5. Specifications
7
5. Specifications
5.1 Environmental specifications
5.2 Electrical & mechanical specifications
5.3 Fuses
Operating temperature:
-5 °C to +45 °C at 12A
Operating relative humidity:
20 to 95 % without condensation
Altitude:
> over 2000 m. Max operating temperature decreases 5°C
every 1000 m. Cooling operates transversally.
Storage temperature:
-25 to +85 °C.
Storage relative humidity:
10 to 95 %.
Mains input voltage (single-phase) 220-240 VAC / 50-60 Hz
Power consumption at full load
760 W
Maximum primary current @ 195 V 4A
Protection Class
Class 1
Neutral and earthing systems
TT, TN, IT
Mains circuit breaker
two pole circuit breaker (D curve) to be provided upstream
Rated output voltage
48 VDC
Floating voltage (half load)
54.4 VDC +/-0.5%
Maximum output current
(total for all 9 outputs)
150A total
Main outputs (6)
40A max.
Auxiliary outputs (3)
5A max.
Rated output current (without
reducing battery capacity)
12A max.
Dimensions (wxhxd)
483 x 44.5 x 310 mm (19”,2U high)
Weight
6 kg
F1 Mother board (AC mains input)
8A, type: T(slow), breaking capacity 1500A, size: 5x20
F8 Mother board (to battery)
12.5A, type: T (slow), size: 5x20
F1 to F6 main outputs
32A, type: gG, size: 10x38
Faux1 to Faux3 auxiliary outputs
5A, type: F (fast), size: 5x20
External Battery fuse (not included) Ib max (when mains not present), type gG