26
Gram
Commercial
Technical information
765041466
Description :
Operation- and servicemanual
Gram Process KPS
Compiled. Latest
revision. Deleted.
Date Name Date Name
Rev.no
Date Name
30.09.11 JP
000
Parameter
Description
Default
Min.
Max.
B09
Surface temperature min. value allowed during phase 3
0
-50
C 99
C
B10
End of IFR cycle core temperature
4
C -50
C 99
C
B11
Delay from the positive result of the probe test, for
starting the procedure to determine the end of phase 1
60 sec
0 sec
99 sec
B12
Phase 1 temperature detection time
30 sec
0 sec
99 sec
B13
Phase 1 min. duration
6 min
0 min
99 min
B16
Defrost on starting IFR cycle
(0=no; 1=yes)
0 0 1
B17 Inhibition
temperature
90
C -50
C 99
C
B18
Room setpoint in the event of automatic switch to time or
temperature mode
-7
C -50
C 99
C
B19
Max. duration possible for IFR process
999 min
1 min
999 min
B20
Surface temperature safety value determining the end of
phase 1
-1
C -50
C 99
C
B21
First coefficient of the room sensor curve (phase 3)
10
-90
99
B22
Second coefficient of the room sensor curve (phase 3)
-50
-90
99
B23
Storing activation at the end of IFR cycle
(0=no; 1=yes)
1 0 1
B24
Room sensor setpoint in storing
2
C -90
C 90
C
B26
Core temperature limit for the timer start
999
0
999
B27
Adjuster of fan speed in the phase 3
99
0
99
B28
Cold pulse adjuster
10
0
99
Communication
ADD Device
address
1
1
147
SC Serial
control
0=not activated
1=print
2=ModBus (RS485)
1 0 2
MB1
Baud rate: 0=2400; 1=4800; 2=9600; 3=18200
2
0
3
MB2
Parity: 0=no parity; 1=odd; 2=even
2
0
2
Type of cycle
G01
Positive QC cycles only:
0=positive and negative
1=positive only
0 0 1
Содержание 860120020