96
Installation and Maintenance
Service Manual
(1)
(2)
Terminal of
compressor
overload
protection
Terminal of
temperature
sensor
Terminal of
4-way valve
Terminal of
outdoor fan
Terminal of
compressor wire
PFC induction
wire
grounding wire
circlip
retainer
high and low
pressure switch
Remove the nut fixing axial flow blade and then
remove the blade.
Remove the grounding wire screw on the
electric box assy and then remove the
grounding wire. (See fig 1)
a
c
b
Disconnect the wiring terminals of reactor,
compressor, high and low pressure switch,
compressor overload protector, temperature
sensor, outdoor fan motor and 4-way valve. (See
fig 2)
N o t e : k e e p p r e s s i n g t h e c i r c l i p w h e n
disconnecting the wiring terminal of reactor;
keep pressing the retainer when disconnecting
other wiring terminals.
Remove the wire inside the wiring groove.
4. Remove axial flow blade
axial flow blade
nut
5.Remove electric box assy
Procedure
Step
Содержание GWH18QD-K3DNA1G
Страница 17: ...14 Technical Information Service Manual 963 892 700 396 560 341 396 3 2 Outdoor Unit Unit mm ...
Страница 86: ...83 Installation and Maintenance Service Manual GWH18QD K3DNB4G I GWH24QE K3DNB4G I ...
Страница 89: ...86 Installation and Maintenance Service Manual 10 2 Outdoor Unit ...