410 ...