HEAT PUMP WATER HEATER (NORTHERN EUROPE) INSTALLATION
11
off and the outdoor fan will stop after 2s.
The condition of quit defrosting mode:
Under defrosting mode, if the continual defrosting time is over the set continual time of defrosting
(
default 8min
),
and the defrosting temperature is over the set stopping temperature(default 20
℃
) ,the
unit will restart running heating mode, and the 4-way valve will turn on and the outdoor fan will run.
3 WIRED CONTROLLER
3.1 Dimension
3.2 Function
3.2.1 Operation View