Aptitude requirement for maintenance man(repairs should be done only
be specialists).

a. All the work men who are engaging in the refrigeration system should bear the

valid certification awarded by the authoritative organization and the qualification for 
dealing with the refrigeration system recognized by this industry.

b. It can only be repaired by the method suggested by the equipment’s manufacturer.

If it needs other technician to maintain and repair the appliance, they should be 
supervised by the person who bears the qualification for using the flammable refrigerant.

Safety preparation work before installation

     The safety must be inspected before maintaining the appliances with the flammable 
refrigerant for reducing the flammable hazard to the lowest.
     Work shall be undertaken under a controlled procedure so as to minimise the risk of a 
flammable gas or vapour being present while the work is being performed.

Environment checking

Detection of flammable refrigerants

      All maintenance staff and others working in the local area shall be instructed on the 
nature of work being carried out. Work in confined spaces shall be avoided. The area 
around the workspace shall be sectioned off. Ensure that the conditions within the area 
have been made safe by control of flammable material.
      The area shall be checked with an appropriate refrigerant detector prior to and during 
work, to ensure the technician is aware of potentially toxic or flammable atmospheres. 
Ensure that the leak detection equipment being used is suitable for use with all applicable 
refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
      No person carrying out work in relation to a refrigeration system which involves 
exposing any pipe work shall use any sources of ignition in such a manner that it may lead 
to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, 
should be kept sufficiently far away from the site of installation, repairing, removing and 
disposal, during which refrigerant can possibly be released to the surrounding space. 
Prior to work taking place, the area around the equipment is to be surveyed to make sure 
that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
      If any hot work is to be conducted on the refrigeration equipment or any associated 
parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry 
powder or CO

2

 fire extinguisher adjacent to the charging area. 

      Ensure that the area is in the open or that it is adequately ventilated before breaking 
into the system or conducting any hot work. A degree of ventilation shall continue during 
the period that the work is carried out. The ventilation should safely disperse any released 
refrigerant and preferably expel it externally into the atmosphere. 

      Under no circumstances shall potential sources of ignition be used in the searching 
for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) 
shall not be used.

Specialist’s Manual

'(

Содержание TOSOT MOMA-19

Страница 1: ...Thank you for choosing our product Please read this Owner s Manual carefully before operation and retain it for future reference Model Owner s Manual Original Instructions Local air conditioner...

Страница 2: ...This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or...

Страница 3: ...Explanation of Symbols Exception Clauses 0 01 2 3 0 DANGER WARNING CAUTION NOTICE...

Страница 4: ...mmable gas R290 Appliance shall be installed operated and stored in a room with a floor area larger than 15 m2 The appliance shall be stored in a room without continuously operating ignition sources f...

Страница 5: ...2 Safety Warning 0 q J...

Страница 6: ...er can only be used for family not for commercial industry Reserved space around the air c QVX YZ at least Do not operate the air conditioner at humid environment Please keep air inlet and air outlet...

Страница 7: ...1 2 Part s Name 4 5 NOTICE 6 7 2 1 8 2 9 5 4...

Страница 8: ...er cooling or heating mode press or button to increase or decrease set temperature by 1 C F Set temperature range is 16 C 30 C Under auto dry or fan mode this button is invalid NOTICE that you can ope...

Страница 9: ...dicator is bright Dual 8 nixie tube won t display Fan Under this mode the air conditioner only blow fan Fan indicator is bright Dual 8 nixie tube won t display Heat Cool Heat Unit only Under this mode...

Страница 10: ...Howtousetheremotecontroller 6 5 CAUTION 3 9 7 Using the remote controller...

Страница 11: ...5 4 5 Buttons on remote controller Introduction for icons on display screen 5 0 99 A 9 0 6 01 B 99 3 C 4 B 9 2 2D B 0 6 BB 6 5 6 6 B 0 B 99 2 3 E 6 F6 F F 6 2 8 9 2 G 9 0 B A G 6...

Страница 12: ...Introduction for buttons on remote controller Note H I I 0 H 3 I I J K H 3 3 0 99 A 1 2 8 3 B 3 B 3 2 L 9 0 8B M F 6 01 4 E F 3 3 2 3 2 L 9 0 8B M M 0 F 99 F H 9 7...

Страница 13: ...tons on remote controller 9 0 6 2 2D 8 9 6 3 B 99 7 B 99 B 0 2 2D A B 0 9 0 I 0 I 44F44 0 A B 8 4 6 B 0 8 4 4 4 2 2D 8 A A 5 8 3 A 8 G 9 0 F 0 99 8 8 G 9 0 F 0 99 G 9 0 8 2 L J K G 9 0 99 G 9 0 3 9 0...

Страница 14: ...troduction for buttons on remote controller 3 C 12 I I 13 G 9 0 F 2 L G 9 0 99 G 9 0 3 9 0 8B F 7 7 2 8B 2 F 7 I I N G 9 0 14 9 N F I I H 9 I WiFi I 9 9 I WiFi I 3 I BI I WiFi I 9 6 BB 10 6 BB 2 8B B...

Страница 15: ...ahrenheit and centigrade 99 I BI I I 0 I6BI A A Combination of TEMP and CLOCK buttons About Energy saving Function I B I I2 2DI 2 0 I I I5 I 9 Combination of TEMP and CLOCK buttons About 8 Heating Fun...

Страница 16: ...1 I 0 99I 2 I BI F 3 2 L 9 0 8B 3 IAI I I N 4 I9 0I F 5 I6 01I Operation guide A Replacement of batteries in remote controller O P IAI I I NOTICE H H 5 H H N H N A 2 1...

Страница 17: ...ntenance WARNING H C 2 H H Clean outer case and grille Clean outer case 7 Clean grille 3 3 4 Remove the filter Press the clasp as shown in the fig and then remove the filter 1 Pull out the filters 2 c...

Страница 18: ...Clean and Maintenance Clean heat discharge pipe 9 I I Checking before use season 2 2 2 2 2 Checking after use season B I I 2 Long time storage 7 F H 7 H H 2 Notice for recovery H H NOTICE...

Страница 19: ...6 7 7 H R H R H R H 7 R H R R H R H H R H R H R H R H H R H H H 5 H H 2 H H H H H 2 H H H H Malfunction analysis Is there malfunction for the circuit...

Страница 20: ...6 6 7 H R H R H 7 H F S2 4S2 H R H 3 H R H R H B H H H 7 0 7 7 H R H L H R L I I H R H 8 Malfunction analysis indoor temperature increase set temperature...

Страница 21: ...denser are H3 3 If the malfunction still occur please contact 1 Pour out the water inside chassis H8 2 If H8 still exits please contact professional person to maintain the unit ERROR CODE and high hum...

Страница 22: ...WARNING H H H C Selection of installation location Basic requirement F Requirement of air conditioner 6 9 L C 5 7 N 4 The appliance shall not be installed in the laundry Requirements for electric conn...

Страница 23: ...ist 20 Optional 2 Insect guard net Bracket Sponge A Sponge B The appliance shall be installed in accordance with national wiring regulations To be in compliance with IEC 61000 3 11 impedance value of...

Страница 24: ...with screws the direction of power cord hooks is as shown in following fig direction of power cord hooks is upward direction of power cord hooks is downward 21 Tools needed for installation Cross scr...

Страница 25: ...assis please follow the instructions bellow Turn the unit off and unplug from the electrical outlet Use a small pan or move the unit to a suitable place to drain the water Remove the pre installed dra...

Страница 26: ...hole Remove the continuous drain cap 1 by turning it counter clockwise then remove the rubber stopper 2 from the spout Screw the drain connector to included in the package the spout by turning clockw...

Страница 27: ...s less than 1m It is recommended to use it with shortest length When installing heat discharge pipe should be as flat as possible Don t prolong the pipe or connect it with other heat discharge pipe In...

Страница 28: ...25 should not be over 130cm from floor would easily cause malfunction Installation of Heat Discharge Pipe...

Страница 29: ...t discharge pipe 3 Insert joint A of heat discharge pipe the side with TOP is upwards into the groove until you hear a sound 4 Lead the exhaust hose outdoors Groove Casp The side with TOP is upwards 2...

Страница 30: ...V V 2 Y F 4 I 4 3 Sponge A 4 I 4 6 4 I 2 B Q 2SWLRQDO QVWDOODWLRQ LQ D GRXEOH KXQJ VDVK ZLQGRZ Installation of Heat Discharge Pipe...

Страница 31: ...B 5 6 6 F 5 I 54 I 44 3 6 6 4 I 5 I 5 I I F 4 I 4 5 I 54 3 Installation of Heat Discharge Pipe...

Страница 32: ...6 C 2 C Installation of Heat Discharge Pipe...

Страница 33: ...Insert joint A of heat discharge pipe the side with TOP is upwards into the groove until you hear a sound Groove Clasp Joint B C The side with TOP is upwards Slide and open the exhaust cover on the wi...

Страница 34: ...V 2 Y F 4 I 4 3 6 4 I 4 6 2 B 4 I Q 2SWLRQDO QVWDOODWLRQ LQ D VOLGLQJ VDVK ZLQGRZ Installation of Heat Discharge Pipe...

Страница 35: ...6 6 F 5 I 54 I 44 3 6 6 4 I 5 I B 5 I I F 4 I 4 5 I 54 3 Installation of Heat Discharge Pipe...

Страница 36: ...2 C 6 C Installation of Heat Discharge Pipe...

Страница 37: ...Insert joint A of heat discharge pipe the side with TOP is upwards into the groove until you hear a sound Groove Clasp Joint B C The side with TOP is upwards Slide and open the exhaust cover on the wi...

Страница 38: ...o the two ends of heat discharge pipe 2 Insert joint A of heat discharge pipe the side with TOP is upwards into the groove until you hear a sound 3 1roove 2lasp he side with TOP is upwards 3 Uoint A U...

Страница 39: ...te the joint D into 36 2 Insert joint A of heat discharge pipe the joint E side with TOP is upwards into the groove until you hear a sound Groove Wall Joint E Joint D Screw Heat discharge pipe Clasp T...

Страница 40: ...immovable cut a hole to install joint F and joint G tightly 3 Install the other side of heat discharge pipe clockwise into joint F Joint F Joint G Cut Inside Outside Joint A Heat discharge pipe Option...

Страница 41: ...38 4 Insert joint A of heat discharge pipe the side with TOP is upwards into the groove until you hear a sound Groove Clasp the side with TOP is upwards Installation of Heat Discharge Pipe...

Страница 42: ...from outdoors Remove joint A Press the clasp and lift joint A upwards to remove it Upwards Clasp Disassemble Joint A 39 Joint B C Disassembly of Heat Discharge Pipe Optional 1 Disassemble for installa...

Страница 43: ...assemble Joint A 40 2 Remove the window adapter Pull out and remove the window adapter by pushing down two PUSH markings and slide and close the exhaust cover in the window panel Optional PUSH PUSH Op...

Страница 44: ...semble Joint A Joint D Joint E 41 Optional 3 1 Disassembly for installation in window Optional 3 2 Disassembly for installation in the wall 1 Remove joint A 2 Remove joint D Press the clasp and lift j...

Страница 45: ...stallation in immovable window 1 Remove joint A Press the clasp and lift joint A upwards to remove it 3 When heat discharge pipe is removed Install the plastic cover into joint D in case of the insect...

Страница 46: ...select auto cooling drying fan or heating function and then check if the unit operates normally If ambient temperature is below 16 C the unit can t operate in cooling mode 3 When heat discharge pipe...

Страница 47: ...1 5 3 1 5220 7 03 6 1625 57 78 7 03 6 1625 57 28778 7 03 6 1625 57 7 5 02725 1 5 9 5 2 5 32 5 1 1 8 1 1 1 7 5 3 0 1 2 5 203 5 0 1 203 63 3 203 1 63 2 5 02 8 67 33 1 02725 7 5 9 6 7 2 1 1 02725 83 1 02...

Страница 48: ...of potentially toxic or flammable atmospheres Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants i e non sparking adequately sealed or intrinsical...

Страница 49: ...hall include initial safety checks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be connected to the circuit until it is satisfacto...

Страница 50: ...xtinguished remove refrigerant purge the circuit with inert gas evacuate purge again with inert gas open the circuit by cutting or brazing If a leakage of refrigerant is found which requires brazing a...

Страница 51: ...ompletion of charging but prior to commissioning A follow up leak test shall be carried out prior to leaving the site Ensure that contamination of different refrigerants does not occur when using char...

Страница 52: ...g order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs The recovery equipment shall be in good working order with a set of instructions concerning the equipment t...

Страница 53: ...66129930507 1 BB B B2 2 02B6 02 9 V838 F U W V 1 2 4 4 F X5 5 5 9 F X5 5 B F Y...

Отзывы: