Connect Power
Power
Power
The electrical control panel comes already attached
and wired to the ram, however before the supply unit
becomes functional you must connect the electrical
control panel to a power source.
All electrical wiring must be done by a qualified
electrician and comply with all local codes and
regulations.
Note
Required voltage and amperage is noted on
the control panel label. Before running power
to the unit, make sure the plant electrical
service meets the machine’s electrical
requirements. Branch circuit protection shall
be provided by the end user.
Use copper conductors rated 600 volts minimum and
167°F (75°C) minimum only. Torque to 55 in-lb (6.2
N•m).
Table
Table
Table 2
2
2 Electrical
Electrical
Electrical Requirements
Requirements
Requirements
Elec-
Elec-
Elec-
trical
trical
trical
Panel
Panel
Panel
Voltage
Voltage
Voltage
Hz
Hz
Hz
Phase
Phase
Phase
Platen
Platen
Platen
Full
Full
Full
Load
Load
Load
Amps
Amps
Amps
AWG
AWG
AWG
EF, ES 90
3 AWG
230 V
50/60
3
EM
100
3 AWG
EF, ES 90
3 AWG
400
V/N
50/60
3
EM
100
3 AWG
EF, ES 45
8AWG
400 V
50/60
3
EM
50
8AWG
EF, ES 45
8AWG
480 V
50/60
3
EM
50
8AWG
3
EF, ES 50
8AWG
600 V
50/60
3
EM
50
8AWG
EF
Standard Finned Bottom
EM
Mega-Flo
ES
Smooth Bottom
1.
Locate the opening in the control panel’s top
housing for the conduit that will enclose the wire
from the facility’s power source. The hole will
accept a a cord diameter range of 0.7–1.2 in
(17–30 mm).
2.
Thread the wire from the power source into the
control panel housing, and then connect the
power source wires to the appropriate terminals
on the DISCONNECT switch.
ti26959a_17C137
Figure 12
To reduce the risk of fire, explosion, or electric
shock, the resistance between the supply unit
components and true earth ground must be
less than 0.25 ohms.
3.
Connect the ground wire to the ground lug.
Have a qualified electrician check the resistance
between each Therm-O-Flow system ground and
the true earth ground. The resistance must be
less than 0.1 ohms. If the resistance is greater
than 0.1 ohms a different ground site may be
required. Do not operate the system until the
problem is corrected.
Note
Use a meter that is capable of measuring
resistance at this level.
334130D
19
Содержание Therm-O-Flow 200
Страница 48: ...Repair Figure 28 48 334130D...
Страница 56: ...Repair Figure 34 Inside of Electrical Control Enclosure 56 334130D...
Страница 59: ...Electrical Schematics 400V 400V 400V 3 3 3 Phase 50 Phase 50 Phase 50 Hz Hz Hz 334130D 59...
Страница 60: ...Electrical Schematics 400 600VV 400 600VV 400 600VV 3 3 3 Phase 60 Phase 60 Phase 60 Hz Hz Hz 60 334130D...
Страница 61: ...Electrical Schematics AWB AWB AWB and and and MZLP 1 MZLP 1 MZLP 1 334130D 61...
Страница 63: ...Electrical Schematics MZLP MZLP MZLP Zones Zones Zones 334130D 63...
Страница 67: ...Parts Electrical Electrical Electrical Module Module Module 334130D 67...
Страница 68: ...Parts 68 334130D...
Страница 94: ...Accessories and Kits 94 334130D...