< S695: 

A

 >

FOR SERVICE PERSONNEL ONLY

Indoor Unit / Outdoor Unit

RAS-S10H2 / RAC-S10H2
RAS-S14H2 / RAC-S14H2

• 

• 

Carefully read through the procedures of proper 
installation before starting installation work.
The sales agent should inform customers regarding 
the correct operation of installation.

( M a r k                     i s   e x c l u s i v e   u s e   t o o l   f o r  R410A)                               
Screwdriver    •    Measuring Tape    •    Knife    •    Saw
• ø65mm  Power  Drill    •    Hexagonal  Wrench  Key
(     4mm) • Wrench (14,17,19,22mm)     Gas leakage
Detector • Pipe Cutter • Putty • Vinyl Tape • Pliers  • 
Flare Tool                Vacuum Pump Adapter              Manifold Valve
   Charge Hose    Vacuum Pump

Tools Needed For Installation Work

SAFETY PRECAUTION

• Read the safety precautions carefully before operating the unit.

The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

WARNING .......... Incorrect methods of installation may cause death or serious injury.
CAUTION

.......... Improper installation may result in serious consequence.

Make sure to connect earth line.
This sign in the figures indicates prohibition.

Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of
the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual.

WARNING

Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the
installation work yourself.

Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause
water leakage, electric shock and fire.

Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may
collapse and impose danger.

Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing
with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and
fire may occur due to the use of low quality wire or improper work.

Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the
conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the
terminal base. Improper insertion and loose contact may cause over-heating and fire.

Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or
stronger vibration may occur.

Be sure to use the specified piping set for R410A. Otherwise, this may result in broken copper pipes or faults.

When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R410A)
does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally
which could result in a rupture and injury.

Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may
occur.

After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the
room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.

Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.

Be sure to connect the earth line from the power supply wire to the outdoor unit and between
the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the
telephone unit. Improper earthing may cause electric shocks.

When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe.
If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a
pressure in the freezing cycle system will build up steeply, causing an explosion or injury.

When installing the unit, be sure to install the refrigerant pipe before starting the compressor.
If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the
pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.

A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the
outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed.
Without a circuit breaker, the danger of electric shock exists.

Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire
if flammable gas leaks around it.

Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your funiture.

An IEC approved power cord should be used. Power cord type: NYM.

INDOOR UNIT

 WARNING

THE CHOICE OF MOUNTING SITE

 

(Please note the following matters and obtain permission from customer before installation.)

• The unit should be mounted at stable, non-vibratory location 

which can provide full support to the unit.

 CAUTION

OUTDOOR UNIT

 WARNING

 CAUTION


Names of Indoor Components

No.

Item

Qty

Hanger

Screw for Hanger

Holder for Remote 
Controller

AAA size Battery

Screw for holder of 
Remote Controller

Remote Controller

Insulation sheet

Bush

Drain Pipe

Switch Cover

(4.1 x 32)

(3.1 x 16)

1

2

3

4

5

6

7

8

9

0

-

1

6

1

2

2

1

1

1

1

1

1

above 

0.9 m

above 

1.6 m

Direction of Piping

Connection

(unit : mm)

Figure showing the Installation 
of Indoor and Outdoor Unit.

INDOOR UNIT

1

Installation of Hanger, Wall Penetration and Installation of Protection Pipe

 CAUTION

Direct Mounting On The Wall

• Please use hidden beams in the wall to hold the hanger.

Procedures of Installation and Precautions

• Procedures to fix the hanger.

1.

2.

3.

• Procedures to fix the holder of remote control.

1.

2.

Wall Penetration and Installation of Protection Pipe

 WARNING

2

Installation Of The Indoor Unit

Holder

 PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)

   Preparation


    Installation

• Insert the pipe through the wall hole.

1

2

 PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)

Preparation

Changed of Drain Hose and Installation Procedures.

 CATION


Cutting Low Cover bush

 CAUTION

INSTALLATION  AFTER CONNECTION OF REFRIGERATING PIPES

THE CONNECTION OF REFRIGERATING PIPE DURING 
THE INSTALLATION OF INDOOR UNIT

Preparation To Install Refrigerating Pipes

below
5mm

Please bend at a small
radius to form an arc

Installation


4

Installation of Drain Hose

 CAUTION

CAUTION

Cable drawer (right side)

3

Heat Insulation and Finish of the Piping

The components of 

9

 & 

0

 are included 

in the package of the outdoor unit.

The Length of Indoor Unit 

Connecting Cord

No nearby heat source and no obstruction near the air 
outlet is allowed.
The clearance distances from top, right and left are 
specified in figure below.
The location must be convenient for water drainage and 
pipe connection with the Outdoor unit.
To avoid interference from noise, please place the unit 
and its remote controller at least 1m from the radio and 
television.
To avoid any error in signal transmission from the remote 
controller, please put the controller far away from high-
frequency machines and high-power wireless systems.

The Outdoor unit must be mounted at a location which can 
support heavy weight. Otherwise, noise and vibration will 
increase.

Do not expose the unit under direct sunshine or rain. 
Besides, ventilation must be good and clear of obstruction.
The air blown out of the unit should not point directly to 
animals or plants.
The clearances of the unit from top, left, right and front are 
specified in figure below. At least two of the above 
sides must be open air.
The installation height should be at least 2,300 mm or more 
from the floor.
Be sure that the hot air blown out of the unit and noise do 
not disturb the neighbourhood.
Do not install at a location where there is flammable gas, 
steam, oil and smoke.
The location must be convenient for water drainage.
Place the Outdoor unit and its connecting cord at least 1 m 
away from the antenna or signal line of television, radio or 
telephone. This is to avoid noise interference.

When the power is 
supplied from the 
indoor unit, pull the 
power cable from the 
cable drawer at the 
right or left side of 
the indoor unit. 

Backward piping 
from left

There are 6 directions allowed, 
namely, backward piping, 
backward piping from left, 
horizontally piping from right, 
horizontally piping from left, 
vertically down from right, vertically 
down from left.

Dimension of Mounting 

Stand of the Outdoor unit

The indoor piping should be 
insulated with the enclosed 
insulation pipe. (If the insulator is 
insufficient, please use commercial 
products.)

The connection of insulated drain 
hose.

Please use insulated drain hose for 
the indoor piping (commercial 
product)

The refrigerating machine oil is 
easily affected by moisture. Use 
caution to prevent water from 
entering the cycle.
The difference in height between 
the indoor and outdoor unit 
should be kept below 10m.
The connecting pipe, no matter 
big or small, should all be 
insulated with insulation pipe and 
then wrapped with vinyl tape. 
(The insulator will deteriorate if 
it is not wrapped with tape).

The refrigerating pipe should be adjusted to fit into 
the hole on the wall and then ready for further 
connection.
The terminals of 2 connected pipes must be covered 
with insulator used for terminal connection. Then the 
pipes are wrapped with insulation pipe.
Connect the connecting cord after removing low 
cover.
(Refer to "CONNECTION OF POWER CORD")
After adjustment, fit the connecting cord and pipes 
into the space available under the unit. Use holder to 
hold them tight.
Holder can be attached at the either of 2 places. 
Please select the easier position.

The refrigerating pipes and connecting cord 
transform and are attached.

While installing the pipe from the right, left or 
bottom side, use a knife to cut openings as 
shown in figure. Then smoothen the edges of 
openings with a file.

Connect connecting cord.
Pull out the pipe, connecting cord and drain hose.

The upper part of the Indoor unit is hanged on the 
hanger.
The projection at the lower part of the Indoor unit is 
hooked onto the hanger.

Hang the indoor unit onto the hanger. Use the temporary stand 
at the back of the Indoor unit to push its lower part 15cm 
forwards.

Place the drain hose through the hole on the wall.
Wrap the refrigerating pipes with insulation pipe after 
connecting refrigerating pipe.
Connect the connecting cord after removing low cover. 
(Refer to "Connection of Power Cord")
After adjustment, the connecting cord and refrigerating pipes 
are placed into the space available under the Indoor unit.
The projection of Indoor unit must hook to the hanger.

The connected terminals should be completed sealed 
with heat insulator and then tied up with rubber strap.
Do not tie the terminals with the tape too tight.
If any clearance or over-tightening may cause 
condensation.
Please tie the pipe and power line together with vinyl 
tape as shown in the figure showing the installation of 
Indoor and Outdoor units.
To enhance the heat insulation and to prevent water 
condensation, please cover the outdoor part of the 
drain hose and pipe with insulation pipe.
Completely seal any gap with putty.

Pull this to the front during 
the connection of refrigerating 
pipe to ease task.

Be sure that the drain hose is 
not loosely connected bend or 
proper condition like left figure.

You are free to choose the side (left or right) for the installation of drain 
hose. Please ensure the smooth flow of condensed water of the Indoor 
unit during installation. (Careless may result in water leakage.)

The rubber strap used for fixing the insulator 
should not be tied with great force. Otherwise, 
this will damage heat insulation and causes 
water condensation.
Please pull the lower part of the Indoor unit 
outwards to check if the unit is hooked onto 
the hanger. Improper installation may cause 
vibration and noise.
Transform the piping while holding down the 
lower portion of pipe-support by hand.

Be sure that the wire is not 
in contact with any metal in 
the wall. Please use the 
protection pipe as wire 
passing through the hollow 
part of the wall so as to 
prevent the possibility of 
damaged by mouse. 
Unless it seals completely 
any air with high humidity 
flows from outdoor and any 
dew may drop.

Remove low cover
Insert drain cap up to the 
location securely till the 
cap stops.

Insufficient insert may 
result in water leakage.

Exchange the location of drain hose and drain cap while installing the pipe from the left side as 
shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.

Please use pliers to pull out the drain cap. 
(This is an easier way to remove the drain 
cap).

Push the pipe deeply until the insulating 
section of the drain hose end gets over 
the rib at the indoor unit side.

Drain layout of 
backward piping

Connecting cords, pipe and 
drain hose must be laid 
together with Vinyl tape.

Drill a ø65mm hole on wall which is 
slightly tilted towards the outdoor side. 
Drill the wall at a small angle.
Cut the protection pipe according to the 
wall thickness.
Empty gap in the sleeve of protection 
pipe should be completely sealed with 
putty to avoid dripping of rain water into 
the room.
Please ensure smooth flow of water 
when installing the drain hose. Improper 
installing may wet your funiture.
An IEC approved power cord should be 
used. Power cord type: NYM.

Fix the hanger on wall with 
4.1 x 32 screw
(As shown in figure below)

Push plug into the holes. 
(As shown below)

Push plug into the holes. 
(As shown below)

Drill holes on wall.
(As shown below)

Drill holes on wall.
(As shown below)

Screw the hanger at the 
positions possibly near the 
upper and lower hooks where 
the indoor unit is hung. Use 4 or 
more screws to fix the hanger.

The draining of the water container inside the Indoor unit can be done from the left. 
Therefore the hanger must be fixed horizontally or slightly tilted towards the side of 
drain hose. Otherwise, condensed water may overflow the water container.

HITACHI SPLIT-UNIT AIR CONDITIONER 

INSTALLATION MANUAL

  CAUTION

Purifying Filter

=

1

3

Remote 
Control
Holder

 Plug

5

 Screw

Wall hole

Pipe

Drain hose

Cable

1

2

Hanger

Projection

Hanger

Refrigerating 
Pipe

Protection 
Pipe

Drain Hose Connecting Cord

Wall hole

Weight

Line

Hanger

Level

2

 Screw for Hanger

450mm

400mm
316mm

125mm

41mm

45mm

ø65mm

199mm

280mm

65mm

390mm

80mm

530mm

780mm

10mm

45mm

ø65mm

42mm

44mm

125mm

20mm

Drain Hose

Drain Hose

Visible outline of the
outdoor unit

Wall hole

32mm

Wall

ø4.8mm

1

 Hanger

2

 Screw

Wall

above 50mm

4.1 x 32 screw

Ceiling

20mm

ø4.4mm

Wall

Seal with
putty

Protection
pipe

Sleeve of
protection
pipe

Seal with
putty

Outdoor

Indoor

2-5mm

WALL

Pipe

Rubber strap tied 
with great force

Pipe 
support

Transform after 
bending downward.

Drain cap

Drain Hose

Drain cap

Rib at the Indoor unit

Condensed 
water pond

Bending upwards

Condensed water 
pond

Ditch

Insulation material for pipe 
connection

Sleeve of 
protection pipe

Putty

Putty

Wall hole

Pipe

Drain hose

Cable

Drain layout of backward piping from left

Heat 
insulation pipe

Refrigerating 
pipe

Connecting 
cord

about 15cm

Hook

Projection

Protection 
pipe

Connecting cord

Holder

Connected 
section

Drain hose

The end of the refrigerating pipes are at 
locations marked with “    ” symbol.

0.85m

Openings

Openings

Connecting cord

Drain hose

Pipe

Holder

Insulation pipe (must be wrapped 
with vinyl tape at every 120 mm)

Inner diameter 16mm

5

3

4

7

Plug
(Procure locally)

1

2

6

above 
50mm

 above 50mm

 above 50mm

about 300mm

about 0.45m

must not bend

Be sure to
completely
seal any gap
with putty.

2,300 mm or more

above 100mm

 above 300mm

 above 50mm

give clearance
as wide as
possible

above 200mm

Maximum pipe length 20m

above 200mm

Mounting
Stand

330

310

(10)

10

500

35

50

12

125

Used in 
horizontal piping

above 50 mm when 
installed on the 
ceiling of balcony

Insulating 
section of the 
drain hose end

Lift the body 
of the unit 
upwards and 
then force it 
downwards.

(Procure locally)

(Procure locally)

Plug

Содержание RAC-S10H2

Страница 1: ...t 2 300 mm or more from the floor Be sure that the hot air blown out of the unit and noise do not disturb the neighbourhood Do not install at a location where there is flammable gas steam oil and smoke The location must be convenient for water drainage Place the Outdoor unit and its connecting cord at least 1 m away from the antenna or signal line of television radio or telephone This is to avoid ...

Страница 2: ... the body of the unit and terminal cover the low cover Remove the cover from the terminal base and screw the cable WARNING The naked part of the wire core should be 10mm fix it to the terminal tightly Then try to pull the individual wire to check if the contact is tight Improper insertion may burn the terminal Be sure to use only wire specified for the use of air conditioner Please refer to the ma...

Страница 3: ... máxima del tubo 20 m más de 50 mm si se instala en un balcón UNIDAD INTERIOR 1 Perforación de la pared e instalación del soporte de pared y la tubería de protección PRECAUCIÓN El drenaje del depósito de agua de la unidad interior se puede hacer por la izquierda Por lo tanto el soporte de pared debe fijarse horizontalmente o ligeramente inclinado hacia el lado de la manguera de drenaje De lo contr...

Страница 4: ... en la que está instalada la unidad interior y compruebe que el mando a distancia funciona correctamente Remoción de la cubierta frontal Inserción de la cubierta frontal Mando a distancia Tornillo 2 piezas Soporte del mando a distancia ÚLTIMA ETAPA DE LA INSTALACIÓN 1 Fuente de alimentación y prueba de funcionamiento ADVERTENCIA No manipule la clavija del cable de alimentación ni extienda el cable...

Страница 5: ... Utilizzare il flessibile di scarico isolato per la tubazione interna prodotto commerciale oltre 100mm oltre 300mm oltre 50mm lasciare la massima distanza possibile oltre 200mm Assicurarsi di sigillare completamente qualsiasi pertura con il mastice Lunghezza massima tubo 20 m UNITÀ INTERNA 1 Installazione di sospensore foratura del muro e tubo di protezione CAUTELA Il drenaggio del contenitore del...

Страница 6: ...o anteriore verso di sé come mostrato nella figura e rimuovere il coperchio Asta Telecomando Vite 2 pezzi Supporto per il telecomando Valvola Foro Reggispinta CAUTELA Non toccare il bocchettone di aspirazione la superficie inferiore o l aletta di alluminio dell unità esterna In caso contrario potrebbero verificarsi lesioni personali 9 BOCCOLA 9 BOCCOLA Spinta Spinta FORD DI SCARICO Diametro estern...

Страница 7: ... ñ ñ ñ ñ ÂÍ ÚÙ Ì Ù 9 0 ÂÚÈ Ï Ì ÓÔÓÙ È ÛÙË Û ÛÎÂ Û ÙË Â͈ÙÂÚÈÎ ÌÔÓ Â ÂÚ ÙˆÛË ÙÚÔÊÔ ÔÛ fi ÙËÓ ÂÛˆÙÂÚÈÎ ÌÔÓ ÙÚ ÍÙ ÙÔ Î ÏÒ ÈÔ ÚÂ Ì ÙÔ fi ÙË ı ÛË ÙÔ ÛÙË ÂÍÈ ÛÙËÓ ÚÈÛÙÂÚ ÏÂ Ú ÙË ÂÛˆÙÂÚÈÎ ÌÔÓ ˆÏËÓÒÛÂÈ Ì ΠÙ ı ÓÛË ÚÔ Ù Ûˆ fi ÚÈÛÙÂÚ À Ú Ô Ó 6  ÈÙÚ fiÌÂÓ ΠÙ ı ÓÛÂÈ ÁÈ ÙÈ ÛˆÏËÓÒÛÂÈ ÚÔ Ù Ûˆ ÚÔ Ù Ûˆ fi ÚÈÛÙÂÚ ÔÚÈ fiÓÙÈ fi ÂÍÈ ÔÚÈ fiÓÙÈ fi ÚÈÛÙÂÚ Î Ù ÎfiÚ Ê ÚÔ Ù Î Ùˆ fi ÂÍÈ Î Ù ÎfiÚ Ê ÚÔ Ù Î Ùˆ fi ÚÈÛÙÂÚ ÈÎfiÓ ÁÈ ÙËÓ ...

Страница 8: ...ÔÏÔÁÈÎ ÂÚÁ Û Â Ô Ú ÂÈ Ó ÂÎÙÂÏ ÛÂÈ Ô ÂÏ ÙË ÂÚÈÏ Ì ÓÔ Ó ÙÈ ÂÚÁ Û Â Ì ÚÈ ÙËÓ Â͈ÙÂÚÈÎ ÌÔÓ Ÿ Ô Ë ÚÔ ÂÓ Â Ó È ÛÙ ıÂÚ Û ÓÈÛÙ Ù È Ë Ú ÛË Ú ıÌÈÛÙ Ù ÛË ÂÁÎ Ù ÛÙ ÛË ÙË Â͈ÙÂÚÈÎ ÌÔÓ Ú ÂÈ Ó Á ÓÂÈ Û ÛËÌÂ Ô Ô Ó Êı ÓÂÈ ÙÔ Î ÏÒ ÈÔ ÙË ÁÚ ÌÌ ªËÓ ÔÛ Ó ÚÌÔÏÔÁ Ù ÙÔ ÛÌ ÙÔ Î Ïˆ Ô ÚÂ Ì ÙÔ Î È ÌËÓ ÙÂÓÙÒÓÂÙ ÙÔ Ì ÎÚ Î ÏÒ ÈÔ Ê ÛÙ ÚÎÂÙfi Ì ÎÔ ÛÙÔ Î ÏÒ ÈÔ Î È ÌËÓ ÛΠ٠ÂÛË ÛÙÔ ÛÌ ÁÈ Ù Ùfi Ì ÔÚÂ Ó Ô ËÁ ÛÂÈ ÛÂ Î Î Â Ê ªËÓ ÛÙ...

Страница 9: ...uit commercial Plus de 100mm Plus de 300mm Plus de 50mm distance de dégagement maximale souhaitée Plus de 200mm Veiller à boucher complètement tous les espaces au mastic Longueur maximale du tuyau 20 m APPAREIL D INTÉRIEUR 1 Installation de la plaque de fixation percée du mur et pose de la gaine de protection ATTENTION Vous pouvez vidanger le conteneur d eau de l appareil intérieur par la gauche P...

Страница 10: ...ne parvenez pas à fixer le panneau latéral en raison du câble de connexion enfoncez ce dernier dans le sens du panneau avant Veillez à ce que les crochets du panneau latéral soient fermement fixés sinon une fuite d eau peut survenir et occasionner un court circuit ou des pannes Le câble de connexion ne doit pas toucher la vanne de service ni les tuyaux Il chauffe en cours de fonctionnement Vérific...

Отзывы: