Pump screen 3 sets the pressure alarm limits for the
pump.
Figure 63 Pump Screen 3
Pressure
Pressure
Pressure Alarm
Alarm
Alarm and
and
and Deviation
Deviation
Deviation Limits
Limits
Limits
Inlet fields are only active if Inlet
Inlet
Inlet Pressure
Pressure
Pressure
, is set to Monitor; they
are grayed out if set to Disabled. Outlet fields are
active at all times.
• Alarm and Deviation ranges are 0-300 psi for
low pressure systems, and 0-1500 psi for high
pressure systems.
• Setting to 0 will disable the alarm. The Inlet Alarm
High and Outlet Alarm High cannot
cannot
cannot be disabled.
• Alarms and Deviations will display when the inlet
or outlet pressure drops below the low limit or
exceeds the high limit.
NOTE:
NOTE:
NOTE: Outlet Alarm Low is only enabled for systems
using Flow Control.
Pump
Pump
Pump Screen
Screen
Screen --- Material
Material
Material Assignment
Assignment
Assignment
For systems using Multiple Guns, see
Appendix B: Multiple Guns, page 118
, for
more detail.