Operating Instructions

Passive
DC signal isolator
SINEAX TI 816

TI 816-5 Be

996 118 5000-10.00

Aargauerstrasse 7
CH-5610 Wohlen/Switzerland
Phone +41 56 618 21 11
Fax +41 56 618 24 58
e-mail: [email protected]
http://www.gmc-instruments.com

3. Brief description

The signal isolator SINEAX TI 816 serves to electrically insulate 

an

 analogue DC

signal in the range 0...20 mA which depending on version is then converted to a
current or voltage signal (0...20 mA or 0...10 V). It does 

not

 require a separate power

supply.

Fig. 1

1

 With current signal

2

 With voltage signal

Safety precautions to be
strictly observed are marked
with following symbols in the
operating instructions:

The instrument fulfils all the important requirements and regulations concerning
electromagnetic compatibility 

EMC 

and 

Safety 

(IEC 1010 resp. EN 61 010). It was

developed and is manufactured and tested in strict accordance with the 

quality

assurance standard

 ISO 9001.

4. Versions

There are two versions of the DC signal isolator SINEAX TI 816 available.

Description

Output

Order code

Order No.

signal A

Passive 

DC signal isolator

input signal E: 0…20 mA,

0…20 mA

816-5110

990 722

with 1 isolation and
transmission channel, in
carrying rail housing N12

0…10 V

816-5111

994 089

5. Technical data

Input signal E  

DC current:

0…20 mA

Max. permissible current:

50 mA

Voltage limiter:

18 V 

±

 5% (with zener diode)

Voltage drop:

< 2 V (for 500 

 burden)

Overshoot:

< 20 

µ

A (typical 5 

µ

A)

Output signal A  

DC current 

or

DC voltage:

0…20 mA 

or 

0…10 V

Limit:

Approx. 30 mA

1

Approx. 15 V

2

Max. burden:

600 

1

Internal resistance:

500 

2

Residual ripple:

< 20 mV ss

Time constant:

Approx. 5 ms

Accuracy data

Error limits:

±

 0,1%

1

(reference value 20 mA,
linearity error included)

±

 0,2%

2

(reference value 10 V,
linearity error included)

Ambient conditions

Operating temperature::

–20 to + 65 

°

C

Storage temperature:

–40 to + 85 

°

C

Annual mean
relative humidity:

 75% Standard climatic rating

Seismic test:

5 g, < 200 Hz, 2 h in each of 3 directions

Shock test:

50 g,

 10 shocks in each of 3 directions

Contents

  1. Read first and then … .................................................................................... 1
  2. Scope of supply ............................................................................................. 1
  3. Brief description ............................................................................................ 1
  4. Versions ......................................................................................................... 1
  5. Technical data ............................................................................................... 1
  6. Mounting ........................................................................................................ 2
  7. Electrical connections ................................................................................... 2
  8. Commissioning and maintenance ................................................................. 2
  9. Releasing the signal isolator .......................................................................... 2
10. Dimensional drawings ................................................................................... 2

1. Read first and then …

The proper and safe operation of the device assumes that
the operating instructions is 

read carefully

 and the safety

warnings given in the various Sections

6. Mounting

7. Electrical connections

are 

observed.

The device should only be handled by appropriately trained
personnel who are familiar with it and authorised to work
in electrical installations.

2. Scope of supply

Signal isolator

 (Fig. 1)

1 ea. operating instructions (Fig. 2) in English, French, German

Fig. 2