MINI CHILLER CONTROL
16
Note
:
(1)
Turn On, Off Auxiliary Heater:
It is only available for heat pump unit. Press
CHECK
once to
enter Check mode. Press
▲
and
▼
to change check object, press
CHECK
again till the present
check object becomes “17”, value “17” switches between 01/03 (auxiliary heater on) and 00/02
(auxiliary heater off). That is 00 Off —>01 On —>00 Off, or 02 Off —>03 On —>02 Off.
(2)
Check Parameter:
After electrifying for 20s, press
QUIT
then
▲
to enter parameter checking
mode. Under this mode,
Auxiliary display area
shows the checking object,
Main display area
displays the value for the checking object. Press
▲
and
▼
to change the checking object. Press
QUIT
to quit from the check mode.
3.2.2 Display View
OFF
QUIT
ON
CHECK
MODE
NO. Name
Function
description
1
Running mode display
: cooling mode,
: heating mode,
: reserved
2
Temp display
It shows temperature value displayed at main display area.
3
Auxiliary display area
It contains 2 numbers and a comma, for showing temperature and
number of parameter at main display area. It only displays when under
Check mode and Parameter checking mode.
4 Main
display
area
It contains a minus, 2 numbers and 1 temperature unit, for displaying
value of temperature and parameter (temperature or time value) and error
code. When temperature value is displayed, it shows value in algorism
and temperature unit; when time is displayed, it shows algorism value but
no temperature unit (default unit is min); when it is code, it displays
specific error (refer to Malfunction Error List) but no temperature unit.
Individual temperature or parameter may exceed 99, then adopt AX for
Содержание T1/R22
Страница 1: ...Mini Chiller Service Manual T1 R22 50Hz GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Страница 10: ...GREE COMMERCIAL AIR CONDITIONERS MINI CHILLER 9 CONTROL...
Страница 11: ...MINI CHILLER CONTROL 10 UNITS CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Operation...
Страница 21: ...GREE COMMERCIAL AIR CONDITIONERS MINI CHILLER 20 INSTALLATION...
Страница 30: ...GREE COMMERCIAL AIR CONDITIONERS MINI CHILLER 29 MAINTENANCE...