Electrical Connections
Install per Graco Control Drawing 16M169, in Manual
332013. See also Figure 1.
1. Connect main power supply cord (E, not
supplied) through strain relief to terminals L and
N on the power supply unit.
Note: Use either strain relief (5) or (6), depending
on the size of the cord.
2. Connect power cord ground wire (W) to ground
terminal block (Y).
3. Connect IS power cable (F) per the following
table.
Table 1 Power Barrier Wiring Connections
Power Cable Leads
Barrier Connection
Brown (power)
Connector 1
Blue (common)
Connector 2
Glossy Black (ground) and Black (drain) connect to
ground block.
Table 2 I/P Transducer Wiring Connections;
Cables 16P790 (non-IS) and 16V142 (IS)
Wiring Table
Wire Color
Function
DIN Connector
Gray
Control A
Connector 1
Blue
Common
Connector 2
Figure 1
KEY
E
Inbound AC Power Cord
F
Power Cable
W
Ground Wires
X
Barrier
Y
Ground Block
5
Strain Relief Fitting
6
Strain Relief Fitting
14
3A2614H