Gossen Metrawatt GmbH
The following selections can be made with the following sub-menus, depending on the
summator type:
U1601/3:
Channel mode 0 ... 8
U1602:
Channel mode 0, 4 ... 8
0: OFF:
The channel is switched off entirely and all functions are deactivated.
1: ANA:
The applied analog quantity is displayed for this channel with the
corresponding “A UNIT” (see A-UNIT parameter on page 37).
2: P
E:
PMOM=ANA
ENERGY (see chapter 5.2)
3: Count:
A binary input quantity is used for energy measurement in accordance
with the S0 standard (COUN) (see chapter 5.2).
4: LON
Measured energy data are made available to the system via linking
amongst various LON users.
5: LON-ANA Analog values via LON for A2000, A210/A230, DME400, U1661,
U128X W1, U138X W1, U228x W1 and U238x W1 (see chapter 5.5)
6: LON-PE
Same as LON-ANA, plus energy is calculated based on LON analog
values (see chapter 5.5)
7: LON-INP Binary inputs via LON for U1660
8: LON-REL Relay outputs via LON for OCL210.
Channel Name
Each physical channel can be assigned a name for the purpose of improved
identification. The name need not be unique, unless it is also used as a field name for a
database. The length of the name may not exceed 8 characters, and it must be at least
one character long. ECL command: CHANNEL
Long Name
An expanded channel name including up to 20 characters. ECL command: LNAME
E-Unit, P-Unit
A freely definable energy unit of measure (e.g. kWh) and power unit of measure (e.g. kW)
can be assigned to each physical channel. The units of measure may not exceed a
length of 4 characters, and must be at least one character long.
ECL command: EUNIT, PUNIT
Each physical channel can be made visible or invisible for queries from the control panel
or for “*” - lists during interpreter operation. The function of the channel remains
otherwise unchanged! If, for example, only channels 1 through 3 are visible, values can
only be queried for these channels in the normal display mode, and the instrument
appears to be a 3 channel device. If “Etot*”, is queried during interpreter operation, total
energy is only displayed for these three channels.
If all channels have been deactivated, time and date are displayed in the normal display
mode. These entries are immediately effective and need not be acknowledged.
ECL command: ONOFF
Channel Start/Stop
The acceptance of meter pulses at a given input is controlled with the Start/Stop
function. A channel which has been created by means of t “differential linking” can be
influenced with the Start/Stop function in an analog fashion. Since the binary input
status of the channel is not influenced, undesired counting of binary data can, for
example, be avoided with this function. These entries are immediately effective and
need not be acknowledged. ECL command: STARTSTOP (STSP)
(Channel) Mode
(Channel) Visible
Содержание U1601
Страница 1: ...U1601 U1602 U1603 Summators Energy Control System ECS 3 348 869 03 15 1 21 Operating Instructions ...
Страница 11: ...Gossen Metrawatt GmbH 11 ECS LAN Sample Network ...
Страница 73: ...Gossen Metrawatt GmbH 73 13 Functions Overviews Functions Overview U1601 ...
Страница 74: ...74 Gossen Metrawatt GmbH Functions Overview U1602 ...
Страница 75: ...Gossen Metrawatt GmbH 75 Functions Overview U1603 ...
Страница 79: ...Gossen Metrawatt GmbH 79 ...