GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL
71
Attachment: Mapping Table of the Temperature
Sensor Resistance and Temperature
The following tables lists the mapping relationship between resistance of different temperature
sensors and temperature. The resistance for different temperature can be queried during maintenance.
Note: Due to variance in measuring method and temperature sensing, the sensor resistance may
deviate at ±5°C.
Mapping between the temperature
and resistance of 15 kΩ (outdoor ambient temperature
sensor)
Temperature (°C)
Resistance (kΩ)
Temperature (°C)
Resistance (kΩ)
-20
144
71
2.523
-19
138.1
72
2.439
-18
128.6
73
2.358
-17
121.6
74
2.28
-16
115
75
2.205
-15
108.7
76
2.133
-14
102.9
77
2.064
-13
97.4
78
1.997
-12
92.22
79
1.933
-11
87.35
80
1.871
-10
82.75
81
1.811
-9
78.43
82
1.754
-8
74.35
83
1.699
-7
70.5
84
1.645
-6
66.88
85
1.594
-5
63.46
86
1.544
-4
60.23
87
1.497
-3
57.18
88
1.451
-2
54.31
89
1.408
-1
51.59
90
1.363
0
49.02
91
1.322
1
46.8
92
1.282
2
44.31
93
1.244
3
42.14
94
1.207
4
40.09
95
1.171
5
38.15
96
1.136
6
36.32
97
1.103
7
34.58
98
1.071
8
32.94
99
1.039
9
31.38
100
1.009
10
29.9
101
0.98
Содержание GRS-1.5/D150ANbA-K
Страница 1: ...AIR SOURCE HEAT PUMP WATER HEATER Capacity 1 5 2 4kW Rated Frequency 50Hz Operation Range 7 45 ...
Страница 3: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 1 PRODUCT ...
Страница 11: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 9 CONTROL ...
Страница 25: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 23 INSTALLATION ...
Страница 47: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 45 COMMISSIONING and TRIAL RUN ...
Страница 55: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 53 MAINTENANCE ...
Страница 70: ...GREE AIR SOURCE HEAT PUMP WATER HEATER SERVICE MANUAL 68 UNIT MAINTENANCE ...
Страница 81: ...JF00303641 ...