TERRA INDOOR UNIT INSTALLATION

Terra Unit Mounting Bracket Diagrams

(inches)

9K and 12K Unit

18K Unit

24K Unit

Left

Right

(Rear piping hole)

(Rear piping hole)

Left

Right

(Rear piping hole)

Left

(Rear piping hole)

(Rear piping hole)

Right

(Rear piping hole)

10

POWER AND WIRING INSTALLATION 

Setting Master-Slave Indoor Units (24K Size Only)

Typically, the outdoor unit will select a master indoor unit upon power up. A single indoor unit may 
be programmed at the master zone. The master zone will always have priority over the other indoor 
units. Setting an indoor unit as the master zone is not required for system operation. 

To set an indoor unit as a master zone, locate master/slave configuration switches on the outdoor main 
control board. The switch locations 1, 2, 3 correspond to Indoor units (or Ports) 1, 2, 3. Select the master
zone by setting the desired switch to the “On” position. The other switches need to be set in the “Off” 
for slaves. By turning the switch from number to ON, the IDU with ON is set to be the master unit.

31

TWD-1518 install_printer.qxp_Layout 1  3/22/17  9:41 AM  Page 23

Содержание MULTI30HP230V1CO

Страница 1: ...tdoor coil compressor reversing valve or EEV is confirmed faulty by a technical support representative from the originating distributor within the first five 5 years of installation The replacement unit will be relative to the confirmed failed component not a complete system THIS WARRANTY DOES NOT COVER 1 Labor or other costs incurred for diagnosing repairing removing installing shipping servicing...

Страница 2: ...9 12 9 9 18 9 9 24 9 12 12 9 12 18 12 12 12 12 12 18 9 9 9 9 9 12 9 9 18 9 9 24 9 12 12 9 12 18 9 12 24 9 18 18 12 12 12 12 12 18 12 12 24 12 18 18 9 9 9 9 9 12 9 9 18 9 9 24 9 12 12 9 12 18 9 12 24 9 18 18 12 12 12 12 12 18 12 12 24 12 18 18 9 9 9 9 9 9 9 12 9 9 12 12 9 9 9 9 9 9 9 12 9 9 9 18 9 9 12 12 9 9 12 18 9 12 12 12 12 12 12 12 9 9 9 9 9 9 9 12 9 9 9 18 9 9 12 12 9 9 12 18 9 12 12 12 9 12...

Страница 3: ... Protection Low DC BusVoltage Protection Capacitor Charging Malfunction Compressor Phase Current Detection Malfunction DC BusVoltage Level Dropping Malfunction Current Detection Malfunction ReversingValve Malfunction InputCurrentDetection Malfunction The four way valve is abnormal Zero cross detection circuit malfunction for indoor unit Zero cross detection malfunction Indoor and outdoor units are...

Страница 4: ...Coil Freeze Protection Frequency Decrease Limit Mode Pump Down or Gathering Refrigerant Status High Indoor CoilTemperature in Heating Frequency Decrease Limit Mode Defrost Mode in Heating Compressor Overload Protection Compressor Overload Protection IPM Module Protection Indoor DC Fan Motor Malfunction Compressor De Synchronized Malfunction Power Factor Correction PFC Protection Compressor Demagne...

Страница 5: ... s 2 Indoor coil temperature sensor no calibrated 3 Refrigerant flow is restricted ex valve exv debris 1 Loose or bad connection between sensor and control board 2 Indoor ambient temperature sensor damaged 3 Control board malfunction 1 Loose or bad connection between sensor and control board 2 Indoor coil temperature sensor damaged 3 Control board malfunction 1 Loose or bad connection between sens...

Страница 6: ...8 30 0 2 20 30 000 R 410A 98 7 2 8 131 40 0 2 20 36 000 R 410A 128 8 3 65 131 40 0 2 20 42 000 R 410A 128 8 3 65 131 40 0 2 20 4 37 DIAGNOSTIC CODES X fan Mode Indoor Evap CoilTemperature Sensor Malfunction Gas valve temperature sensor is open short circuited System Configuration Malfunction Communication wire error or electronic expansion valve malfunction Wrongconnectionofcommunication wireormal...

Страница 7: ... Change the batteries The remote controller must be within 25 ft 7 5 m with no obstructions of the indoor unit If remote controller needs to be replaced contact a qualified service professional for assistance In the meantime use the Aux button to operate the system Cause There are a number of system functions that will prevent air flow Solution Check for the following In heating mode the indoor fa...

Страница 8: ...ode Otherwise contact a qualified service professional for assistance Cause There are a number of reasons for inadequate cooling or heating Solution Check the following Remove obstructions blocking airflow into the room Clean dirty or blocked air filter that is restricting airflow into the system Seal around door or windows to prevent air infiltration into the room Relocate or remove heat sources ...

Страница 9: ...displaying an error code on the indoor unit display Add batteries and press the ON button on the remote controller Verify the remote controller display turns ON and the indoor unit display is ON NOTE The Crown indoor units must first be synced to the remote controller See Crown Owner s Manual for instructions Press the Mode button to Cooling For each indoor unit adjust the room setpoint to bring t...

Страница 10: ...cuate using either deep vacuum or triple evacuation method 6 After evacuation is complete fully close the low side of manifold gauge and stop operation of vacuum pump 7 Disconnect charge hose from charge connection of the low side service valve 8 Fully open service valves B andA 9 Securely tighten caps of service valves Additional Charge TESTINGAND INSPECTION 33 Unit Size Total Piping Length ft m ...

Страница 11: ...uate each indoor unit one unit at a time Repeat the evacuation sequence for each indoor unit UNIT DAMAGE HAZARD Never use the system compressor as a vacuum pump It may result in equipment damage or improper system operation Refrigerant pipes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns The alternate triple evacuation method may be used if the procedur...

Страница 12: ...at the master zone The master zone will always have priority over the other indoor units Setting an indoor unit as the master zone is not required for system operation To set an indoor unit as a master zone locate master slave configuration switches on the outdoor main control board The switch locations 1 2 3 correspond to Indoor units or Ports 1 2 3 Select the master zone by setting the desired s...

Страница 13: ... Tightly connect main power wires to outdoor unit terminal block per wiring diagram above 7 Secure all wires inside wire clamp strain reliefs Verify wires are secure not loose and no external force on wires affects the connections at the terminals 8 Replace service panel on right side of the outdoor unit 9 Install Disconnect Switch Box per manufacturer s instructions National Electrical Code NEC a...

Страница 14: ... Record wire colors and terminal references for uses with Outdoor Unit wire connections 3 Connect wiring to indoor unit per system wiring diagram NOTE The indoor unit is powered from the outdoor unit depending on local code a disconnect switch may need to be installed to a power supply circuit 4 Replace field wiring cover and close front cover of indoor unit NOTE For wire connection instructions f...

Страница 15: ...door units with the greatest vertical distance from each other Measure the maximum vertical height H2 between those two indoor units from bottom of one unit to bottom of the other unit H2 INDOOR UNIT INSTALLATION L2 Ln L1 H1 H2 13 POWERANDWIRING INSTALLATION L1 L2 To the power supply L1 L2 C C D C cable T cable T cable Power cord L1 L2 To unit A Connecting cable To unit B Connecting cable To unit ...

Страница 16: ...farthest indoor units LS must be less than Verify your LS and LT maximum piping length measurements are less than the system limits The maximum total pipe length making up the system LT must be less than INDOOR UNIT INSTALLATION L L1 L2 LS Ln 14 POWERANDWIRING INSTALLATION To the power supply To unit B Power cord To unit A connecting cable L1 L2 connecting cable cable T cable C L1 L2 L1 L2 cable T...

Страница 17: ... the system limits L2 L3 Ln H1 H2 15 Oil return bend Indoor Outdoor 20 ft 30 ft Oil return bend Oil Return Bend When the outdoor unit is more than 30 feet above the indoor unit an oil return bend must be added for every 20 feet of connection pipe PIPING INSTALLATION 3 Apply a small amount of refrigerant oil to the flare connection on the refrigerant pipe 4 Properly align piping and tighten flare n...

Страница 18: ...cut and re flare refrigerant pipes if required An R410A FlaringTool is required for re flaring refrigerant pipes PIPING INSTALLATION 18 000 0 None 24 000 2 3 8 to 1 2 2 3 8 to 5 8 30 000 4 3 8 to 1 2 2 1 4 to 3 8 2 3 8 to 5 8 36 000 4 3 8 to 1 2 2 1 4 to 3 8 3 3 8 to 5 8 42 000 4 3 8 to 1 2 2 1 4 to 3 8 An adapter pipe may be required to transition from the indoor unit to the outdoor unit refriger...

Страница 19: ...nsulation to the entire drain line and joints to prevent sweating 3 The through wall hole for the drain hose must be lower than the indoor wall unit drain outlet for a functional gravity drain system 4 Install field supplied drain hose with a downward slope from the Indoor wall unit drain outlet to the drain hose outlet 5 Route the condensate drain hose in the safety location to dispose of the con...

Страница 20: ...unit 4 Verify the wall hangers or ground pad is level and meets all outdoor dimensional clearances Install Outdoor Unit Risers If the outdoor unit requires added elevation above the ground installing riser legs will provide a sturdy and stable solution Follow all instructions provided by manufacturer for installing riser legs to outdoor unit NOTE Riser legs will also help absorb vibrations and noi...

Страница 21: ... PIPING INSTALLATION 4 Properly align piping and tighten flare nut using a standard wrench and a torque wrench as shown in figure to the below Carefully tighten flare nuts to correct torque level referring to theTorqueTable above NOTE Over tightening may damage flare connections and cause leaks 5 Individually insulate each refrigerant line to prevent sweating Insulate pipes Indoor Unit Piping Tape...

Страница 22: ...ensate drain hose and wiring 5 Proper weather proofing of the wall surface and wall sleeve is essential to assure a trouble free installation Apply sealant caulking or equivalent weather proofing material around the perimeter of the wall sleeve interior exterior to eliminate outdoor air and water leaks into the living space Refrigerant Piping INDOOR UNIT INSTALLATION NOTE Expandable foam insulatio...