U-Match Series Service Manual
70
MAINTENANCE
1 TROUBLE TABLE
1.1 Main Control Malfunction
Table 1 Fault Display on Indoor Wired Controller
No.
Error
code
Malfunction
name
Origin of
malfunction
signal
Control description
1
E1
High pressure
protection
High pressure
switch
When outdoor unit detects the high pressure switch is cut off for 3s
successively, high pressure protection will occur. All the loads (except
the 4-way valve in heating mode) will be switched off. In this case, all
the buttons and remote control signals except ON/OFF button will be
disabled and cannot be recovered automatically. Switch off the unit or
re-energize the unit after cutting off power to eliminate this protection.
2
E2
Freeze
protection
Indoor
evaporator
temperature
sensor
If detecting that the evaporator temperature is lower than protective
temp. Value after the unit has been running for a period of time under
cooling or dry mode, the unit will report this fault, in which case the
compressor and outdoor fan motor will be stopped. The unit will not run
until evaporator temperature is higher than the protective temp. value
and the compressor is stopped for 3min.
3
E3
Low pressure
protection
Low pressure
switch
If it is detected within 30s successively that the low-pressure switch is
cut off under ON or standby state, the unit will report low pressure
protection. If the fault occurs successively 3 times within 30min, the unit
cannot be recovered automatically.
Refrigerant
lacking
protection
If the unit reports system refrigerant lacking within 10min after turning
on the unit, the unit will stop operation. If the fault occurs successively 3
times, the unit cannot be recovered automatically.
Refrigerant
recycling mode
If enter refrigerant recycling mode through special operation, E3 will be
displayed. After exiting refrigerant recycling mode, the code will
disappear.
4
E4
Compressor
high discharge
temperature
protection
Compressor
discharge
temperature is
high
If outdoor unit detects that the discharge temperature is higher than
protective temp. Value, the unit will report high discharge temperature
protection. If the protection occurs over 6 times, the unit cannot be
recovered automatically. Switch off the unit or re-energize the unit after
cutting off power to eliminate this protection.
6
E6
Communicatio
n malfunction
Communicatio
n between
indoor and
outdoor
mainboard
If the outdoor unit does not receive data from indoor unit,
communication malfunction will be reported. If there is communication
abnormity between display board and indoor unit, communication
malfunction will be reported too.
9
E9
Full water
protection
Water level
switch
If cut-off of water level switch is detected for 8s successively once
energized, the system will enter full water protection. In this case,
switch off the unit and then switch it on to eliminate this malfunction.
10
F0
Malfunction of
indoor ambient
temperature
sensor at air
return port
Indoor ambient
temperature
sensor
If the indoor ambient temperature sensor is detected of open circuit or
short circuit for 5s successively, indoor ambient temperature sensor
malfunction will be reported. The unit can automatically resume
operation after the malfunction disappears. If indoor ambient
temperature sensor malfunction occurs in fan mode, only the error code
is displayed and the indoor unit can work normally.
11
F1
Malfunction of
evaporator
temperature
sensor
Evaporator
temperature
sensor
If the indoor evaporator temperature sensor is detected of open circuit
or short circuit for 5s successively, evaporator temperature sensor
malfunction will be reported. The unit can automatically resume
operation after the malfunction disappears. If evaporator temperature
sensor malfunction occurs in fan mode, only the error code is displayed
and the indoor unit can work normally.
12
F2
Malfunction of
condenser
temperature
sensor
Condenser
temperature
sensor
If the outdoor condenser temperature sensor is detected of open circuit
or short circuit for 5s successively, condenser temperature sensor
malfunction will be reported. The unit can automatically resume
operation after the malfunction disappears. If condenser temperature
sensor malfunction occurs in fan mode, only the error code is displayed
and the indoor unit can work normally.
Содержание GFH60K3HI
Страница 1: ...T1 R410A 50Hz GC201510 U MATCHAIR CONDITIONERS SERVICE MANUAL...
Страница 4: ...U Match Series Service Manual 1 PRODUCT...
Страница 16: ...U Match Series Service Manual 13 4 PIPING DIAGRAM...
Страница 17: ...U Match Series Service Manual 14 CONTROL...
Страница 18: ...U Match Series Service Manual 15 CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation...
Страница 19: ...U Match Series Service Manual 16 1 2 Heating Operation...
Страница 38: ...U Match Series Service Manual 35 INSTALLATION...
Страница 41: ...U Match Series Service Manual 38 condensate Figure 3 1 5 1 1 4 Dimension Data For the units 18K Figure 3 1 6...
Страница 72: ...U Match Series Service Manual 69 MAINTENANCE...
Страница 77: ...U Match Series Service Manual 74 E4 Discharge Protection E6 Communication Malfunction...
Страница 87: ...U Match Series Service Manual 84 Model GKH60K3HI...
Страница 102: ...U Match Series Service Manual 99 Model GUHN30NK3HO Exploded Views and spare parts list...
Страница 104: ...U Match Series Service Manual 101 Model GUHN36NM3HO Exploded Views and spare parts list...
Страница 106: ...U Match Series Service Manual 103 Model GUHN42NM3HO Exploded Views and spare parts list...
Страница 108: ...U Match Series Service Manual 105 Model GUHN48NM3HO Exploded Views and spare parts list...
Страница 110: ...U Match Series Service Manual 107 Model GUHN60NM3HO Exploded Views and spare parts list...
Страница 112: ...U Match Series Service Manual 109 5 2 Indoor Unit 5 2 1 Duct Type Model GFH18K3H1I exploded view and spare parts list...
Страница 114: ...U Match Series Service Manual 111 Model GFH24K3H1I GFH30K3H1I exploded view and spare parts list...
Страница 116: ...U Match Series Service Manual 113 Model GFH36K3H1I GFH42K3H1I exploded view and spare parts list...
Страница 118: ...U Match Series Service Manual 115 Model GFH48K3H1I exploded view and spare parts list...
Страница 120: ...U Match Series Service Manual 117 Model GFH60K3H1I exploded view and spare parts list...
Страница 122: ...U Match Series Service Manual 119 Model GFH18K3HI exploded view and spare parts list...
Страница 124: ...U Match Series Service Manual 121 Model GFH24K3HI GFH30K3HI exploded view and spare parts list...
Страница 126: ...U Match Series Service Manual 123 Model GFH36K3HI GFH42K3HI exploded view and spare parts list...
Страница 128: ...U Match Series Service Manual 125 Model GFH48K3HI exploded view and spare parts list...
Страница 130: ...U Match Series Service Manual 127 Model GFH60K3HI exploded view and spare parts list...
Страница 132: ...U Match Series Service Manual 129 5 2 2 Cassette Type Model GKH18K3HI exploded view and spare parts list...
Страница 134: ...U Match Series Service Manual 131 Model GKH24K3HI GKH30K3HI exploded view and spare parts list...
Страница 136: ...U Match Series Service Manual 133 Model GKH36K3HI GKH42K3HI GKH48K3HI exploded view and spare parts list...
Страница 139: ...U Match Series Service Manual 136 Model GKH60K3HI exploded view and spare parts list...
Страница 141: ...JF00302749...