U-Match Series Service Manual 

70 

MAINTENANCE 

1 TROUBLE TABLE   

1.1 Main Control Malfunction   

Table 1 Fault Display on Indoor Wired Controller 

No. 

Error 
code 

Malfunction 

name 

Origin of 

malfunction 

signal 

Control description 

E1 

High pressure 

protection   

High pressure 

switch   

When outdoor unit detects the high pressure switch is cut off for 3s 
successively, high pressure protection will occur. All the loads (except 
the 4-way valve in heating mode) will be switched off. In this case, all 
the buttons and remote control signals except ON/OFF button will be 
disabled and cannot be recovered automatically. Switch off the unit or 
re-energize the unit after cutting off power to eliminate this protection. 

E2 

Freeze 

protection   

Indoor 

evaporator 

temperature 

sensor   

If detecting that the evaporator temperature is lower than protective 
temp. Value after the unit has been running for a period of time under 
cooling or dry mode, the unit will report this fault, in which case the 
compressor and outdoor fan motor will be stopped. The unit will not run 
until evaporator temperature is higher than the protective temp. value 
and the compressor is stopped for 3min. 

E3 

Low pressure 

protection 

Low pressure 

switch   

If it is detected within 30s successively that the low-pressure switch is 
cut off under ON or standby state, the unit will report low pressure 
protection. If the fault occurs successively 3 times within 30min, the unit 
cannot be recovered automatically. 

Refrigerant 

lacking 

protection   

 

If the unit reports system refrigerant lacking within 10min after turning 
on the unit, the unit will stop operation. If the fault occurs successively 3 
times, the unit cannot be recovered automatically. 

Refrigerant 

recycling mode   

 

If enter refrigerant recycling mode through special operation, E3 will be 
displayed. After exiting refrigerant recycling mode, the code will 
disappear. 

E4 

Compressor 

high discharge 

temperature 

protection   

Compressor 

discharge 

temperature is 

high   

If outdoor unit detects that the discharge temperature is higher than 
protective temp. Value, the unit will report high discharge temperature 
protection. If the protection occurs over 6 times, the unit cannot be 
recovered automatically. Switch off the unit or re-energize the unit after 
cutting off power to eliminate this protection. 

E6 

Communicatio

n malfunction   

Communicatio

n between 

indoor and 

outdoor 

mainboard   

If the outdoor unit does not receive data from indoor unit, 
communication malfunction will be reported. If there is communication 
abnormity between display board and indoor unit, communication 
malfunction will be reported too. 

E9 

Full water 
protection   

Water level 

switch   

If cut-off of water level switch is detected for 8s successively once 
energized, the system will enter full water protection. In this case, 
switch off the unit and then switch it on to eliminate this malfunction. 

10 

F0 

Malfunction of 

indoor ambient 

temperature 

sensor at air 

return port 

Indoor ambient 

temperature 

sensor 

If the indoor ambient temperature sensor is detected of open circuit or 
short circuit for 5s successively, indoor ambient temperature sensor 
malfunction will be reported. The unit can automatically resume 
operation after the malfunction disappears. If indoor ambient 
temperature sensor malfunction occurs in fan mode, only the error code 
is displayed and the indoor unit can work normally. 

11 

F1 

Malfunction of 

evaporator 

temperature 

sensor   

Evaporator 

temperature 

sensor   

If the indoor evaporator temperature sensor is detected of open circuit 
or short circuit for 5s successively, evaporator temperature sensor 
malfunction will be reported. The unit can automatically resume 
operation after the malfunction disappears. If evaporator temperature 
sensor malfunction occurs in fan mode, only the error code is displayed 
and the indoor unit can work normally. 

12 

F2 

Malfunction of 

condenser 

temperature 

sensor   

Condenser 

temperature 

sensor   

If the outdoor condenser temperature sensor is detected of open circuit 
or short circuit for 5s successively, condenser temperature sensor 
malfunction will be reported. The unit can automatically resume 
operation after the malfunction disappears. If condenser temperature 
sensor malfunction occurs in fan mode, only the error code is displayed 
and the indoor unit can work normally. 

Содержание GFH60K3HI

Страница 1: ...T1 R410A 50Hz GC201510 U MATCHAIR CONDITIONERS SERVICE MANUAL...

Страница 2: ...of Wired Controller 25 5 4 Removal of Wired Controller 26 6 TROUBLESHOOTING 26 6 1 Display of Error Code 26 7 CENTRALIZED CONTROLLER 27 7 1 Smart Zone Controller 27 7 2 Additional Special Functions 30...

Страница 3: ...tdoor unit 80 3 2 Indoor unit 82 4 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS 85 4 1 Outdoor Unit 85 4 2 Indoor Unit 90 5 EXPLODED VIEWS AND SPARE PART LIST 97 5 1 Outdoor Unit 97 5 2 Indoor Uni...

Страница 4: ...U Match Series Service Manual 1 PRODUCT...

Страница 5: ...r Supply V Ph Hz Appearance GUHN18NK3HO CF021W2090 220 240V 50Hz GUHN24NK3HO CF021W2100 220 240V 50Hz GUHN30NK3HO CF021W2110 220 240V 50Hz GUHN36NM3HO CF021W2080 380 415V 3N 50Hz GUHN42NM3HO CF021W207...

Страница 6: ...11 5 GFH42K3HI CF022N0790 12 0 13 5 GFH42K3H1I CF022N0800 12 0 13 5 GFH48K3HI CF022N0770 14 0 15 0 220 240V 50Hz GFH48K3H1I CF022N0780 14 0 15 0 GFH60K3HI CF022N0750 16 0 18 0 GFH60K3H1I CF022N0760 16...

Страница 7: ...Hz M 380 415V 3N 50Hz 8 Refrigerant 1 R22 2 R407C 3 R410A 9 Design Code Design Code A B C D Design Change Code 0 default 1 2 3 10 Unit Code O Outdoor unit 2 2 Intdoor Unit G F H 18 T K 3 H I 1 2 3 4 5...

Страница 8: ...20 1260 1260 Rated Ext Static Pressure Pa 25 25 37 37 Ext Static Pressure Range Pa 0 30 0 30 0 30 0 30 Sound Pressure Level H M L dB A 36 33 30 29 36 33 30 29 43 38 34 32 43 38 34 32 Air Filter Standa...

Страница 9: ...a 37 37 37 37 Ext Static Pressure Range Pa 0 50 0 50 0 75 0 75 Sound Pressure Level H M L dB A 48 46 45 44 48 46 45 44 51 48 46 44 51 48 46 44 Air Filter Standard washable synthetic Drain Piping mm 20...

Страница 10: ...Pa 37 37 50 50 Ext Static Pressure Range Pa 0 75 0 75 0 100 0 100 Sound Pressure Level H M L dB A 51 48 46 44 51 48 46 44 53 52 50 50 53 52 50 50 Air Filter Standard washable synthetic Drain Piping m...

Страница 11: ...ssure Pa 50 50 Ext Static Pressure Range Pa 0 100 0 100 Sound Pressure Level H M L dB A 56 52 49 49 56 52 49 49 Air Filter Standard washable synthetic Drain Piping mm 30 1 5 26 3 0 Outline Dimensions...

Страница 12: ...m 3 h 720 1450 1500 1650 Sound Pressure Level H M L dB A 50 49 47 46 49 48 47 46 51 50 49 48 52 47 46 43 Air Filter Standard washable synthetic Drain Piping mm 26 3 0 33 4 0 33 4 0 33 4 0 Outline Dim...

Страница 13: ...3 h 1650 1650 1800 Sound Pressure Level H M L dB A 52 47 46 43 52 47 46 43 53 51 49 47 Air Filter Standard washable synthetic Drain Piping mm 33 4 0 33 4 0 32 2 0 Outline Dimensions W H D mm 850 850 3...

Страница 14: ...on due to environmental change 3 2 Operation Range Mode Range of Outdoor Temperature Cooling 15 43 Heating 10 24 3 3 Electrical Data 3 3 1 Outdoor unit Table 1 4 1 Electrical Data of Outdoor Unit Mode...

Страница 15: ...40 1 50 1 5 6 1 0 GKH60K3HI 220 240 1 50 1 5 6 1 0 Notes RLA Rated load amperes LRA Locked rotor amperes FLA Full load current Install the disconnect device with a contact gap of at least 3mm in all p...

Страница 16: ...U Match Series Service Manual 13 4 PIPING DIAGRAM...

Страница 17: ...U Match Series Service Manual 14 CONTROL...

Страница 18: ...U Match Series Service Manual 15 CONTROL 1 OPERATION FLOWCHART 1 1 Cooling Dry Operation...

Страница 19: ...U Match Series Service Manual 16 1 2 Heating Operation...

Страница 20: ...er modes the initial value is 25 C 77 F AUTO COOL DRY FAN HEAT only for cooling and heating unit button Preset temperature can be decreased by pressing this button Pressing and holding this button for...

Страница 21: ...hin 5 seconds it is allowed to set the ON time by pressing the button Each press will make the time increase or decrease one minute Besides the time can also be set by pressing the button constantly T...

Страница 22: ...powered on Sleep Off is defaulted Once the unit is turned off the Sleep function is canceled When Sleep is set to on the symbol of SLEEP will display Under the Fan and Auto modes this function is not...

Страница 23: ...isplay of master and slave wired controller 14 Shield function The button operation temperature setting On Off operation Mode setting and Save setting are disabled 15 Fan speed 16 Memory function The...

Страница 24: ...not indoor unit is defaulted to be off after power recovery Ex factory setting of memory function is on 2 and 6 Lock Upon startup of the unit without malfunction or under off state of the unit press a...

Страница 25: ...onsumption mode selecting door control function selecting human sensitive function long distance monitoring temperature compensation value at the air return port 3 2 3 Setting of Wired Controller s Ad...

Страница 26: ...er and 02 for slave wired controller Press or button to adjust address of master slave wired controller and then press Enter Cancel button to confirm If slave wired controller is set the icon will be...

Страница 27: ...control information is received when the room card is inserted it will keep the original status 2 The unit can not be controlled by buttons when the card is not inserted 5 INSTALLATION OF WIRED CONTRO...

Страница 28: ...signal wire are as below 1 Choose suitable signal wire 2 core signal wire wire diameter 0 75mm wire length 30m and the recommended length is 8m 2 Make sure the power of indoor unit is cut off fix the...

Страница 29: ...ressure protection during operation Error Code Error E1 Compressor high pressure protection E2 Freeze protection E3 Compressor low pressure protection refrigerant lacking protection refrigerant recycl...

Страница 30: ...n The smart zone controller can directly control up to 16 sets of indoor units in a control network and is available to check the running status of any unit through the LCD including running mode time...

Страница 31: ...sed for the switchover between unit 3 and unit 11 Under the timing or clock setting status it indicates Wednesday 9 Thu 4 12 It is used for the switchover between unit 4and unit 12 Under the timing or...

Страница 32: ...temperature Indoor unit code It displays the set temperature indoor unit code 01 16 and symbols of Celsius and Fahrenheit scale 7 Control mode It displays CENTER under the centralized control mode an...

Страница 33: ...ted to this interface 2 Electrical characteristic none 3 Working principle when the card is inserted this interface is short circuited when the card is not inserted this interface is cut off Connect t...

Страница 34: ...cted the unit will turn to standby state If the unit is with wired controller icon will be displayed on the wired controller If the unit is without wired controller there will be no display The unit w...

Страница 35: ...long distance control address mode The address mode is defaulted to be connecting to centralized controller mode and the defaulted address is 1 3 Setting method Firstly set the address mode of wired...

Страница 36: ...setting method is Under off state of the unit press Function and Mode buttons at the same time for 5s to enter setting interface of wired controller address LCD displays address sequence Press or but...

Страница 37: ...centralized control address mode otherwise this function can not be realized The unit can not be connected to MODBUS and centralized controller at the same time only one of them can be selected 255 s...

Страница 38: ...U Match Series Service Manual 35 INSTALLATION...

Страница 39: ...to avoid possible explosion or fire due to leakage 1 1 2 Installation Site Ensure the top hanging piece has strong strength to withstand the weight of the unit The drainage pipe has convenient flow of...

Страница 40: ...e the installation so as to achieve smooth installation Drill an opening on the ceiling Maybe it is required to support the ceiling to ensure the evenness of it and avoid the vibration of it Consult w...

Страница 41: ...U Match Series Service Manual 38 condensate Figure 3 1 5 1 1 4 Dimension Data For the units 18K Figure 3 1 6...

Страница 42: ...H18K3HI GFH18K3H1I 940 430 740 738 206 125 1015 275 720 GFH24K3HI GFH24K3H1I 1101 515 820 1159 1260 555 1002 160 235 270 GFH30K3HI GFH30K3H1I GFH36K3HI GFH36K3H1I 1011 748 820 1115 1230 790 979 160 23...

Страница 43: ...rainage pipe 2 Used for wrapping the condensate pipe and rubber plug Nut M8 with gasket 8 Use for fixing the hanger hook 4 4 sets used for ceiling mounting of the indoor unit Nut and spring gasket 4 H...

Страница 44: ...this installation manual and keep the area warm enough to prevent condensation Problems with the piping may lead to water leaks 1 Install the drain hose with downward gradient 1 50 to 1 100 and no ri...

Страница 45: ...ort on right side has been plugged 8 When using the drain port on the right side of the unit reinstall the drain cap to the left side drain port Figure 3 1 13 CAUTION Always check that the drain cap i...

Страница 46: ...densate pump which is different from that of the unit without the condensate pump 3 For the unit with the condensate pump two drain ports at the bottom are defaulted to be factory plugged with drain c...

Страница 47: ...U Match Series Service Manual 44 Figure 3 1 18 1 1 7 Installation of air duct Dimensions of the Supply Air Outlet Return Air Inlet Figure 3 1 19 Supply Air Outlet Figure 3 1 20 Return Air Inlet...

Страница 48: ...tion of the Rectangular Duct Figure 3 1 21 CAUTION The maximum length of the duct means the maximum length of the supply air duct plus the maximum length of the return air duct The duct is rectangular...

Страница 49: ...ply Air Duct 3 Return Air Duct 6 Grille 1 2 Installation of Cassette Type 1 2 1 Before Installation After receiving the machine please check for any transport damage If finding any surface or internal...

Страница 50: ...crease the operating noise and vibration 4 The horizontality of the installation place should be guaranteed 5 Select the place where is easy to drain out the condensate water and connect with outdoor...

Страница 51: ...not the water pump and the float switch would function improperly and even lead to water leakage 5 Remove the gasket anchor board and tighten the nut remained 6 Remove the paper template 1 2 4 Instal...

Страница 52: ...hip of the front panel and the connecting pipe Figure 3 1 30 2 Place the panel at the unit and latch the hooks beside and opposite the swing flap motor 3 Latch other two hooks 4 Tighten four hexagonal...

Страница 53: ...7 Improper screwing of the screws may cause the troubles shown in Figure 3 1 32 Figure 3 1 32 8 If gap still exists between ceiling and decoration panel after tightening the screws readjust the height...

Страница 54: ...wing flap motor as shown in Figure 3 1 34 Figure 3 1 34 1 2 7 Dimension Data For the units 18k A B C D E F G H I J Bottom face of ceiling Figure 3 1 35 Table 3 1 7 Item Model A B C D E F G H I J GKH18...

Страница 55: ...ds at a gradient of at least 1 100 so that air may not remain trapped inside the pipe 2 Keep pipe size equal to or greater than that of the connecting pipe 3 Install the drain piping as shown and take...

Страница 56: ...gradient it is necessary to fit a riser pipe field supplied to it 5 If the air flow of indoor unit is high this might cause negative pressure and result in return suction of outdoor air Therefore U ty...

Страница 57: ...Connect the drain hose to the drain lift pipe and insulate them 2 Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Figure 3 1 45 2 Make sure the lift pipe i...

Страница 58: ...n reference to the packing list Ensure that the model is correct and the machine is in good condition Please also check if the specification and quantity of accessory parts are correct Determine the c...

Страница 59: ...the unit and generates as less noise and vibration as possible 7 Provide the space shown in Figure 3 2 1 so that the air flow is not blocked Also for efficient operation leave three of four directions...

Страница 60: ...all the wall cross tube must be installed The installing dimension shall comply with the installation requirements in these instructions The outdoor unit must be fixed at the installing position The i...

Страница 61: ...nding Pipes 1 The pipes are shaped by your hands Be careful not to collapse them Figure 3 2 4 2 Do not bend the pipes in an angle more than 90 3 When pipes are repeatedly bent or stretched the materia...

Страница 62: ...it from the unit please do use both the spanner and the torque wrench Figure 3 2 6 When connecting smear both inside and outside of the flare nut with refrigeration oil screw it hand tight and then ti...

Страница 63: ...onnected 3 1 6 Heat Insulation on the Pipe Joints Indoor Side Only Stick coupler heat insulation large and small to the place where connecting pipes Figure 3 2 3 3 1 7 Vacuum and Gas Leakage Inspectio...

Страница 64: ...ction pipe to balance the pressure inside and outside of the connection pipe so that air will not come into the connection pipe when removing the hose Note that the gas and liquid valve can be opened...

Страница 65: ...door Unit m Drainage pipe Outer Diameter wall thickness mm Liquid Gas GUHN18NK3HO 1 4 1 2 15 15 16X2 0 GUHN24NK3HO 3 8 5 8 15 15 16X2 0 GUHN30NK3HO 3 8 5 8 30 15 16X2 0 GUHN36NM3HO 3 8 3 4 30 15 16X2...

Страница 66: ...c company standards WARNING The power source capacity must be the sum of the air conditioner current and the current of other electrical appliances When the current contracted capacity is insufficient...

Страница 67: ...that power is not being supplied to the indoor unit and outdoor unit Match the terminal block numbers and connection cord colors with those of the indoor unit side Erroneous wiring may cause burning...

Страница 68: ...GFH30K3HI GFH30K3H1I Power cord 3 4 0 mm 2 H07RN F Power cord 3 1 0 mm 2 H05VV F Communication Cords 2 0 75 mm 2 H05VV F Three phase units 36 60k Duct Type Unit GUHN36NM3HO GFH36K3HI GFH36K3H1I Power...

Страница 69: ...m 2 H07RN F Power cord 3 1 0 mm 2 H05VV F Communication Cords 2 0 75 mm 2 H05VV F Single phase units 24 30k Casssete Type Unit GUHN24NK3HO GKH24K3HI GUHN30NK3HO GKH30K3HI Power cord 3 4 0 mm 2 H07RN F...

Страница 70: ...OPEN terminal of the fresh air valve respectively Cassette Type Unit 18k 24 60k Figure 3 2 12 CAUTION The power cord and the wire of the fresh air valve are high voltage while the communication cord a...

Страница 71: ...ure 3 2 9 Ground both the indoor and outdoor units by attaching a ground wire Unit shall be grounded in compliance with the applicable local and national codes 6 Electric wiring of outdoor unit side N...

Страница 72: ...U Match Series Service Manual 69 MAINTENANCE...

Страница 73: ...temp Value the unit will report high discharge temperature protection If the protection occurs over 6 times the unit cannot be recovered automatically Switch off the unit or re energize the unit after...

Страница 74: ...disappears 15 F5 Malfunction wired controller temperature sensor Wired controller If the wired controller detects open circuit or short circuit of its temperature sensor for 5s successively wired con...

Страница 75: ...malfunction If freeze protection occurs frequently during operation please check if the indoor filter is with filth blockage or if the indoor air outlet is abnormal The user is required to clean the...

Страница 76: ...l operation the displayed E3 is not an error code It will be eliminated when exiting refrigerant recycling mode If you do not want to have refrigerant lacking protection you can enter the debugging mo...

Страница 77: ...U Match Series Service Manual 74 E4 Discharge Protection E6 Communication Malfunction...

Страница 78: ...the full water switch or make sure the float of full water switch works normally Yes F0 Malfunction of Indoor Ambient Temperature Sensor Malfunction of indoor ambient temperature sensor Check if the i...

Страница 79: ...U Match Series Service Manual 76 F1 Malfunction of Evaporator Temperature Sensor F2 Malfunction of Condenser Temperature Sensor...

Страница 80: ...U Match Series Service Manual 77 F3 Malfunction of Outdoor Ambient Temperature Sensor F4 Malfunction of Discharge Temperature Sensor...

Страница 81: ...U Match Series Service Manual 78 F5 Malfunction of Wired Controller Temperature Sensor 2 2 Interface GUHN18NK3HO GUHN24NK3HO GUHN30NK3HO Main Control Board...

Страница 82: ...system protection obligate Interface of low pressure protection 7 HPP High pressure switch for systemprotection obligate Interface of high pressure protection 8 CN1 1 2 pin Tube sensor 3 4 pin Ambien...

Страница 83: ...tection 7 HPP High pressure switch for systemprotection obligate Interface of high pressure protection 8 CN1 1 2 pin Tube sensor 3 4 pin Ambient temperature 5 6 pin Air discharge 1 2 pin Case temperat...

Страница 84: ...U Match Series Service Manual 81 Model GUHN24NK3HO GUHN30NK3HO Model GUHN36NM3HO GUHN42NM3HO GUHN48NM3HO GUHN60NM3HO...

Страница 85: ...The actual wiring should always refer to the wiring diagram of the unit 3 2 1 Duct Type Model GFH18K3HI GFH24K3HI GFH30K3HI GFH36K3HI GFH42K3HI GFH48K3HI GFH60K3HI Model GFH18K3H1I GFH24K3H1I GFH30K3...

Страница 86: ...U Match Series Service Manual 83 3 2 2 Cassette Type Model GKH18K3HI Model GKH24K3HI GKH30K3HI GKH36K3HI GKH42K3HI GKH48K3HI...

Страница 87: ...U Match Series Service Manual 84 Model GKH60K3HI...

Страница 88: ...Remove the top cover and handle 2 Remove the grille outer case and right side plate 2 Remove motor 1 Remove the blade nut and then remove the blade 2 Remove the motor from motor support 3 Remove comp...

Страница 89: ...the top cover and handle 2 Remove the grille outer case front side plate and right side plate 2 Remove motor 1 Remove the blade nut and then remove the blade 2 Remove the motor from motor support 3 R...

Страница 90: ...nal casing 1 Remove the top cover and handle 2 Remove the grille outer case and right side plate 2 Remove motor 1 Remove the blade nut and then remove the blade 2 Remove the motor from motor support 3...

Страница 91: ...4 Take away the compressor from chassis 5 Assemble unit Assemble the unit in the reverse procedures of disassembly 42k 48k 60k Disassembly and Assembly of external casing Remark Step Illustration Han...

Страница 92: ...lve assy from gas liquid separator 3 Remove the gas liquid separator 4 Remove compressor 1 Discharge the refrigerant inside the pipeline and recycle the refrigerant during discharging 2 Unsolder the 4...

Страница 93: ...use screwdriver to remove the air inlet cover board 3 Remove the screws on fan sub assembly Remove the screws on fan sub assembly 4 Overturn the propeller housing Rotate the propeller housing to the...

Страница 94: ...to the direction shown by the arrow There are 2 filter screens for return air Disassembly of electrical parts box cover panel and electrical parts box Remark Make sure that the power supply is cut off...

Страница 95: ...e symmetrically arranged both on left and right 2 Disassembly of water containing plate Disassemble the fastening screws on the water containing plate pull upward and remove the water containing plate...

Страница 96: ...e arrows direction in Graph 2 Disassemble fastening screws connecting evaporator valve seal plate and joint flange Disassemble the fastening screws on the valve seal plate and remove the valve seal pl...

Страница 97: ...ner to loosen the bolts fixing the fan 4 Remove the fan Remove the fan 5 Loosen the screws fixing the motor Use screwdriver to loosen the screws fixing the motor 6 Remove the motor and replace it Remo...

Страница 98: ...ng the water tray Removal and Installation of Drainage Pump Step Illustration Handling Instruction 1 Loosen the screws fixing the water tray Use screwdriver to loosen the screws fixing the water tray...

Страница 99: ...p and replace it 5 Connect the drainage pipe and tighten the screws fixing the water pump Connect the drainage pipe and use screwdriver to tighten the screws fixing the water pump 6 Mount the water tr...

Страница 100: ...U Match Series Service Manual 97 5 EXPLODED VIEWS AND SPARE PART LIST 5 1 Outdoor Unit Model GUHN18NK3HO GUHN24NK3HO Exploded Views and spare parts list...

Страница 101: ...2623525404 1 18 Rear Grill 01473043 1 01473043 1 19 Clapboard Sub Assy 01245200032 1 01245200032 1 20 Strainer 07220019 1 07220019 1 21 Electronic Expansion Valve 07133978 1 07133909 1 22 Bifurcate S...

Страница 102: ...U Match Series Service Manual 99 Model GUHN30NK3HO Exploded Views and spare parts list...

Страница 103: ...07133157 1 17 Valve Support Sub Assy 01715020P 1 18 Silencer 07245008 1 19 Preessure Protect Switch 4602000902 1 20 Right Side Plate Sub Assy 01315464P 1 21 Big Handle 2623500101 1 22 Rear Grill 0147...

Страница 104: ...U Match Series Service Manual 101 Model GUHN36NM3HO Exploded Views and spare parts list...

Страница 105: ...Strainer 07225088 1 18 Valve Support Sub Assy 01715020P 1 19 Right Side Plate Sub Assy 0131520006901P 1 20 Big Handle 2623500101 1 21 Rear Grill 01475013 1 22 Clapboard Sub Assy 01245200027 1 23 Conde...

Страница 106: ...U Match Series Service Manual 103 Model GUHN42NM3HO Exploded Views and spare parts list...

Страница 107: ...ve Fitting 43000344 1 19 Electronic Expansion Vlave 43005017 1 20 Cut off Valve 071302392 1 21 Cut off Valve 07135058 1 22 Silencer 07245011 1 23 Valve Support Sub Assy 01715257P 1 24 Right Side Plate...

Страница 108: ...U Match Series Service Manual 105 Model GUHN48NM3HO Exploded Views and spare parts list...

Страница 109: ...Strainer 07225088 1 18 Electric Expand Valve Fitting 43000344 1 19 Right Side Plate Sub Assy 01315200076P 1 20 Rear Grill 01475012 1 21 Clapboard Sub Assy 01235069 1 22 Condenser Assy 01125200305 1 2...

Страница 110: ...U Match Series Service Manual 107 Model GUHN60NM3HO Exploded Views and spare parts list...

Страница 111: ...19 Electronic Expansion Valve 43005017 1 20 Strainer 0741410000601 1 21 Cut off Valve 07130212 1 22 Bidirection Strainer 07210044 1 23 Rear Side Plate Sub Assy 01315200088P 1 24 Silencer 07245012 2 25...

Страница 112: ...U Match Series Service Manual 109 5 2 Indoor Unit 5 2 1 Duct Type Model GFH18K3H1I exploded view and spare parts list...

Страница 113: ...n Motor 1570521802 1 11 Filter Sub Assy 11725202 1 12 Rear Volute Casing 22202029 2 13 Cover Of Air In 01258650 1 14 Water Tray Assy 01284166 1 15 Bottom Cover Plate 01265409 1 16 Choke Plug of Water...

Страница 114: ...U Match Series Service Manual 111 Model GFH24K3H1I GFH30K3H1I exploded view and spare parts list...

Страница 115: ...2285301 1 02285301 1 10 Filter Sub Assy 11125303 2 11125303 2 11 Water Tray Assy 81211150020 1 81211150020 1 12 Lower Cover Plate Sub Assy 01265304 1 01265304 1 13 Water Pump 43138000058 1 43138000058...

Страница 116: ...U Match Series Service Manual 113 Model GFH36K3H1I GFH42K3H1I exploded view and spare parts list...

Страница 117: ...1 11 Choke Plug of Drain Pipe 76712455 2 76712455 2 12 Water Pump 43138000058 1 43138000058 1 13 Water Tray Assy 01285323 1 01285323 1 14 Lower Cover Plate Sub Assy 15265301 1 15265301 1 15 Right Side...

Страница 118: ...U Match Series Service Manual 115 Model GFH48K3H1I exploded view and spare parts list...

Страница 119: ...ater Pump 43138000058 1 10 Air Intake Side Board 01375301 1 11 Filter Sub Assy 111253031 2 12 Choke Plug of Drain Pipe 76712455 2 13 Lower Cover Plate Sub Assy 15265301 1 14 Water Tray Assy 01285323 1...

Страница 120: ...U Match Series Service Manual 117 Model GFH60K3H1I exploded view and spare parts list...

Страница 121: ...Assy 111253032 2 10 Water Tray Assy 01279114 1 11 Pump Drainpipe 2690520014601 1 12 Water Pump 43138000058 1 13 Water Level Switch 45020216 1 14 Bottom Cover Plate Assy 01259114 1 15 Ritht Side Plate...

Страница 122: ...U Match Series Service Manual 119 Model GFH18K3HI exploded view and spare parts list...

Страница 123: ...ub Assy of Return Air Frame 02225234 1 10 Fan Motor 1570521802 1 11 Filter Sub Assy 11725202 1 12 Choke Plug of Water Pipe 76712454 1 13 Rear Volute Casing 22202029 2 14 Cover Of Air In 01258650 1 15...

Страница 124: ...U Match Series Service Manual 121 Model GFH24K3HI GFH30K3HI exploded view and spare parts list...

Страница 125: ...81211150020 1 8 Filter Guide Groove Sub Assy 02285301 1 02285301 1 9 Filter Sub Assy 11125303 2 11125303 2 10 Lower Cover Plate Sub Assy 01265304 1 01265304 1 11 Right Side Plate Sub Assy 013152002340...

Страница 126: ...U Match Series Service Manual 123 Model GFH36K3HI GFH42K3HI exploded view and spare parts list...

Страница 127: ...76712455 1 76712455 1 10 Water Tray Assy 01285323 1 01285323 1 11 Lower Cover Plate Sub Assy 15265301 1 15265301 1 12 Right Side Plate Sub Assy 0131520022301 1 131520022301 1 13 Electric Box Assy 013...

Страница 128: ...U Match Series Service Manual 125 Model GFH48K3HI exploded view and spare parts list...

Страница 129: ...sy 01025200172 1 8 Air Intake Side Board 01375301 1 9 Filter Sub Assy 111253031 2 10 Choke Plug of Drain Pipe 76712455 1 11 Water Tray Assy 01285323 1 12 Lower Cover Plate Sub Assy 15265301 1 13 Right...

Страница 130: ...U Match Series Service Manual 127 Model GFH60K3HI exploded view and spare parts list...

Страница 131: ...1 8 Filter Guide Groove 01729166 1 9 Filter Sub Assy 111253032 2 10 Water Tray Assy 01279114 1 11 Bottom Cover Plate Assy 01259114 1 12 Ritht Side Plate Assy 0131520022101 1 13 Electric Box Assy 01395...

Страница 132: ...U Match Series Service Manual 129 5 2 2 Cassette Type Model GKH18K3HI exploded view and spare parts list...

Страница 133: ...te Sub Assy 01319400012 1 10 Press Plate Outlet Pipe 01349400004 1 11 Front Side Plate Sub Assy 01319400014 1 12 Capacitor 3301074710 1 13 Terminal Board 4201025301 1 14 Terminal Board 42010259 1 15 M...

Страница 134: ...U Match Series Service Manual 131 Model GKH24K3HI GKH30K3HI exploded view and spare parts list...

Страница 135: ...1 07212403 1 12 Left Side Plate Assy 01302715 1 01302715 1 13 Tube Exit Plate Assy 01382715 1 01382715 1 14 Base Plate Assy 01222701 1 01222701 1 15 Front Side Plate assy 01302718 1 01302718 1 16 Pum...

Страница 136: ...U Match Series Service Manual 133 Model GKH36K3HI GKH42K3HI GKH48K3HI exploded view and spare parts list...

Страница 137: ...y Installing Plate 01332701 4 01332701 4 11 Tube Exit Plate Assy 01382715 1 01382715 1 12 Connection sheet assy 01349400007 1 01349400007 1 13 Front Side Plate assy 01302713 1 01302713 1 14 Base Plate...

Страница 138: ...01302711 1 10 Body Installing Plate 01332701 4 11 Tube Exit Plate Assy 01382715 1 12 Connection sheet assy 01349400007 1 13 Front Side Plate assy 01302713 1 14 Base Plate Assy 01222701 1 15 Water Lev...

Страница 139: ...U Match Series Service Manual 136 Model GKH60K3HI exploded view and spare parts list...

Страница 140: ...ide Plate 1 01319400025 1 10 Liquid Level Switch 4502021601 1 11 Body Installing Plate 01332701 4 12 Side Plate 3 01319400036 2 13 Base Plate Assy 02229400021 1 14 Fan Motor 15709400010 1 15 Seal Plat...

Страница 141: ...JF00302749...