
5
Due to the hazardous nature of electrical and mechanical requirements only trained and
qualified personnel should install and service heating and cooling equipment.
WARNING
It is important to check airflow and make sure that the furnace does not operate above
the temperature rise specified in the specifications, Section 6. This is particularly
important if a cooling or heat pump coil has been installed. High limit thermal protectors
should never engage during normal operation of the furnace. The high limit protectors
are designed to engage during the improper functioning of the blower or when the air filter
has not been kept clean.
Fig 1
Horizontal Installation
Selecting a location
This furnace shall be centrally located in relation to the outlet registers. All ductwork shall be
suitably sized with external static pressure in mind to ensure adequate air distribution.
These furnaces are suited for vertical up flow, down flow and horizontal installations. This furnace
shall not be installed on its front or back. To install this unit on its front or back would result in
inadequate access for servicing. Always ensure that when suspending this furnace that suitable
structural support is available and provides adequate access to the control and fan
compartments for service.
Note : Return air opening must be cut out
to knockouts provided. Minimum return air
opening size, 18’’ X 18’’
Caution : Return air openings shall not be
installed in back panel.
Supply air plenum must be constructed of
suitable materials and sized by installing
contractor so as to be of sufficient strength
to support furnace and accessory fittings
and materials.
Minimum 1’’ x 1’’ x 1/8’’ angle
Note : Field selected suspension
materials must be sized by the installing
contractor and be of sufficient strength to
support air handler weight of 100 lbs and
connected accessory fittings and
materials.
Upflow Installation
Counterflow Installation
Return air knock out.
Содержание KHE-00-G010-03
Страница 13: ...13 ...