background image

Digi 20 Series

One Circuit Electronic
24 Hour or 7 Day Time Switches

Digi 20A

(surface mounting)

Digi 20E

(flush mounting)

APPLICATION

Time based control of lighting, ventilating, heating, cooling

or other electrical loads in commercial and industrial applica-
tions. The Digi 20 time switches are programmable for 24-
hour or 7-day schedules.

The Digi 20A is intended for either surface or rail mounting.

The control is completely enclosed in a plastic housing and
includes a terminal cover and sub-base for installation and
hard wiring.

The Digi 20E is intended for flush (panel) mounting. 
All units are supplied with a clear plastic dust cover. They

are also available with an enclosure for stand-alone applica-
tions. (GM and GMX models)

TECHNICAL DATA

Output–1 SPDT relay with dry contacts
Switch Rating: 16A/277VAC resistive

1000W tungsten @ 240VAC; 500W @ 120VAC
1/2 hp @ 120VAC; 1 hp @ 240VAC

100 hour capacitor back-up of memory and display
Supply voltages: Separate Models – 24VAC/DC, 120VAC,

208/240VAC, all 50/60Hz (refer to product label)

Shortest switch time–1 minute
Ambient Temperature Range –20°F to 140°F (–28°C to 60°C)
VA required: 120V & 240V models: 4VA

24V model: 2VA @ 24VAC, 1VA @ 24VDC

Screw terminal connections (Digi 20A)
1/4” quick connects (Digi 20E)
Accuracy ± 4 minutes per year

Installation

To the installer:
1. Read operating instructions carefully.
2. Check the input and output ratings marked on the unit to

make sure this product is suitable for your power supply
and application.

3. Disconnect power supply prior to installation to prevent

electrical shock.

4. Wire in accordance with National and Local electrical code

requirements.

SURFACE MOUNTING—Digi 20A

Remove dust cover, loosen two screws on opposite corners.

Remove the housing that surrounds the time switch and the
terminal cover away from the base. Remove timer module by
pulling straight out.

Place screws through 3 mounting holes in base and screw

to back panel or wall.

Wire in accordance with instructions. Replace terminal cover

and push timer firmly onto base. Now replace housing and
secure with screws.

NOTE: 

The Digi 20A is also suitable for DIN rail mounting.

Break out housing part on each side that fits over rail.

PANEL MOUNTING—Digi 20E

Cut a square hole 2-5/8” x 2-5/8” (66mm x 66mm) in the front

of the panel. Insert the time switch through the opening. With
a screwdriver, press down and turn outer screws (A) until
flanges are in position to fasten the unit in front panel, then
release. Insert plugs into holes (B).

Use 1/4” quick connects and make connections in accor-

dance with the wiring diagram shown and applicable code
requirements.

WIRING

1. Disconnect the power.
2. Wire input to timer, 

, with the

proper voltage marked on the
unit. Wiring to incorrect voltage
will void the warranty.

3. Connect wiring according to the

wiring diagram. The terminals on
the Digi 20A sub-base will accom-
modate 10 to 24 AWG wire.

M

LOAD

POWER

TIMER INTERNAL WIRING

COM

NO

NC

TIME

SWITCH

FIELD WIRING

1

2

3

4

5

Terminal Connections

B

A

A

B

C

FILE: E83486

 

http://waterheatertimer.org/Intermatic-timers-and-manuals.html

 

For updated timers and manuals

Содержание Digi 20A

Страница 1: ... power supply and application 3 Disconnect power supply prior to installation to prevent electrical shock 4 Wire in accordance with National and Local electrical code requirements SURFACE MOUNTING Digi 20A Remove dust cover loosen two screws on opposite corners Remove the housing that surrounds the time switch and the terminal cover away from the base Remove timer module by pulling straight out Pl...

Страница 2: ...y does not show AM it is in military time mode 24 00 hr To change to AM PM mode press and hold the h key and press the 1h key once AM will appear in display If display is in AM mode and military mode is desired press and hold the h key press the 1h key once SETTING THE TIME NOTE If the h and m keys are held down longer than 2 seconds the numbers will advance rapidly Press and hold the key during t...

Страница 3: ...NG A PROGRAM Select the program to be changed with the Prog key A new set of days may be selected with the Day key just as in initial programming Hour and minute can be changed with the h and m keys Press Prog or key to store the new program DELETING A PROGRAM To delete only one or a few programs Press Prog key until the desired program is displayed Press m key to 59 and press once more to blank o...

Страница 4: ...______________________________________________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________________________________________________________________ ___________________________________________________________________________...

Отзывы: