4.6 Error Code List
Error code
Meaning for Error
Method of Clearing Error
E1
Compressor 1 high-pressure protection
Press OFF to clear
E2
System-antifreeze protection
Resumes automatically
E3
Compressor 1 low-pressure protection
Press OFF to clear
E4
Compressor 1 exhaust temp. protection
Press OFF to clear
E5
Compressor 1 overload protection
Press OFF to clear
E6
Water pump overload protection
Press OFF to clear
E7
Water-flow on/off error
Press OFF to clear
E8
Fan 1 overload protection
Press OFF to clear
E9
System 1 anti high-temp.
Resumes automatically
b1
Compressor 2 high-pressure protection
Press OFF to clear
b2
System 2 antifreeze protection
Resumes automatically
b3
Compressor 2 low-pressure protection
Press OFF to clear
b4
Compressor 2 exhaust temp. protection
Press OFF to clear
b5
Compressor 2 overload protection
Press OFF to clear
b8
Fan 2 overload protection
Press OFF to clear
b9
System 2 anti-high temp.
Resumes automatically
F1
Antifreeze temp. sensor 1 error
Resumes automatically
F2
Antifreeze temp. sensor 2 error
Resumes automatically
F3
Defrost temp. sensor 1 error
Resumes automatically
F4
Defrost temp. sensor 2 error
Resumes automatically
F5
Exhaust temp. sensor 1 error
Resumes automatically
F6
Exhaust temp. sensor 2 error
Resumes automatically
F7
Outdoor ambient temp. sensor error
Resumes automatically
F8
Water-in temp. sensor
Resumes automatically
F9
Water-out temp. sensor
Resumes automatically
EC
Communication malfunction
Resumes automatically
1) Auto reset: It means after error is cleared and compressor stop protection time is satisfied, unit resumes
running automatically.
2) Manual reset: It means manually press OFF to clear error code first, and then press ON to make the unit
operates after malfunction is cleared.
3) When low-pressure protection is detected for 3 times in consecutive 30min, reset mode changes
to manual mode from auto mode. When overload at compressor and fan motor is detected for 3 times in
consecutive 30min, reset mode changes to manual mode from auto mode. Note:The installation of the
controller must be done by professionals.
Note
:
The installation of the controller must be done by professionals.