DC Inverter Multi VRF System
19
4.4 Disassembly of Compressor Feet
In order to prevent unit from damage during transportation, 2 metal pieces are fitted to outdoor
unit’s compressor feet before unit leaves factory. See Fig.23.
Fig. 23
When installing the unit, metal pieces for transportation must be removed. Then fasten the
binding nuts again and wrap back soundproofing cotton.
NOTE!:
If unit runs with metal pieces fitting on, compressor will shake abnormally and unit’s operating
life will be shortened.
4.5 Vacuum Pumping, Refrigerant Adding
4.5.1 Vacuum Pumping
(1) Outdoor unit has been charged with refrigerant before delivery. Field-installed connection
pipe needs to be charged with additional refrigerant.
(2) Confirm whether outdoor liquid and gas valves are closed.
(3) Use vacuum pump to withdraw the air inside indoor unit and connection pipe from the
outdoor valve, as shown below.
Fig. 24