background image

RS485 cable requirements

2

RS485 cable requirements

The communication is running on RS485 line and must be connected by cables specially
designed for this. These cables should conform demands by EIA-485 specification. (E.g.
see BELDEN 3016A)

It requires shielded twisted 2-pair cable or 1.5-pair cable. Recommended thickness

of cable lines is 0,2 - 0,32 mm

2

(24 - 22 AWG,

0.5 - 0.65 mm)

One twisted pair is used for connection of A and B. Remaining line(s) are used for

GND connection.

Shielding of the cable must be attached on the chassis of

one

of the devices. Best

practice is to attach it on the outmost indoor unit chassis.

6 Modbus Gateway

Содержание TD GUD 30/01

Страница 1: ...ease read this manual carefully before operation and retain it for future reference In case of lost manual please contact your local dealer or the manufacturer TD metal s r o at info tdmetal cz TD metal s r o reserves the right to interpret this manual which will be subject to any change due to product improvement without further notice ...

Страница 2: ......

Страница 3: ...iption and application 4 1 1 Package contents 4 1 2 Application 5 2 RS485 cable requirements 6 3 Configuration by wired controller 8 3 1 Activation of Modbus communication 8 3 2 Address settings of indoor unit 8 4 Connection 9 ...

Страница 4: ...ailable functions of your Gree air condi tioner via BMS WiFi module Premium or PC Please read this manual thoroughly for correct installation In case of installation problems please contact the manufacturer info tdmetal cz 420 585 237 171 1 1 Package contents 1 Modbus Gateway 2 Communication cable 4 Modbus Gateway ...

Страница 5: ...on bus Every device which is able to communicate over Modbus can be connected to common bus e g BMS system HMI system WiFi module Premium PC with proper software and RS 485 converter USB cable module Communication witk units is based on Modbus commands complete list of the commands is in the separate manual for GREE indoor units Connectable devices to Modbus Gateway bus Installation manual 5 ...

Страница 6: ...on E g see BELDEN 3016A It requires shielded twisted 2 pair cable or 1 5 pair cable Recommended thickness of cable lines is 0 2 0 32 mm2 24 22 AWG 0 5 0 65 mm One twisted pair is used for connection of A and B Remaining line s are used for GND connection Shielding of the cable must be attached on the chassis of one of the devices Best practice is to attach it on the outmost indoor unit chassis 6 M...

Страница 7: ... bus should have terminating resistor 120 Ω be tween A and B lines some devices do already have this implemented inside it can be activated by DIP switch or by software command see manual to specific device Meeting these requirements is essential for seamless communication partic ularly in environments with high surrounding electromagnetic interference i e substations server rooms utility rooms Ins...

Страница 8: ...te hold buttons FUNCTION and TIMER for more than 5 seconds 2 Press MODE multiple times to get to 10th settings parameter middle number by arrows choose option 01 and confirm by pressing SWING ENTER button 3 2 Address settings of indoor unit When there are several Modbus Gateways on the common bus each indoor unit has to be assigned with unique address Otherwise it is recommended to keep the default...

Страница 9: ... by plugging in the attached 6 pin cabel to brownish red socket of the mainboard labeled as COM BMS 9 Duct type unit Mainboard The other of the cable connect to Modbus Gateway socket labeled as UNIT Connect bus lines A B and GND If the Modbus Gateway is the last device on bus plug terminating resistor 120 Ω between the connectors A andB Installation manual 9 ...

Страница 10: ...Notes ...

Страница 11: ...Notes ...

Страница 12: ...TD metal s r o Werichova 1 Olomouc Czech republic 779 00 Tel 420 585 237 171 E mail info tdmetal cz www gree at www tdmetal cz ...

Отзывы: