4 GRX-WCI Installation Instructions

Communication Link Wiring

• PELV (Class 2: USA) low-voltage wiring connects the

GRX-WCI to GRX-3000/4000 control units and other
components.

• You can link up to 8 control units and up to 16 total

GRX-WCIs, wallstations, and/or control interfaces, for a
total of 24 control points.

System Communications

• If used as part of an unaddressed system (control

units not addressed), the GRX-WCI will affect all
control units on the system.

• For an addressed system (control units addressed),

follow the steps below.

1.

Enter program mode

(only one GRX-WCI can be in

program mode at a time). Press and hold the program
button for about 3 seconds, until the LED starts
flashing.

2.

Identify the control unit(s)

that you want to “listen” to

this GRX-WCI. (Control units must be addressed!)
Press and hold the top scene button on the control
unit for about 3 seconds, until the LEDs flash in
unison. Repeat for each control unit that you want to
“listen” to the GRX-WCI.

Note:

To make a “listening” control unit not listen to a

GRX-WCI, put the GRX-WCI in program mode, then
press the “listening” control unit’s OFF button until
the LEDs stop flashing.

3.

Exit program mode.

Press and hold the program

button for about 3 seconds, until the LED stops
flashing.

Contact Closure Wiring

• Connect the desired input(s) and common wires to the

switch provided by others.

• Cap off unused input wires.

Switch (provided by others).
If input switch is solid state,
must have a solid-state
output with an on-state
saturation voltage less than
1 V

at 1 mA and an 

off-state leakage current of
less than 1 mA.

Common

Input 1

LUTRON

Control unit

LEDs flash in unison

Press here
for “listen”

R

Program button

Wiring

Note:

Use appropriate wire connecting devices

as specified by local codes.

To other control
interfaces

(2) 2.5 mm

2

(#12 AWG )

(2) 2.5 mm

2

(#12 AWG )

(2) 1.0 mm

2

(#18 AWG)

twisted, shielded pair from
terminals 3 to 3 and 4 to 4

Drain wires

4   3   2   1

(2) 1.0 mm

2

(#18 AWG)