12. Flow chart for outdoor communitcation circuit detecting:
(1) Test the voltage between N point of wiring board and communication cable with universal meter. The voltage shall be
variable. Otherwise, it might be malfunction of mainboard of indoor unit, or malfunction of mainboard of outdoor unit, or wrong
wire connection of indoor and outdoor unit. Please ensure that there is no malfunction of mainboard of indoor unit, or wrong wire
connection of indoor and outdoor unit. After removing the malfunction of indoor unit, remove the malfunction of outdoor unit.
(2) Test the voltage of pin 1 and pin 2 of U132 with universal meter (voltage of both sides of R135). The voltage should be
variable. (Test 10) Test the voltage of pin 3 and pin 4 of U132 with universal meter (voltage of both sides of R1312). The voltage
should be variable. (Test 15) Otherwise, there is malfunction of mainboard of outdoor unit.
(3) Test the voltage of pin 3 and pin 4 of U131 with universal meter (voltage of both sides of R134). The voltage should be
variable. (test 11) Test the voltage of pin 1 and pin 2 of U132 with universal meter (voltage of both sides of C134). The voltage
should be variable. (test 12) Otherwise, there is malfunction of mainboard of outdoor unit.
(4) Test the voltage between pin 1 of R135 (white) and pin 1 of U4. The voltage should be variable. Test voltage between pin1 of
R131 (white) and pin 1 of U4 with universal meter. The voltage should be variable. Otherwise, there is malfunction of mainboard
of outdoor unit.