GPI GBM 110 Скачать руководство пользователя страница 7

6

THEORY OF OPERATION

Relay B Operation
Relay B can be programmed as a prewarn relay or grand 
total/batch counter alarm.  

When Relay B is set for Prewarn, Relay B will energized 
when the batcher is started.  Relay B will drop out when 
the count is at the selected number (Preset B) before 
final Preset A.  This is often used for slow down (2 stage 
batching).

When Relay B is set for total (Batch or Grand Total), 
Relay B will energize for the selected time duration when 
the Batch/Grand Total reaches Preset B. If the Relay is 
set to latch, it can be reset by resetting the Batch/Grand 
Total. (as described above).

Relay B as Scaled Pulse Output
To  use  output  B  as  a  scaled  output  proceed  as  fol-
lows:

1) Select 

gr tot

 under 

count 

section of menu.

2) Select 

tot 

under 

relay 

section of menu.

3) Enter the desired duration for the B Relay.
4) Set 

Pre B

 at desired scaling (

pre b

 is a  divider). 

  Maximum output frequency is 15 pulses/second.

Presets
Preset A can be viewed and changed by pressing the 
"PRE  A"  button.    The  present  Preset  A  will  appear.  
Press buttons "A" through "E" to load in desired Preset 
A. Press the ENTER button once to enter.

Preset B can be viewed and changed by entering the 
program menu.  Press the PRGM button.  PRE B will ap-
pear.  Press ENTER.  The present Preset B will appear.  
Press buttons "A" through "E" to load in desired Preset 
B. Press the ENTER button once to enter.

VIEW Button
The VIEW button allows you to alternately view:

 

1. Count of "A" (Batch)

 

2. Rate of "A" (Batching speed)

 

3.*  A)  Grand Total if "

gr tot

" is selected 

 

 

B)  Number  of  Batches  if  "

BA  tot

"  is  se-

lected

* All decimal points are inverted when Grand/Batch Total 

is being displayed.

Batching
After the batcher has been programmed, it will operate 
as follows:

The unit will reset to "0" (count up mode) or load Preset 
A (count down mode) when RESET/STOP is activated. 
(front button or rear input)

When Start (front button or rear input) is activated, Relay 
A (and Relay B if Prewarn is selected) will energize and 
the right decimal will light.  The unit will count in engi-
neering units corresponding to the input scaling.

If Prewarn is selected for Relay B, Relay B will drop out 
when the count is at the selected number (Preset B) 
before final Preset A.  When Preset A (or "0") is reached, 
Relay A drops out and the right decimal turns off.  (The 
right decimal turns on whenever Relay A is energized).  
At the end of the batch the display is immediately loaded 
with "P" and Preset A number.  At this point you can:
 

Press START to reset and start another batch

 

Press PRE A to change Preset A

 

Press VIEW to view count (over-run)

 

Press RESET/STOP to reset to "0" (Preset A)

If RESET/STOP is activated while the unit is started, 
Relay A (and Relay B if Prewarn) will drop out and the 
last count will remain on the display. Press START to 
continue the batch or RESET/STOP to abort the batch. 
All starts are inhibited if RESET/STOP is held active.

Grand Total or Batch Counter
The second counter (displayed with inverted decimals) 
can be programmed as a Grand Total or Batch counter.  
The  Grand  counter  counts  the  grand  total,  the  Batch 
counter counts the total number of complete batches.  
These counters can only be reset from the front panel 
while viewing them.  To reset, press the VIEW key until 
the displays shows a number with all decimals lit.  Press 
RESET/STOP to reset. 

Содержание GBM 110

Страница 1: ......

Страница 2: ...RING 4 THEORY OF OPERATION 6 MILIVOLT INPUT OPTION JUMPER SELECTIONS 7 FRONT PANEL OPERATIONS 8 PROGRAMMING FLOW CHART 8 DEFINITIONS OF MENU PROMPTS 9 CALCULATING SCALE FACTORS 11 PROGRAMMING 12 TROUBLESHOOTING GUIDE 17 WARRANTY DECODING PART NUMBER ...

Страница 3: ... 0 587 14 91 4 245 107 8 BEZEL GASKET CUSTOMER PANEL Panel Thickness 0 062 1 5 to 0 187 4 7 max 3 925 99 7 SPECIFICATIONS continued Application Panel Cutout Dimensions Flowmeter Solenoid Valve STOP RST ENTER LOCK PRE A PROG VIEW START A B C D E ...

Страница 4: ...per mounting procedures are followed and the required and supplied hardware is correctly used If the panel in which the unit is mounted is less than 125 of an inch thick the possibility exists that there will be some flex ing Should this flexing occur the resulting deformation of the panel could cause a loss of the water tight seal In case this should occur the use of silicone or other sealant wou...

Страница 5: ...er input lines Also keep these input lines isolated from inductive lines from devices drawing heavy loads If there is a possibility of electrical noise we recommend using shielded cable with the shield being hooked to the D C ground terminal on the instrument and to earth at one point in the circuit preferably at the D C ground terminal of the unit 3 Output lines The unit has two relay outputs Whe...

Страница 6: ...o 40Hz select Lo CPS or solid state switches select hi CPS up to 9 99KHz No rear terminal jumpers are required Use PNP sourcing type pulsers Wiring Terminations Magnetic Pickup 30 mV Pulse Input High Impedance 4 30VDC Pulse Input with Analog Output Typical Flowmeter Connections 1 COMMON 2 N O N C NPN 3 COMMON 4 N O N C NPN 5 COUNT 6 START 7 12VDC OUT DC IN 8 DC GROUND 9 STOP RESET 10 NOT USED 11 A...

Страница 7: ...t is se lected All decimal points are inverted when Grand Batch Total is being displayed Batching After the batcher has been programmed it will operate as follows The unit will reset to 0 count up mode or load Preset A count down mode when RESET STOP is activated front button or rear input When Start front button or rear input is activated Relay A and Relay B if Prewarn is selected will energize a...

Страница 8: ...6 U U5 R8 R9 C1 C2 C9 B If the unit has the millivolt input bd 20229 the count input can be separately solder jumper programmed to accept either a low millivolt or 4 30 V input Each unit shipped is programmed according to part number If solder jumpers are made the part number should be modified to reflect the changes made C CLOSE O OPEN 4 30V INPUT Millivolt INPUT J1 O J2 C J3 O J1 C J2 O J3 C ...

Страница 9: ...N MODE PRGM PRGM PRGM PRGM pre b RUN MODE ENTER ENTER PRGM hi cps lo cps PRGM SECS NNiNS hours PRGM tot preuu PRGM Start Here PROGRAMMING FLOWCHART A STOP RST B C D E ENTER LOCK PRE A PROG VIEW START Press to STOP RESET in operating mode Press to EN TER in program ming mode Press to enter LOCK code for panel lock Press to view or change Preset A Press to alter nately view Rate A Total or B Total P...

Страница 10: ...here the decimal is desired Changing the decimal will change the decimal location in the counter s presets and rate display gr tot GRAND TOTAL This sets the second counter to count the Grand Total ba tot BATCH TOTAL This sets the second counter to count the number of Batches HI CPS HIGH COUNTS PER SECOND This sets the unit for high count speeds 0 9 99 kHz LO CPS LOW COUNTS PER SECOND This sets the...

Страница 11: ...iewed but not changed Start and Stop Reset buttons will still operate CODE LOCK CODE This message code will flash on display for approximately 3 seconds It will be followed by a 5 digit number xxxxx The number you enter here will be the code to lock and unlock the unit RELAY RELAY This portion of the menu allows you to set your relay operation variables preuu PREWARN When this is selected Relay B ...

Страница 12: ...r To display hundredths of gallons 0 01 gal enter 6 784 for the factor SCALING FACTOR EXAMPLES Flow Batching You want to fill a 55 0 gallon drum The flow sensor gives 387 pulses per gallon Solution Dial in a scale factor of 38 7 38 7 to display 0 1 gal 387 for whole gal Under count set dploc to dplo c to read tenths of gallons Set PRE A at 55 0 Wire Relay A to solenoid valve UNITS CONVERSION CHART...

Страница 13: ... the decimal is desired To clear the decimal press the arrow key furthest to the right PRGM This is the scaling factor for the count input To change press the arrow key under the digit s to change Press ENTER to enter the displayed value STEP 2 REMARKS This section of the menu is used to set Preset B value This is Preset B To change press the arrow key under the digit s to change Press ENTER to en...

Страница 14: ...digit location To clear the decimal press the arrow key furthest to the right Press the ENTER key to enter the displayed location This section sets the second counter operation Press the program key to choose GR TOT Grand Total or BA TOT Batch Total Press the ENTER key to enter the displayed choice Press the PRGM key to choose HIGH CPS 0 9 99KHz or LOW CPS 0 40Hz Press the ENTER key to enter the d...

Страница 15: ...ts to change Press ENTER to enter displayed value This sets the number of significant figures to be displayed Press the arrow key under the digit to change Press ENTER to enter displayed value This sets the delay time 2 to 24 sec that the unit will look for valid input data before the display falls to 0 Press the arrow key under the digits to change Press ENTER to enter displayed value pre b facto...

Страница 16: ...e After CODE flashes the display will show the existing lock code To change the code press the key under each digit to be changed Press ENTER to enter displayed value see below to turn lock ON or OFF Key in the lock code see programming step 4 by pressing the keys under the digits to be changed Press the ENTER key to enter the displayed code After the code is entered the unit will display LOC unit...

Страница 17: ...on 01 to 99 99 sec that relay B will remain energized If 00 00 is selected the relay will latch until reset PRE A Preset A Batch Amount The set point at which output A will drop out after started If the displayed value is not the de sired preset press the keyunder the digit s to be changed PRE B Preset B a Tot selected The set point at which output B will energize b preuu selected The number of co...

Страница 18: ...s causes the counter to auto reset at the preset 1 The menu flow chart and the setup steps show the setup for units with all of the available options Options not ordered will be suppressed in the programming menu 1 Recheck power wiring 1 Use a different power supply or install a surge suppressor 1 Recheck input wiring 2 Recheck scale factors and factor calculations 3 Replace transmitting device 4 ...

Страница 19: ......

Отзывы: