Multi Variable Air Conditioners Ducted Type Indoor Unit
18
Fig.5.5.1
6 Setting of External Static Pressure
Working range for external static pressure of this series of duct type unit is 0 Pa~80 Pa. For
corresponding external static pressure to the respective static pressure notch please see as below. The
setting of static pressure for indoor fan can be done via wired controller. For specific setting method
please see the Wired Controller Instruction Manual.
Applicable to: GMV-ND30~48PLS/C-T(U)
Static pressure notch for indoor fan
3
4
5
6
7
External static pressure (Pa)
0
30
50
65
80
Note: The defaulted static pressure notch for all models at ex-factory is 5.