Multi Variable Air Conditioners Ducted Type Indoor Unit
7
4.1.2 Suspend the indoor unit
(1) Drill bolt holes and install bolts
1) Stick the reference cardboard on the installation position; drill 4 holes according to the
hole site on the cardboard as shown in fig 4.1.2; diameter of drilling hole is according to
the diameter of expansion bolt and the depth is 60-70mm(2-3/8~2-3/4 in.), as shown in
fig 4.1.3.
Fig 4.1.2 Fig 4.1.3
2) Insert the M10 expansion bolt into the hole and then knock the nail into the bolt, as
shown in fig 4.1.4, and then remove the paper pattern.
Note
:
The length of bolt depends on the installation height of the unit, bolts are field supplied.
Fig 4.1.4
(2) Install the indoor unit temporarily
Assemble suspension bolt on the expansion bolt, attach the hanger bracket to the suspension
bolt. Be sure to fix it securely by using a nut and washer from upper and lower sides of the hanger
bracket. The washer fixing plate will prevent the washer from falling.
NOTES!
①
Before operation, please prepare all pipelines (connection pipe, drainage hose) and
wires (connection wire for wired controller, connection wire for indoor unit).
②
When drilling holes on ceiling (air return outlet or air outlet), you can need to reinforce
the ceiling to prevent vibration. For detailes, please consult user or builder.
③
If the strength of the ceiling is not good, please install a beam bracket, and then put
the unit on the beam bracket.
(3) Adjust the unit to the right position.
(4) Check the level of the unit.