43
Troubleshooting
9.2.3 C5 malfunction
C5 is displayed
on the unit.
Is there jumper cap on
the controller ?
Install a matching
jumper cap
.
No
Is the jumper cap inserted
incorrectly or improperly?
Re-insert the
jumper cap.
The mainboard is
defined abnormal
replace it.
Yes
No
Yes
End
Is the
malfunction
eliminated?
Yes
No
Is the
malfunction
eliminated
No
Yes
Is the
malfunction
eliminated?
Replace the
jumper cap.
No
Yes
Possible causes:1.There is no jumper cap on the controller;2.Jumper cap is not inserted
properly and tightly;3.Jumper cap is damaged;4. Controller is damaged.See the flow chart
below: