Option 36 - Set temperature override rule
This establishes the degree of temperature override
available to the user. Press
+
until Option 36 is
displayed, use
V
and
Λ
to select required setting.
Setting 0
No limit (factory setting)
Setting 1
Limited to ±2°C
Setting 2
No override allowed
Option 37 - Set time duration of override rule
(Option 36 set to 1 or 2)
This establishes the duration of a temperature
override available to the user. Press
+
until Option 37
is displayed, use
V
and
Λ
to select required setting.
Setting 0
Next event (factory setting)
Setting 1
1 hour
Setting 2
2 hours
Setting 3
3 hours
Setting 4
4 hours
Option 38 - Relay state on low battery detect
(battery products only)
This establishes the position that the relay is driven to
when the unit shuts down due to low battery state.
Press
+
until Option 38 is displayed, use
V
and
Λ
to
select required setting.
Setting 0
Relay parked with output
OFF
(factory setting)
Setting 1
Relay parked with output
ON
Option 40 - Number of Events per Day
This sets the thermostat to operate with either 2, 4 or
6 switching events per day or to run it in stat mode.
Press
+
until option 40 is displayed, use
Λ
or
V
to
select required setting.
1
Stat mode
2
Two switching events per day
4
Four switching events per day (Factory setting)
6
Six switching events per day