King Series
-44-
compressor is started, it will not stop within 5 minutes unless it is plugged out.
c. overload protection
If it detect the system current surpass the designed 13 A for continuous 3 minutes, the machine
go into fan mode, when 3 minutes passed and it detect the current no more than 13 A, it will back
to original state. If it detects overloading states for 3 consecutive times within 30 minutes, the
machine stops, and must be restarted by remote controller.
d. locked motor protection
if it detects no feedback from the PG motor for continuous 15 seconds , the machine stops,
after 3 minutes delay, the machine backs to original state. If the motor be detected locked for 3
consecutive times, the whole machine stops and can not run again automatically.
2.dehumidifying mode
(1) the working conditions and control measures
a. If T
in
T
set
+2
, it is in cooling running, the indoor motor speed can be selected ,and outdoor
motor run at low speed.
b. If T
set
-2
T
in
T
set
+2
,it goes into dehumidifying running ,the indoor motor run at the low
speed, 6 minutes later the compressor stops, another 15 seconds later the outdoor fan stops
and another 30 seconds later, the indoor motor stops, 3 and a half minutes later, compressor
and outdoor fan run again ,indoor motor runs at the low speed, then the machine cycle the
above procedures repeatedly. outdoor motor runs at the low speed.
c. If T
in
T
set
-2
, compressor ,outdoor motor and indoor motor stop.
(2) in this mode, the reversing valve is inactive , the temp. setting range is 16~30
.
(3) Anti-freezing protection.
If T
indoor
T
set
+ 2 , it goes into cooling running , anti-freezing function is same with cooling
mode, but the compressor must stops for 4 minutes. when it goes into dehumidifying mode, com-
pressor runs 6 minutes , if it detects T
eva
0
,compressor stop, outdoor stop after 15 seconds,
indoor motor runs at low speed ,after 3 minutes delay ,and T
eva
10
,it will be back to its original
state.
3.heating mode
(1) the working conditions and control measures
a. If T
in
T
set
+2
, it goes into heating mode, reversing valve, compressor and outdoor motor
all work in the same time, indoor fan will run at the same procedures with anti cool air function.
b. If T
in
T
set
+ 4 , compressor stops first, 15 seconds late, outdoor motor stops ,but reversing
valve keeps working, indoor motor run at the procedures of blowing surplus heat.
c. If T
set
+ 2
< T
indoor
< T
set
+4
, keep the previous running state.
(2) in this mode, the temperature setting range is from 16~30
.
(3) The working conditions of auxiliary electric heater.
In heating mode, when compressor is working, indoor motor runs at high speed and middle speed
.if it detect T
eva
<48
for continuous 8 seconds and T
indoor
22
, electric heater will work ,if com-
pressor stop or indoor motor runs at low speed or T
eva
52
or T
indoor
25
or 10 seconds
Содержание KFR-35GW/J11
Страница 12: ...King Series 13 3 Performance curves figure 2...
Страница 13: ...King Series 14 figure 3...
Страница 14: ...King Series 15 figure 4...
Страница 15: ...King Series 16 4 Outlines and dimensions of indoor unit figure 5...
Страница 16: ...King Series 17 figure 6 Model KFR 45GW J11 12405...
Страница 17: ...King Series 18 5 Outlines and dimensions of outdoor unit figure 7...
Страница 18: ...King Series 19 Blank...
Страница 19: ...King Series 20 figure 8 6 Explosive view and spare parts list of indoor unit...
Страница 24: ...King Series 25 Blank...
Страница 25: ...King Series 26 Model KFR 45GW J11 12405 figure 9...
Страница 27: ...King Series 28 figure 10 7 Explosive view and spare parts list of outdoor unit...
Страница 33: ...King Series 34 figure 12 GSW18 22L B...
Страница 34: ...King Series 35 GSW18 22R B figure 13...
Страница 35: ...King Series 36 KF 26GW J11 figure 14...
Страница 36: ...King Series 37 KF 45GW J11 figure 15...
Страница 37: ...King Series 38 figure 16 GSW12 22R B KFR 35GW NJ11 KFR 26GW NJ11 KFR 35GW J11 KFR 35GW J11 12405...
Страница 38: ...King Series 39 KFR 26GW J11 KFR 26GW J11 12405 figure 17...
Страница 39: ...King Series 40 KFR 45GW J11 figure 18...
Страница 40: ...King Series 41 KFR 45GW J11 12405 figure 19...
Страница 41: ...King Series 42 KF 35GW A4 12206...