DC Inverter Multi VRF System
4
If the ODU is totally surrounded by walls, please refer to the following figures for space dimension:
Unit: mm (inch)
Fig. 2
Dimension
A
Allow for wall finishing
B
Allow for floor finishing
Min.(mm/inch)
Min. (mm/inch)
Max. (mm/inch)
No Accessories
6.35(1/4)
6.35(1/4)
—
With Subbase
45(1-3/4)
89(3-1/2)
127(5)
With Lateral Duct
19(3/4)
6.35(1/4)
—
NOTE
If more than one accessory is to be used, use the maximum dimension. If the wall thickness is more
than 350mm(13-3/4inch) - (A +6.35mm(1/4inch)), a sleeve extension must be used.
3.3 Piping Work Requirements
Refer to the table below for piping work requirements:
R410A Refrigerant System
Outer diameter (mm/inch)
Wall thickness(mm/inch)
Φ6.35(1/4)
≥0.8(1/32)
Φ9.52(3/8)
≥0.8(1/32)
Φ12.7(1/2)
≥0.8(1/32)
Φ15.9(5/8)
≥1.0(1/25)
Φ19.05(3/4)
≥1.0(1/25)
4 Installation Instructions
NOTE
Graphics here are only for reference. Please refer to actual products. Unspecified dimensions are all
in mm/inch.