(3) High temperature and overload protection diagnosis (AP1 hereinafter refers to the control board of the outdoor unit)
<" K
»)F"¼
»>""¼
»)¼
%" K
End
Yes
No
Yes
No
Yes
No
Overheat and high
temperature protection
Is outdoor ambient temperature higher than 53?
20 minutes after the complete
unit is powered off.
Is heat dissipation of the indoor unit
and outdoor unit abnormal?
Normal protection, please operate
it after the outdoor ambient temp-
erature is normalized.
Improve the heat
dissipation environ-
ment of the unit
Does the outdoor fan work normally?
1. Check if the fan terminal OFAN
is connected correctly
2. Resistance between any two
terminals is measure by an ohm
gauge and should be less than 1K
Ohm.
Replace the
control panel
AP1
Replace the fan
capacitor C1
Replace the
outdoor fan
Содержание GWC24ACE-K6DNA1 A/I
Страница 1: ...Service Manual Models Change for life GREE ELECTRIC APPLIANCES INC OF ZHUHAI...
Страница 36: ...33 Technical Information Service Manual...
Страница 37: ...34 Technical Information Service Manual...
Страница 102: ...99 Installation and Maintenance Service Manual P N...
Страница 105: ...102 Installation and Maintenance Service Manual 0 7AN P 31...
Страница 110: ...107 Installation and Maintenance Service Manual Procedure Step F c S E F B _ D _ F F J j 7 0...
Страница 111: ...108 Installation and Maintenance Service Manual Procedure Step Y F Y F Y F Y F S J D F F G...
Страница 113: ...110 Installation and Maintenance Service Manual Procedure Step S S S S B B J Y F J J Y F J Y F N J Y F...
Страница 114: ...111 Installation and Maintenance Service Manual 7 F J J S S S J J F J F J K _ E F J Procedure Step...
Страница 116: ...113 Installation and Maintenance Service Manual Procedure Step D F FA F FA B D F FA F FA D G J S K U J A F...