5
SYSTEM REQUIREMENTS
REFRIGERANT CHARGE
ELECTRICAL REQUIREMENTS
PIPE SIZE
in (mm)
Notes: 1) System must be on a single dedicated circuit.
2) Main power is supplied to the outdoor unit.
3) Use table above to size over current protection.
4) Follow all local building codes and NEC (National Electrical Code) regulations.
Interconnecting Cable: Recommended cable - 14/4 AWG stranded bare copper conductors THHN 600V unshielded wire
Note: Use shield cable if installation is in close proximity of RF and EMI transmitting devices.
Condensate Drain Size: 5/8-in OD 7/16-in ID
Unit Size
Voltage
Liquid Line
Suction/Gas Line
(BtuH)
9,000
115v - 1ph 60hz
1/4 (6)
12,000
115v - 1ph 60hz
1/4 (6)
9,000
208/230v - 1ph 60hz
1/4 (6)
12,000
208/230v - 1ph 60hz
1/4 (6)
18,000
208/230v - 1ph 60hz
1/4 (6)
24,000
208/230v - 1ph 60hz
1/4 (6)
30,000
208/230v - 1ph 60hz
1/4 (6)
36,000
208/230v - 1ph 60hz
1/4 (6)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
3/8 (9.5)
1/2 (12)
5/8 (16)
5/8 (16)
5/8 (16)
Unit Size
Voltage
Min Line
Max Line
Max
(BtuH)
Length
Length
Elevation
9,000
115v - 1ph 60hz
10 (3)
66 (20)
12,000
115v - 1ph 60hz
10 (3)
66 (20)
9,000
208/230v - 1ph 60hz
10 (3)
49 (15)
12,000
208/230v - 1ph 60hz
10 (3)
49 (15)
18,000
208/230v - 1ph 60hz
10 (3)
82 (25)
24,000
208/230v - 1ph 60hz
10 (3)
82 (25)
30,000
208/230v - 1ph 60hz
10 (3)
98 (30)
36,000
208/230v - 1ph 60hz
10 (3)
98 (30)
Unit Size
Voltage
Refrigerant
Factory System
Additional
(BtuH)
Type
Charge oz (kg)
Charge oz/ft (g/m)
9,000
115v - 1ph 60hz
R410A
12,000
115v - 1ph 60hz
R410A
9,000
208/230v - 1ph 60hz
R410A
12,000
208/230v - 1ph 60hz
R410A
18,000
208/230v - 1ph 60hz
R410A
24,000
208/230v - 1ph 60hz
R410A
30,000
208/230v - 1ph 60hz
R410A
36,000
208/230v - 1ph 60hz
R410A
Unit Size
Voltage
Min Circuit
Max Overcurrent
Main Power
(BtuH)
Amps (MCA)
Protection (MOP)
Wire Size (AWG)*
9,000
115v - 1ph 60hz
12,000
115v - 1ph 60hz
9,000
208/230v - 1ph 60hz
12,000
208/230v - 1ph 60hz
18,000
208/230v - 1ph 60hz
24,000
208/230v - 1ph 60hz
30,000
208/230v - 1ph 60hz
36,000
208/230v - 1ph 60hz
*Main power wire from electrical panel to outdoor unit.
REFRIGERANT LINE LENGTHS
ft (m)
33 (10)
33 (10)
33 (10)
33 (10)
33 (10)
33 (10)
33 (10)
33 (10)
25 (7.5)
25 (7.5)
25 (7.5)
25 (7.5)
25 (7.5)
25 (7.5)
25 (7.5)
25 (7.5)
24.7 (0.7)
31.8 (0.9)
24.7 (0.7)
30.0 (0.9)
49.4 (1.4)
65.3 (1.9)
84.7 (2.4)
91.7 (2.6)
0.2 (20)
0.2 (20)
0.2 (20)
0.2 (20)
0.2 (20)
0.54 (50)
0.54 (50)
0.54 (50)
17
20
9
9
16
16
20
24
25
30
15
15
25
25
30
40
12/3
10/3
14/3
14/3
12/3
12/3
10/3
8/3