Water-cooled Heat Recovery DC Inverter VRF
43
-
Debugging code
Progress code
State code
Meaning
progress
LED1
LED2
LED3
Code
Display
state
Code
Display
state
Code
Display
state
06_Detect
outdoor
components
db
ON
06
ON
OC
ON
No error is detected in outdoor
components. Start next progress.
If error is detected, system stays at current progress. Error has to be solved manually. Below is
relevant error:
-
Debugging code
Progress code
State code
Meaning
progress
LED1
LED2
LED3
Code
Display
state
Code
Display
state
Code
Display
state
06_Detect
outdoor
components
db
ON
06
ON
Error
code
ON
System detects error in outdoor
components.
Elimination methods of above error can be found in Troubleshooting.
Step10:
progress 07 is “Detect indoor components”
If no error is detected, system displays as below and go to next progress.
-
Debugging code
Progress code
State code
Meaning
progress
LED1
LED2
LED3
Code
Display
state
Code
Display
state
Code
Display
state
07_Detect
indoor
components
db
ON
07
ON
OC
ON
No error is detected in indoor
components. Go to next progress.
If error is detected, system stays at current progress. Error has to be solved manually. Below is
relevant error:
-
Debugging code
Progress code
State code
Meaning
progress
LED1
LED2
LED3
Code
Display
state
Code
Display
state
Code
Display
state
07_Detect
indoor
components
db
ON
07
ON
XXXX
or
Error
code
ON
System detects error in indoor
components.
XXXX is the project no. of the faulted IDU. 3s later, relevant error code is displayed. For example,
IDU no. 100 has d5 error, then LED3 displays: 01 (2s later) 00 (2s later) d5, and repeat again.
Elimination methods of above error can be found in Troubleshooting.
Step 11:
progress 08 is “Confirm preheated compressor”
If more than 8h of preheat time is detected, system displays as below and go to next progress.