Grandaire R4H3 Series Скачать руководство пользователя страница 2

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pump

2

428 01 5301 05

Specifications subject to change without notice.

INSPECT NEW UNIT

After uncrating unit, inspect thoroughly for hidden

damage.  If damage is found, notify the transportation

company immediately and file a concealed damage

claim.

SAFETY CONSIDERATIONS

Consult a qualified installer, service agency, or the

dealer/distributor for information and assistance. The

qualified installer must use factory authorized kits and

accessories when modifying this product. Refer to the

individual instructions packaged with the kit or accessory

when installing.
The weight of the product requires careful and proper

handling procedures when lifting or moving to avoid

personal injury. Use care to avoid contact with sharp or

pointed edges.
Follow all safety codes. Wear safety glasses, protective

clothing, and work gloves. Use a heat sinking material 

such as a wet rag 

 during brazing operations. Keep a fire

extinguisher available. Consult local codes and the

National Electric Code (NEC) for special requirements.
Improper installation, adjustment, alteration, service or

maintenance can void the warranty

.

!

CAUTION

CUT HAZARD
Failure to follow this caution may result in proper-

ty damage.
Sheet metal parts may have sharp edges or burrs.

Use care and wear appropriate protective clothing

and gloves when handling parts.

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in

personal injury or death.
Before installing, modifying or servicing system,

main electrical disconnect switch must be in the

OFF position. There may be more than 1

disconnect switch. Lock out and tag switch with a

suitable  warning label.

!

CAUTION

PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in proper-

ty damage
R

410A systems operate at higher pressures than

R

22 systems. When working with R

410A sys-

tems, use only service equipment and replace-

ment components specifically rated or approved

for R

410A service.

LOCATION

Check local codes for regulations concerning zoning,

noise, platforms, and other issues.
Locate unit away from fresh air intakes, vents, or

bedroom windows. Noise may carry into the openings

and disturb people inside.
Locate unit in a well drained area, or support unit high

enough so that water runoff will not enter the unit.
Locate unit away from areas where heat, lint, or exhaust

fumes will be discharged onto unit (as from dryer vents).
Locate unit away from recessed or confined areas where

recirculation of discharge air may occur (refer to

CLEARANCES section of this document).
Roof

top installation is acceptable providing the roof will

support the unit and provisions are made for water

drainage and noise/vibration dampening.

NOTE:

 Roof mounted units exposed to wind may require

wind baffles. Consult the manufacturer for additional

information.

CLEARANCES

When installing, allow sufficient space for airflow

clearance, wiring, refrigerant piping, and service. Allow

24 in. (610 mm) clearance to service end of unit and 48

in. (1219.2 mm) above unit. For proper airflow, a 6 in.

(152.4 mm)  clearance on one side of unit and 12 in.

(304.8 mm) on all remaining sides must be maintained.

Maintain a distance of 24 in. (609.6 mm) between units

or 18 in. (457.2 mm) if no overhang within 12 ft.

(3.66m). Position so water, snow, or ice from roof or

eaves cannot fall directly on unit.
On rooftop applications, locate unit at least 6 in.

(152.4mm) above roof surface.

UNIT SUPPORT

NOTE:

 Unit must be level 

|

 2 degrees {

a

 inch rise or3/8 fall

per foot of run (10mm rise or fall per 305 mm of run) } or

compressor may not function properly.

A. GROUND LEVEL INSTALLATION

The unit must be level and supported above grade by

beams, platform, or a pad. Platform or pad can be of open or

solid construction but should be of permanent materials

such as concrete, bricks, blocks, steel, or pressure

 treated

timbers approved for ground contact. Soil conditions must

be considered so that the platform or pad does not shift or

settle and leave the unit partially supported. Minimum pad

dimensions are shown in Figure 2.
If beams or an open platform are used for support, it is

recommended that the soil be treated or area be graveled

to reduce the growth of grasses and weeds.
To minimize vibration or noise transmission, it is

recommended that supports not be in contact with the

building structure. However, slabs on grade constructions

with an extended pad are normally acceptable.

Содержание R4H3 Series

Страница 1: ...e following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on p...

Страница 2: ...r intakes vents or bedroom windows Noise may carry into the openings and disturb people inside Locate unit in a well drained area or support unit high enough so that water runoff will not enter the un...

Страница 3: ...1 4 540 26x26 660x660 31 1 8x31 1 8 791x791 9 1 16 230 6 1 2 165 24 5 8 625 31 1 2x31 1 2 800x800 C FASTENING UNIT DOWN If conditions or local codes require the unit be attached in place remove the k...

Страница 4: ...ine Applications Guideline for line set sizing NOTE Total line set length must not exceed 200 feet 61m NOTE A crankcase heater must be used when the refrigerant line length exceeds 80 feet 24 4m If ou...

Страница 5: ...operation Do not bury more than 36 1m of line set under ground Refrigerant may migrate to cooler buried section during extended periods of unit shut down causing refrigerant slugging and possible com...

Страница 6: ...efer to Figure 5 Replace valve core when brazing is completed WARNING FIRE HAZARD Failure to remove refrigerant and oil charge before brazing could result in personal injury death and or property dama...

Страница 7: ...ur During this time dry nitrogen will diffuse throughout the system absorbing moisture 5 Repeat this procedure as indicated in Figure 7 6 After the final evacuate sequence confirm there are no leaks i...

Страница 8: ...e panel or a properly driven and electrically grounded ground rod Wiring Connections Make all outdoor electrical supply Line Voltage connections with raintight conduit and fittings Most codes require...

Страница 9: ...DOOR FAN COIL WHEN INSTALLING OUTDOOR THERMOSTATS SYSTEMS WITH ONE OUTDOOR THERMOSTAT G R W 3 C O R G R W 3 C E C W 2 Y W 2 O R C W 2 Y W 2 C L G Y E O R SYSTEMS WITHOUT OUTDOOR THERMOSTATS C G R W 2...

Страница 10: ...circuit and operation of the defrost thermostat itself will not be observed Skip to 3 2 Use a volt meter to confirm there is no voltage across the DFT leads 24 volts across the SFT terminals indicates...

Страница 11: ...ithout notice Figure 12 Defrost Control Board R8 OF1 K1 O1 R21 C2 R6 H9C1 C US R14 R13 D13 R7 C4 C10 JW2 JW1 D3 C16 C7 R28 D6 JW3 C13 R4 R1 R2 R3 R11 R5 R26 D1 D2 D10 A29 R9 D4 C19 C9 C1 OF2 CEBD43052...

Страница 12: ...range NOTE If line length is beyond 80 feet 24 4m or greater than 20 feet 6 1m vertical separation See Long Line Guideline for special charging requirements A UNITS WITH COOLING MODE TXV Units install...

Страница 13: ...34 37 24 3 5 7 8 10 12 13 16 17 19 21 80 5 8 12 15 18 21 25 28 31 35 27 3 4 7 8 10 12 14 16 17 19 85 8 11 15 19 22 26 30 33 29 4 6 8 11 12 14 17 18 90 5 9 13 16 20 24 27 31 32 3 5 7 9 11 13 15 17 95 6...

Страница 14: ...26 299 90 32 88 31 86 30 84 29 82 28 80 27 308 92 33 90 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88...

Страница 15: ...3 FS M U 4P24 A TXV 5 3 ED 4X30 EA 4X30 14 17 A 3 EN 4X30 3 3 EHD4X30A 3 3 FEM4 P X 30 A TXV 3 FSA4X30 A 3 FEA4X30 A 3 FXM4X30 A 5 5 FS M U 4P30 A TXV 5 5 FVM FCM 4X36 5 3 ED 4X36 EA 4X36 14 17 21 A 5...

Страница 16: ...cer bringing on the first bank supplemental electric heat and providing electrical potential to the second heater sequencer if used If outdoor temperature falls below the setting of the outdoor thermo...

Страница 17: ...ith other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not i...

Отзывы: