Floor Ceiling Tpye Fan Coil Unit

10

7.2  Electric wiring 

The electric wiring of the valve should  be according with the Fig.10  

 It is prohibited to bind directly the water valve 

wire and sponge up with the copper tube, as there 

would be probably    a short circuit or even electric 

leakage(as Fig.18).

Water valve wire

Sponge

Water tube

Fig.18

 The right way is letting the water valve wire go 

through the pipe sleeve and then binding the sponge 

and pipe sleeve up(as Fig.19).

Water valve wire PVC pipe sleeve

Sponge

Water tube

Fig.19

 It is prohibited to put the valve core upside down, 

as thiswould allow the condensate water to enter or 

damage the valve core and even form a short circuit 

which wouldresult in a fire hazard(as Fig.20).

Fig.20

 

The right way is placing the valve core in the 

proper position and letting the leading wire pointing 

at the unit(as Fig.21).

Fig.21

Sponge

     

It is prohibited to wrap the whole 

valve with sponge, as this would 

affect the heat diffusion of the 

valve core and probably pose a fire 

hazard(as Fig.22).

Fig.22

8 Evaluation of the Performance

(1)  Check electric main wire’s voltage.
(2)  Use a thermometer to measure cool air temperature both inlet side and outlet side.
(3)  The difference between in-air and out-air temperature should not be less than 8

℃ .

Thermometer

(4)  The unit has Auto-restart function, it can remember the running model before power-broken.

Содержание FP-102WM-D

Страница 1: ...D FP 102WM K BMS FP 34ZD K FP 51ZD K FP 68ZD K FP 85ZD K FP 102ZD K FP 136ZD K FP 170ZD K FP 204ZD K FP 136WM K BMS Thank you for choosing commercial air conditioners Please read this Owner s Manual c...

Страница 2: ...l DISPOSAL This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environment or human health from uncontrolled w...

Страница 3: ...g 4 5 Installation 4 5 1 Dimension 4 5 2 Selection of Installation location 5 5 3 There are two types of installation 5 5 4 Electrical wiring 7 6 Drain Piping Work 8 7 Motorized valve 9 7 1 Installati...

Страница 4: ...or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety 2 Children sh...

Страница 5: ...le to blow all over the room Clean the air filter every week for higher efficiency by professional Close the window and door while operating the unit for saving energy Cover windows with a blind or a...

Страница 6: ...ecified capacity Do not use pieces of wire instead of fuse Do not insert objects into the air inlet or outlet when the air conditioner is running as it may cause damage or personal injury Also pay spe...

Страница 7: ...me coming out of the unit while running Hot air in the room mixes with cool air This causes smoke fume Inoperative remote control Loosened or disconnected wire between the unit and the display Check i...

Страница 8: ...more 60cm or more Fig 1 Fig 2 5 3 There are two types of installation Ceiling type Floor type Fig 3 Each type is similar to the other as follows 1 Determine the mounting position on ceiling or wall 2...

Страница 9: ...of the drain pipe slightly inclines to improve drainage Adjust the height by turning the nut with a spanner Insert the spanner from the hanger bracket opening Refer to Fig 8 Hanging installation It i...

Страница 10: ...sulated power cable used at 40 and resistible to 90 see GB T 16895 15 If the working condition changes they should be modified according to the related national standard Rubber bush Wiring clamp Power...

Страница 11: ...tely into the drain socket Tighten the clamp within the range of gray tape until the screw head is less than 4 mm from the hose Refer to Fig 12 13 5 Wrap the attached sealing pad OD over the clamp and...

Страница 12: ...uaranteed Flare nut Wiring interface Water outlet tube Torque wrench Thread fasten Spanner Valve Tape Water tube joint Fig 16 2 Both the tube joint and the motorized valve are G3 4 threaded Prior to t...

Страница 13: ...ould allow the condensate water to enter or damage the valve core and even form a short circuit which wouldresult in a fire hazard as Fig 20 Fig 20 The right way is placing the valve core in the prope...

Страница 14: ...function or damage the part Has the inlet and outlet been covered It may cause insufficient cooling or heating capacity 10 Test Operation wireless remoter controller 10 1 Before test operation 1 Do no...

Страница 15: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail gree gree com cn www gree com...

Отзывы: