Multi Variable Air Conditioners Ducted Type Indoor Unit
6
3.4 Wiring Requirements
(1) Power Cord Size and Air Switch Capacity
Model
Power Supply
MCA(A)
MOP(A)
GMV-ND18PHS/A-T(U)
208/230V-1ph-60Hz
1.2
15
GMV-ND24PHS/A-T(U)
1.2
15
GMV-ND30PHS/A-T(U)
1.8
15
GMV-ND36PHS/A-T(U)
1.8
15
GMV-ND42PLS/A-T(U)
2.0
15
GMV-ND48PHS/A-T(U)
2.0
15
(1)
Use copper wire only as unit’s power cord. Operating temperature should be within its rated
value.
(2) If the power cord is more than 15 m (49-1/4 ft.) long, please increase properly the sectional
area of power cord to avoid overload, which may cause accident.
(3) Above selection requirements: Power cord size is based on BV single-core wire (2~4pc) at
40° (104°F) Ambient temperature when laying across plastic pipe. Air switch is D type and used
at 40°C (104°F). If actual installation condition varies, please lower the capacity appropriately
according to the specifications of power cord and air switch provided by manufacturer.
(4) Install cut-off device near the unit. The minimum distance between each stage of cut-off
device should be 3 mm (1/8 in.) (The same for both indoor unit and outdoor unit).