14
7.2.4
7.2.5
℃
.
7.3
7.3.1
FAN mode
Indoor fan motor runs at setting fan speed:
AUTO
LOW
MED
HIGH
Temp. setting range is 16
℃~
30
℃
.
Auto mode
When Tamb
>
2
℃
, it runs at cool mode, indoor setting temp. is25
Protection Functions
Indoor antifreezing protection
When 20
℃≤
Tamb
≤
2 6
℃
, it will run in dry mode, the inner setting temp. is 24
℃
.
When Tamb
<
2 0
℃
, it will run in HEAT mode, inner setting temp. is 20
℃
, Tamb
≥
24
℃
, quit HEAT mode.
If it is cooling only type unit, when Tamb
<
2 0
℃,
it will run in FAN mode, inner setting temp. is 24
℃.
When each mode start up, at least running for 30 seconds, Tamb then switch to AUTO mode running status.
Teva
<-
2
℃,
it shows E2, compressor stops running, outdoor and indoor fan motor,
swing motor keep original running; when Teva
>6℃,
com
pressor
has stopped 4min,
When in COOL mode, compressor started up 10min, when continuously 3min detected