,QVWDOODWLRQDQG0DLQWHQDQFH
6HUYLFH0DQXDO
Steps
Procedure
gas and liquid seperator
compressor
13.Remove gas and liquid separator
14.Remove compressor
15.Remove
valve support
、
electric expansion valve
、
gas valve and liquid valve
Loosen the two screws used for fixing the gas
and liquid separator, pull it upward and then
remove the gas and liquid separator.
Twist off the nuts used for fixing the compressor
withwrench, pull the compressor upward to
remove it.
liquid valve
gas valve
electric expansion valve
valve support
Unsolder the spot weld connecting capillary and
connecting pipe of liquid valve,remove 2 bolts fixing
the valve support with wrench.Remove 4 bolts
connecting gas and liquid valves,and valve
support and then remove the gas and liquid vales.
Twist off the screws used for fixing the , unsolder
the spot weld between
electric expansion valve
(notice: before soldering, the refrigerant should
be released completely), pull it outward and then
remove the
electric expansion valve
.