Deviations and Advisories
There are two types of errors that can occur. Errors
are indicated on the display.
Deviations, indicated by
, require attention, but
not immediately.
Advisories, indicated by
, do not require
attention.
If a deviation or advisory occurs, the system
continues running. The error code and the
or the
flash on the screen. If multiple alarms
occur, F2 and F3 have higher priority than MF. They
will appear first and must be cleared first.
Alarm Log Logic: If Alarm Auto Clear is enabled,
the system will not log the same alarm twice. For
example, if the system goes back forth between low
flow (F2) and normal, the system will log this error
only once, to keep the log from filling up before the
operator corrects the condition.
If Alarm Auto Clear is not enabled, each alarm will
log only once if the operator corrects the condition
and then clears the alarm. The alarm will log twice
if the operator clears the alarm before correcting the
condition.
The following table explains the error type that is
associated with each error code and icon.
Deviations and Advisories
Icon
and
Code
Description
How to Correct and Clear
MF
Advisory alarm. If enabled, the
maintenance totalizer alarm displays
when the user-set maintenance target
value is reached.
Reset Maintenance Totalizer to zero (see
). Perform maintenance.
Press
to clear alarm. Alarm will not clear until
Maintenance Totalizer has been reset to zero.
F2
Deviation alarm. If enabled, the flow
rate low alarm displays when the
flow rate is lower than the user set
minimum.
Adjust flow rate, reset minimum flow target (see
), or disable alarm (see
).
Press
to clear screen. The alarm will not clear if the
flow rate is still lower than the user set target.
F3
Deviation alarm. If enabled, the flow
rate high alarm displays when the
flow rate is higher than the user set
maximum.
Adjust flow rate, reset maximum flow target (see
), or disable alarm (see
).
Press
to clear alarm. The alarm will not clear if the
flow rate is still higher than the user set target.
3A2614H
31
Содержание ProControl 1KE
Страница 16: ...Installation Typical Installation Non Hazardous Location Hazardous Location 16 3A2614H ...
Страница 34: ...Parts Parts Kits for Hazardous Location 24L085 24P593 24P595 24L087 24P597 24L089 24L091 34 3A2614H ...
Страница 36: ...Parts Kits for Non Hazardous Location 24L084 24L086 24L088 24L090 24P592 24P594 24P596 36 3A2614H ...
Страница 38: ...Parts Fluid and Air Control Parts 38 3A2614H ...
Страница 52: ...Notes Notes 52 3A2614H ...