Components and Operation
English, Revision 09, Date: 13.12.2016
27
PDO_2 is transmitted with identifier 0x280 + node address. It contains 8 bytes accord-
ing to the following table.
The synchronous identifier is 0x80. It is possible to read out this parameter under index
[1005,00], but it is not possible to change it.
4.2.3.4.2
Heartbeat
The heartbeat mode is supported. Whenever a heartbeat time > 0 is set in the CAN
menu, the device status is transmitted under identifier (0x700 + node address) each
time the heartbeat timer has expired. The guard time is set to 0 afterwards.
4.2.3.4.3
Node Guarding
Whenever the Heartbeat time is set to 0, the device replies to a Remote Transmission
Request of the Identifier (0x700 + Node address) with the device status (refer to Table
14 above), while the highest bit changes. The device does not monitor the timely re-
ception of RTR Frames.
4.2.3.4.4
Description of the Service Data Objects (SDOs)
The service data opject is used to access to the object index. An SDO is always trans-
mitted with a confirmation, i. e. each reception of the message is acknowledged. The
identifiers for read and write access are:
Value
Variable
Value range
Comment
Sum Voltage
unsigned 16
0...1023
Voltage of the reference antenna coil
Dif Voltage
signed 16
0...±1023
Voltage of the positioning coil
Codes read
unsigned 8
0...255
Number of code readings
Voltage
unsigned 8
0...255
Operating voltage of the antenna [100 mV]
Power
unsigned 8
0...255
Power consumption of the antenna [10 mA]
Temperature
signed 8
-23...61
Board temperature [
o
C]
Table 13
Variables of PDO_2
Node status
Code
stopped
0x04
preoperational
0x7f
operational
0x05
Table 14
Coding of the Node status
Read access
0x600 + Node address
Write access
0x580 + Node address
Table 15
Identifiers for read and write access