1. Air conditioner is type I electric appliance, thus please do conduct reliable earthing
measure.
2. The yellow-green two-color wire in air conditioner is earthing wire and cannot be used
for other propose. It cannot be cut off and be fix it by screw, otherwise it would cause
electric shock.
3. The earth resistance should accord to the National Criterion.
4. The user power must offer the reliable earthing terminal. Please don't connect the
earthing wire with the following place:
Tap water pipe.
Gas pipe.
Contamination pipe.
Other places that professional personnel consider them unreliable.
5
6. An all-pole disconnection switch having a contact separation of at least 3mm in all poles
should be connected in fixed wiring. For models with a power plug, make sure the plug
is within reach after installation
7. Including an air switch with suitable capacity, please note the following table. Air switch
should be included magnet buckle and heating buckle function, it can protect the
circuit-short and overload. (Caution: please do not use the fuse only for protect the circuit)
Air-conditioner
16A
25A
20A
Air switch capacity
. The model and rating values for fuses according the silk print on fuse cover or related
PCB board.
Notices for installation