Parameters Configuration
X1 = lower range limit, X2 = upper range limit, MR = X2 – X1
Parameter
Display
Range
Default
Comment
Upper limit value for relay A1
oFF, 1 ... MR
oFF, X1 ... X2
oFF
oFF
Relative (= default config.)
Absolute
Lower limit value for relay A1
Upper limit value for relay A2
Lower limit value for relay A2
Setpoint 2
SPL
...
SPH
X1
Ramp for rising setpoints
oFF, 1 ... MR per min.
oFF
Ramp for falling setpoints
oFF, 1 ... MR per min.
oFF
Heating current setpoint
(see Balancing)
Auto, oFF, 0.1 ...
A H
oFF
Not with step-action control-
lers
1)
Proportional band heating
0.1 ... 999.9%
10.0
Proportional band cooling
0.1 ... 999.9%
10.0
Only with 3-step controllers
2)
Dead band
0 ... MR
0
Not with 2-step controllers
3)
Path delay time
0 ... 9999 s
100
Read-out cycle time
0.5 ... 600.0 s
10.0
4)
Motor run-time
5 ... 5000 s
60
Only with step-action control-
lers
5)
Switching hysteresis
0 ... 1.5% MR
0.5%MR
For limit value monitoring and
limit transducers
Maximum setpoint
SPL
... X2
X2
Minimum setpoint
X1 ...
SPH
X1
Maximum manipulating factor
–100 ... 100 %
100
Actual value correction
(see Balancing)
(Auto), –MR/4 ... +MR / 4
0
Only with designations B1,
B3 and B4
Decimal point position
9999, 999
•
9, 99
•
99, 9
•
999 9999
Only with designation B2
Upper range limit, standard signal
rn L
... 9999
100
Only with designations
B2, B4, A7 and A8
Lower range limit, standard signal
–1500 ...
rn H
0