CAN1 network: network
③
shown in the figure is the CAN1 network, which is
consist of Modbus Gateway(Mini) and all IDUs and ODUs of the system. One
CAN1 network can be connected to maximum 80 IDUs. L3 shown in the network is
CAN1 bus.
CAN2 network: network
①
and
②
shown in the figure is the CAN2 network,
which is consist of Modbus Gateway(Mini) and main control ODU of the system.
One CAN2 network can be connected to maximum 16 systems and 255 IDUs. If
the system quantity exceeds 16 sets or IDU quantity exceeds 255 sets, it shall be
divided into two CAN2 network. L2 shown in the figure is CAN2 bus.
System: One system consists of one set of outdoor unit (one set of outdoor unit
is a module group consisting of 1~4 modules, that is 1~4 outdoor units) and its
connected indoor units.
Connectable unit quantity of Modbus Gateway(Mini): one Modbus Gateway(-
Mini) can be connected to maximum 16 systems and 128 IDUs. If IDU quantity
exceeds 128 sets, two Modbus gateways are needed.
Modbus Gateway(Mini)