07 Battery Parameters
User Manual V1.0-2022-02-18
6.5 Battery Module Power Off
Technical Data
LX F6.6-H
LX F9.8-H
LX F13.1-H
LX F16.4-H
Usable Energy (kWh)
*1
6.55
9.83
13.10
16.38
Battery Module
LX F3.3-H
:
102.4V 3.27kWh
Number of Modules
2
3
4
5
Cell Type
LFP(LiFePO4)
Cell Configuration
64S1P
96S1P
128S1P
160S1P
Nominal Voltage (V)
204.8
307.2
409.6
512
Operating Voltage Range (V)
182.4~230.4
273.6~345.6
364.8~460.8
456~576
Nominal Dis-/Charge Current (A)
*2
25
Nominal Discharge Power (kW)
*2
5.12
7.68
10.24
12.80
Follow the steps to power off the Battery System to avoid the System be damaged.
Method 1:
1. Press the button for at least 15s.
2.
Make sure that both the SOC indicator and the button indicator of the control unit are off.
Method 2:
1.
Turn off the air switch.
2.
Make sure that both the SOC indicator and the button indicator of the control unit are off.
Steady Red
Relay Fault
Restart the battery. If the problem persists,
please contact the after-sales service.
Circuit Breaker Fault
Restart the battery. If the problem persists,
please contact the after-sales service.
Insulation Fault
Do not touch the battery, and contact the
after-sales service.
Internal
Communication Fault
Power off and check the COM cable. Restart
the battery. If the problem persists, contact
the after-sales service.
SN Fault
Contact the after-sales service.
Voltage Balance Fault
Restart the battery. If the problem persists,
contact the after-sales service.
Inconsistent Master
and Slave
Restart the battery. If the problem persists,
contact the after-sales service.
Temp. Sensor Fault
Restart the battery. If the problem persists,
contact the after-sales service.
Others
Contact the after-sales service.
07 Battery Parameters