GMC-I Messtechnik GmbH
R2500–33
Manual Optimization
Parameters
Pb I
,
Pb II
,
tu
and
tc
are determined by means of manual optimization in order to maintain optimized controller dynamics. A start-up test or
an oscillation test is performed to this end.
Preparation
–
Complete configuration
(page 14) and
parameter settings
(page 27) must first be performed for use of the controller.
–
Deactivate the program controller
, because a constant setpoint is required for the optimization procedure.
– The actuators should be deactivated with the
Off
or
Manual Operation
function (page 13).
– A
recorder
must be connected to the sensor and adjusted appropriately to prevailing circuit dynamics and the setpoint.
– For 3-step or split range controllers, on and off time of the switching output for heating or the continuous output must be recorded (e.g. with an
additional recorder channel or a stopwatch).
– Configure
limit transducer
(
Cout
=
OnOF
).
– Set read-out cycle time to the minimum value:
tc
=
0.1
.
– If possible, deactivate manipulating factor limiting:
Y H
=
100
.
– Reduce (or increase) the
setpoint
so that overshooting and undershooting do not cause any impermissible values.
Performing the Start-Up Test
–
dbnd
=
MRS
Setting for 3-step and split range controllers (switching output for cooling may not be triggered)
dbnd
=
0
Setting for step-action controllers (switching output for cooling must be triggered)
– Start the recorder.
– Activate the actuators with
Automatic Operation
.
– Record two overshoots and two undershoots.
Actuation test is now complete for 2-step, continuous-action and step-action
controllers. Continue as follows for 3-step and split range controllers:
– Set
dbnd
to
0
in order to cause further overshooting with active switching output for cooling. Record two overshoots and two undershoots.
– Record
on-time T
I
and
off-time T
II
for the last oscillation at the switching output for cooling or the continuous output.