5.1 GENERaL

The flow and return pipework can be routed to either side of the 

boiler, dependant on the type and direction of the flue system 

used.
For condensate disposal pipework refer to Section 6.
A drain cock is supplied in the accessories pack and should be 

fitted at the bottom on the front of the boiler to allow the boiler to 

be drained.

Key to diagrams

Key

F

Flow

FP

Flow pipe

FC

Flow connection

R

Return

MB

Mounting bracket

DS

Dual stat

CP

Removable cover plate

P

Pockets

SP

Split pin

5.2  15/21, 21/26 aND 26/35 mODELS

FLOW CONNECtiON

A 1ʺ BSP socket is provided for the boiler flow connection. This is 

located on the top of the boiler towards the right hand side. Refer 

to Figure 5-1.

The flow pipe from the boiler will need to be vented as it is the 

highest point on the primary heat exchanger.

REtURN CONNECtiON

A second 1ʺ BSP socket is provided for the boiler return 

connection. This is located on the top of the boiler towards the 

front on the right hand side. Refer to Figure 5-1.
The return pipe to the boiler will also need to be vented as it is the 

highest point on the secondary heat exchanger.

Figure 5-1:

 15/21, 21/26 and 26/35 models - dual stat/mounting 

bracket, flow and return connections and removable cover plate

5.3  36/46 mODEL ONLY

FLOW CONNECtiON

A 28mm compression connection is supplied for the boiler flow 

connection. This is located on the right hand side of the boiler 

behind a removable cover plate. To gain access to the connection, 

unscrew and remove the two screws from the top flange of the 

cover plate and remove cover plate from boiler. Refer to Figure 

5-2.

Figure 5-2:

 36/46 model - dual stat/mounting bracket, flow and 

return connections and removable cover plate

A bent 28mm flow pipe, with two thermostat pockets, is supplied 

with the boiler to be fitted into the flow connection, as follows: 

1.  With the cover plate removed, loosen the compression nut 

and fit the longer leg of the bent flow pipe into the connection.

2.  Ensure that the pipe is vertical and fully pushed into the 

connection.

3. 

With the open end of the flow pipe pointing in the required 

direction (see below), fully tighten the compression nut. Refer 

to Figure 5-3.

4.  Replace cover plate and secure with the two screws 

previously removed.

Figure 5-3:

 36/46 model - flow pipe fitted (cover plate removed)

The direction of the bent flow pipe will depend on the flue system 

being used with the boiler.

If a Grant low level balanced flue (Yellow System) or external 

balanced flue system (Green System) is used, the flow pipe must 

be positioned as follows:

• 

If the flue points towards the right of the boiler (viewed from 

the front), the flow pipe must be set to point either to the right 

or to the front of the boiler to avoid clashing with the flue.

• 

If the flue points towards the rear of the boiler, the flow pipe 

must be set to point either to the rear, to the right or to the 

front of the boiler to avoid clashing with the flue.

• 

If the flue points towards the left of the boiler (viewed from 

the front), the flow pipe must be set to point either to the rear, 

to the right or to the front of the boiler to avoid clashing with 

the flue.

Section 5: pipe Connections

page 16

5  pipE CONNECtiONS

Содержание Vortex VTXBH1521

Страница 1: ...UK DOC 0116 Rev 1 1 November 2017 Grant Vortex Boiler House Floor Standing Condensing Oil Boiler Range Installation and Servicing Instructions...

Страница 2: ...e instructions in the caution NOTE Used for emphasis or information not directly concerned with the surrounding text but of importance to the reader PRODUCT CODES COVERED These instructions cover the...

Страница 3: ...tem requirements 20 7 2 Filling the sealed system 21 7 3 Venting the pump 21 7 3 Pressure relief safety valve 21 operation Contents Page 3 8 ELECTRICAL 22 8 1 General 22 8 2 Connecting the power suppl...

Страница 4: ...ted to either a conventional flue system or a balanced flue system as required 1 3 1 For Conventional Flue Applications Where a chimney is to be lined Grant recommends the use of the Grant Orange flue...

Страница 5: ...duct code RBS104 The temperature of the water leaving the boiler to heat the radiators and hot water cylinder is user adjustable The boiler is fitted with an overheat thermostat which allows it to be...

Страница 6: ...imum static head m 28 Minimum circulating head m 1 Boiler thermostat range C 50 5 to 75 4 Limit safety thermostat shut off temperature C 110 3 Maximum hearth temperature C Less than 50 Electricity sup...

Страница 7: ...level 6 Factory settings 15 21 18 5kW 21 26 23 5kW 26 35 31 9kW 36 46 41 5kW 58 70 52 0kW 58 70 64 0kW 7 The combustion door test point may be used for CO2 and smoke readings only Do not use this test...

Страница 8: ...E VIEW 106 629 591 CONDENSATE DRAIN FLOW RETURN 114 Figure 2 4 15 21 21 26 and 26 35 dimensions Figure 2 5 36 46 dimensions DWG NO REV BOILERHOUSE 26 46kW 04 07 17 22621 DATE JOB TITLE BOILERHOUSE SER...

Страница 9: ...DWG NO REV BOILERHOUSE 46 70kW 04 07 17 22622 DATE JOB TITLE BOILERHOUSE SERIES 2 DRAWING TITLE REV DISCRIPTION REV DATE PLAN VIEW REAR VIEW LEFT SIDE VIEW RIGHT SIDE VIEW 271 411 111 443 430 28 1078...

Страница 10: ...ve the burner A spring clip for mounting the sensor is provided with the boiler This should be fixed with the screw provided using the small hole in the front panel of the boiler The fire valve should...

Страница 11: ...2 6 12 9 7 4 8 5 4m Max 300mm Min Min 1 2 3 2 6 12 9 7 4 8 5 11 3 5m Max 10 Key to oil supply diagrams 1 Oil tank 5 External wall 9 Burner 2 Isolating valve 6 Oil filter 15 m max filtration size 10 No...

Страница 12: ...product code ISOLATION1 4 These are available to purchase from Grant UK 3 2 BURNER OIL CONNECTION WARNING The blanking plug supplied in the inlet suction port is plastic and will not provide an oil t...

Страница 13: ...iello RDB burner components 15 21 21 26 26 35 and 36 46kW 8 9 3 10 5 1 6 7 2 4 Figure 3 8 Riello RDB burner components 46 58 and 58 70kW 3 2 2 two pipe connection For either a two pipe sub gravity or...

Страница 14: ...ting systems BS 7593 Code of Practice for treatment of water in domestic hot water central heating systems BS 7671 Requirements for Electrical installations IET Wiring Regulations BS 7291 Thermoplasti...

Страница 15: ...water connections as described in Section 5 If access will be restricted make any connections to the boiler before placing it in its final position Refer to Section 7 if the boiler is to be used on a...

Страница 16: ...the two screws from the top flange of the cover plate and remove cover plate from boiler Refer to Figure 5 2 Figure 5 2 36 46 model dual stat mounting bracket flow and return connections and removable...

Страница 17: ...supplied on a mounting bracket for fitting on to the boiler casing by the installer on site It is to be located on the top of the boiler at the front towards the right hand side Refer to Figures 5 1...

Страница 18: ...pipe is suitable NOTE Copper or steel pipe is NOT suitable and MUST NOT be used Condensate disposal pipes should have a minimum nominal diameter of 22 mm e g use 21 5 mm OD polypropylene overflow pipe...

Страница 19: ...m the trap outlet If there is any discharge of condensate from the overflow outlet this could indicate a blockage possibly due to freezing Turn off the boiler and investigate the cause If necessary co...

Страница 20: ...the expansion vessel position it below the pipe to which it is connected The expansion vessel may be positioned away from the system providing the connecting pipe is not less than 13 mm diameter If t...

Страница 21: ...escaping from the system 3 Top up the system pressure as necessary NOTE Ensure that the expansion vessel used is of sufficient size for the system volume Refer to BS 7074 1 or The Domestic Heating De...

Страница 22: ...Figure 8 3 as follows Switched live Brown to terminal C on the overheat thermostat Earth Green Yellow to the earth terminal marked on the overheat thermostat An earth link not supplied must be fitted...

Страница 23: ...ler Green Yellow Blue Brown Blue Green Yellow Refer to Figure 8 3 for connection details Figure 8 1 2 x 2 port valve control system Cylinder Stat N Grant 2 Channel Wall Mounted Programmer ESKIT 230V 5...

Страница 24: ...f boiler Power supply from controls Power supply to burner L E N N E L Green Yellow Brown Brown Blue Blue Figure 8 3 Dual thermostat wiring diagram NOTE Links and connector to link Neutral wires to be...

Страница 25: ...ILER IN COMP AR TMENT Conventional open flue compartment ventilated from room Conventional open flue compartment ventilated from outside C C D D E Figure 9 2 Air supply for conventional flue boilers 9...

Страница 26: ...the flue should terminate with a standard cowl Refer to the locally applicable Building Regulations BS 5410 1 and OFTEC Installation Requirements OFTEC Technical Books 2 and 4 for further guidance on...

Страница 27: ...directional see Section 9 2 Note Terminal Adjustable section 235 300mm WXA250 100 WXA250 125 100mm dia 125mm dia Locking band C 45 elbow O Top plate Clamp Figure 9 6 Grant Orange flue system in a typi...

Страница 28: ...aptor using the lubricant provided before attempting to fit the flue adaptor 6 Fit the first section of flue into the flue adaptor and secure using the clamp band provided 7 Assemble the remainder of...

Страница 29: ...he following items are additionally available Extensions to extend the flue by 225 mm 450 mm or 950 mm An adjustable extension of 275 to 450 mm A 45 elbow No more than 6 x 45 elbows should be fitted p...

Страница 30: ...tures windows doors etc are shown in Figure 9 15 The terminal must be positioned so as to avoid products of combustion accumulating in stagnant pockets around the buildings or entering into buildings...

Страница 31: ...lanced flue green system Table 9 14 Green system components product codes Item 15 21 and 21 26 models 26 35 36 46 46 58 and 58 70 models Standard starter kit stainless steel GK90B GK200B Short starter...

Страница 32: ...ed for appliances that have been approved for low level flue discharge when tested in accordance with BS EN 303 1 OFS A100 or OFS A101 4 Terminating positions should be at least 1 8 metres from an oil...

Страница 33: ...as shown in Figure 9 19 Side wall Rear wall Note This dimension is given with the boiler pushed back against the rear wall Any clearances must be added to it Hole to be cut in wall Hole to be cut in w...

Страница 34: ...to Figure 10 4 Figure 10 4 Spiral turbulators 26 35 model 5 Check that the baffles are in position Refer to Figures 11 1 11 2 11 3 11 4 and 11 5 as required 6 Re fit the cleaning door and check it is...

Страница 35: ...t boss on the fan housing 6 Replace the screw in the centre of the air adjuster disc A and tighten 7 Re fit the air inlet cover B to the side of the burner and reassemble in reverse order B 1 2 A Figu...

Страница 36: ...r has been moved Under no circumstances may the smoke number be above 1 NOTE It is essential that the air damper is correctly set for clean and efficient operation of the boiler 10 6 Balancing the Sys...

Страница 37: ...House models will indicate the fuel used and the nozzle fitted 11 3 Dismantling Prior to Servicing The procedure for dismantling the boiler is as follows 1 Disconnect the flexible air tube from the bu...

Страница 38: ...Section 11 Boiler Servicing Page 38 Figure 11 1 15 21 and 21 26kW baffles Figure 11 2 26 35kW baffles Figure 11 3 36 46kW baffles Figure 11 4 46 58kW baffles Figure 11 5 58 70kW baffles...

Страница 39: ...lace if necessary 4 Check the electrode and diffuser settings Figure 11 7 1 2 B 0 5 0 3 0 0 2 5 75 A Figure 11 7 46 58 and 58 70 electrode settings 5 To adjust the diffuser disc Loosen the diffuser cl...

Страница 40: ...d adjust 2 Burner pulses Insufficient air supply check the air damper setting and the condition of the fan Check room ventilation is adequate see Section 9 1 Check the nozzle size and type 3 Flame slo...

Страница 41: ...e k c o l b n o i t s u b m o C head set S E Y O N S E Y S E Y S E Y S E Y S E Y S E Y S E Y S E Y S E Y S E Y S E Y S E Y S E Y O N S E Y O N O N O N d n a k c e h C set the s e d o r t c e l e e c...

Страница 42: ...urner exploded diagram 15 21 21 26 26 35 and 36 46kW models 13 1 Riello RDB 2 2 burners 15 21 21 26 26 35 and 36 46 MODELS This section gives exploded views of the Riello burners in the Grant Vortex b...

Страница 43: ...ring kit 3008878 RBS140 10 Fan impellar 3005788 RBS151 11 Air damper assembly 3008647 RBS116 11 Air damper assembly 3008839 RBS166 12 Photocell 3008646 RBS115 13 Capacitor 4 5 F 20071576 RBS149A 14 S...

Страница 44: ...3 3 Riello RDB 3 2 burner exploded diagram 46 58 and 58 70kW models 13 2 Riello RDB 3 2 burners 46 58 AND 58 70 MODELS This section gives exploded views of the Riello burners in the Grant Vortex boile...

Страница 45: ...impellar 3005799 RBS162 11 Photocell 3008646 RBS115 12 Burner cover 3008962 RBS168 13 Electrode assembly 3020121 RBS158 14 Capacitor 5 F 20081251 RBS167A 15 x BSP adaptor 3003602 RBS35 16 Flexible oi...

Страница 46: ...Baffle set complete 58 70 VBS77 Turbulator baffle 360 mm single 15 21 21 26 26 35 and 36 46 VBS05 Turbulator baffle 476 mm single 46 58 and 58 70 VBS03 Access combustion door 15 21 21 26 VBS92 Access...

Страница 47: ...e and its amending directives 2004 108 EC Conforms with the essential protection requirements of the Electromagnetic Compatibility Directive and its amending directives 92 42 EC Conforms with the requ...

Страница 48: ...ds Irritation to eyes Precautions Avoid inhalation of vapour contact with eyes and prolonged or repeated contact with skin After handling always follow normal good hygiene practices Protection Use eye...

Страница 49: ...e information given in the Servicing section of the Installation Servicing Instructions provided with the boiler Recycling Many of the materials used in Grant oil boilers can be recycled these are lis...

Страница 50: ...y electricity consumption At full load elmax kW 0 113 0 154 0 146 0 155 0 215 0 215 At part load elmin kW 0 035 0 047 0 045 0 046 0 064 0 064 In standby mode PSB kW 0 0 0 0 0 0 Useful efficiency Seaso...

Страница 51: ...Notes Page 51 NOTES...

Страница 52: ...Grant Engineering UK Limited Hopton House Hopton Industrial Estate Devizes Wiltshire SN10 2EU Tel 44 0 1380 736920 Fax 44 0 1380 736991 Email info grantuk com www grantuk com...

Отзывы: